Brand:

JUMO ecoTRANS Lf 02 202731/02-016/000 Conductivity Switch

Description

If a plant only needs to raise an alarm or switch a valve when conductivity crosses a threshold, a full transmitter is more than the job requires. JUMO 202731/02-016/000 is the relay-output half of the ecoTRANS Lf 01/02 pair: a narrow DIN-rail conductivity switching device with a changeover contact, a teach-in connector that sets the trip point from the live measurement, and a factory range of 0 to 20 mS/cm for a cell with K = 1.0 per cm. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer; this text is a paraphrase of the JUMO datasheet 202731.

Key idea behind 202731/02-016/000

The datasheet describes the Lf 01 as a freely configurable analog transmitter and the Lf 02 as the unit with a changeover relay, aimed at general water engineering. The relay version can automatically define its switching point through the teach-in connector, so a commissioning technician can bring the cell to the desired concentration, plug in the connector, and let the module memorize the threshold, which avoids typing a value. Typical areas are freshwater monitoring and treatment, reverse osmosis, ion exchangers, condensate monitoring and cooling water checks.

Reading the order code 202731/02-016/000

The base 202731 is the Lf 01/02 family. The first number after the slash chooses the output: 01 is the analog output and 02, used here, is the relay. The block 016 selects the measuring range 0 to 20 mS/cm for K = 1.0 per cm, the standard range set at the factory for the relay type, whereas 015 means 0 to 2 mS/cm and is the factory range for the analog type. The suffix 000 means without options; 024 would include the PC setup software. The part number for this stock code is 00421032, with shipment stated as three working days after receipt of order.

Technical data for 202731/02-016/000

Feature Datasheet statement
Output Relay, changeover contact, 4 A at 250 V AC or 4 A at 24 V DC resistive
Contact life more than 100,000 operations at rated load
Factory range 0 to 20 mS/cm with K = 1.0 per cm
Other ranges by software 0 to 5 microsiemens per cm up to 0 to 200 mS/cm, depending on cell constant
Temperature input Pt100 or Pt1000, 2- or 3-wire, minus 10 to plus 250 degrees Celsius, or customised NTC/PTC up to 4500 ohms
Reference temperature 10 to 40 degrees Celsius
Supply 20 to 30 V DC, 2 W, reverse-polarity protected
Housing Polycarbonate, 22.5 mm wide, DIN rail, approx. 110 g, IP20
Ambient minus 10 to plus 60 degrees Celsius operating
Display of state one two-colour LED, red or green

How 202731/02-016/000 differs from 202731/01-015/000 and the Lf 03

The analog sibling 202731/01-015/000 has no relay but a galvanically isolated 0(4) to 20 mA or 0(2) to 10 V output and a 0 to 2 mS/cm default range; its part number is 00421026, and the 024 version with software is 00421035. The larger ecoTRANS Lf 03 of data sheet 202732 adds a display, two analog outputs and USP 645 functions. 202731/02-016/000 has neither a display nor an analog signal: it is a switch with a status LED, which is its advantage in cost and panel space.

Relay logic and calibration

The relay can be programmed as a limit with differential, as a pulse function, and with pull-in and drop-out delay. Calibration includes the cell constant, by manual entry within 20 to 500 percent or by automatic calibration, and the temperature coefficient. Measuring circuit monitoring covers out-of-range conditions and temperature probe short circuit or break, and the unit places the relay in a configurable state in a fault.

Installation and commissioning

Snap the unit on a 35 mm rail, wire the cell using the connection table for plug-in heads to DIN 43650 or the M12 connector, connect the temperature probe on terminals 4 to 6 in 2- or 3-wire circuit, and supply 24 V DC. The datasheet shows the PS5R-A-24 switching power supply as an accessory with part number 00374661. Programming needs the setup cable and the Lf 01/02 setup program, part number 00432577 for the software and 00456352 for the interface.

Maintenance of 202731/02-016/000

Inspect the cell for fouling and check the relay function when the plant is shut down. Because a conductivity simulator is available from the accessories, a loop test does not require a process excursion. Keep the stored teach-in threshold documented.

Sizing a threshold alarm with 202731/02-016/000

A conductivity switch is only as good as its set point. For a reverse-osmosis permeate alarm the trip point is normally a small multiple of the normal permeate reading; for a cooling-tower blowdown valve it is a stated cycle of concentration; for a condensate return line it is the contamination limit that protects the boiler. With a factory span of 0 to 20 mS/cm, 202731/02-016/000 is better suited to higher-conductivity services than to ultrapure water, and the datasheet shows lower ranges, down to 0 to 5 microsiemens per cm with a K = 0.01 cell, if the setup program is used to change the range. Use the hysteresis (the limit with differential) so that the valve does not chatter around the threshold, and a pull-in delay to ignore short air bubbles that can pass the cell. For critical alarms, wire the relay so that a power loss or a fault state drives the plant to its safe position.

Because the unit holds its configuration in EEPROM, a replacement of the same order code can be configured in minutes with the saved setup file, or re-taught on the plant.

Documents and quotation

The JUMO 202731 datasheet is attached. For a quotation on 202731/02-016/000, send the order code, the quantity and your delivery location in Oman or the GCC with your RFQ.

Other Models in the EcoTRANS Lf Conductivity Transmitters Range

Seven Star LLC supplies models from the EcoTRANS Lf Conductivity Transmitters range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
JUMO ecoTRANS Lf 03 202732/888-888-101/000 TransmitterLiquid Analytical SystemsView details
JUMO ecoTRANS Lf 02 202731/02-016/000 Conductivity SwitchLiquid Analytical SystemsYou are viewing this model
Datasheets & Documents
  • PDF Datasheet JUMO ecoTRANS Lf 02 202731/02-016/000 Conductivity Switch Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.

Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.

JUMO company profile

Established 1948, Fulda, Germany, by Moritz Kurt Juchheim
First products Glass and contact thermometers; platinum glass sensors from 1966
Ownership Family-owned; renamed JUMO GmbH & Co. KG in 2003
Product families RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments

Milestones

  • 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
  • 1966: Platinum glass temperature sensors are added.
  • 2003: The parent company is renamed JUMO GmbH & Co. KG.

JUMO products we list

Family Models Typical use
RTD and thermocouple probes 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp Temperature measurement in pipes, vessels, machines, HVAC and food plants
Thermowells and inserts 909710 thermowells, 909740 measuring inserts Protecting sensors and replacing them without opening the process
Temperature transmitters dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch Converting sensor signals to 4-20 mA, HART or IO-Link
Pressure and level dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 Pressure in process, hydraulic and OEM systems; tank and well level
Controllers, limiters and recorders DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T Furnace, oven and process control, over-temperature protection and recording
Liquid analysis and flow AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 pH, conductivity, oxygen and turbidity in water treatment; liquid flow

Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.

Where JUMO products are used

In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.

Ordering JUMO products: what we need

Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.

Facts checked against JUMO's company history, October 2026.

FAQ

Questions about the JUMO ecoTRANS Lf 02 202731/02-016/000 Conductivity

Answers from our engineering team on installation, compatibility and integration.

01What is the factory range of 202731/02-016/000?
The relay type is shipped with 0 to 20 mS/cm for a cell constant K = 1.0 per cm, and the range can be changed in the setup program within the cell-constant limits.
02What is teach-in on 202731/02-016/000?
The Lf 02 relay version can automatically define its switching point through the teach-in connector, so the live measured value is memorised as the threshold.
03How much can the relay of 202731/02-016/000 switch?
The changeover contact is rated 4 A at 250 V AC or 4 A at 24 V DC with resistive load, and the datasheet states a contact life of more than 100,000 operations.
04Does 202731/02-016/000 have a display or analog output?
No. It has one two-colour LED for operating states and the relay; the analog output belongs to the Lf 01 type, such as 202731/01-015/000.
05What power does 202731/02-016/000 need?
It needs 20 to 30 V DC with ripple below 5 percent, power consumption of 2 W and reverse-polarity protection, for SELV or PELV circuits.