Brand:

JUMO ecoTRANS Lf 03 202732/888-888-101/000 Transmitter

Description

JUMO 202732/888-888-101/000 is the ecoTRANS Lf 03 conductivity and resistivity transmitter in its relay-output stock configuration. It reads an electrolytic conductivity cell, compensates for temperature, drives two isolated analog outputs and closes a changeover relay, all inside a 35 mm DIN-rail housing. What sets the Lf 03 apart from simpler conductivity modules is the high-purity-water support: it can show resistivity in megohm-centimetres, switches in line with the USP 645 pharmacopoeia logic, and accepts cells from K = 0.01 up to K = 10. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Where 202732/888-888-101/000 is used

The datasheet names freshwater monitoring, water-treatment plants, reverse osmosis, ion exchangers, high-purity water, pharmaceutical applications, condensate monitoring, rinse baths and cooling water. In Oman and the GCC that points to desalination permeate lines, boiler feed and condensate return on power and cogeneration stations, demineralization skids at refineries and petrochemical sites, and purified-water loops in pharmaceutical and hospital facilities. The relay version fits plants where a dump valve or a high-conductivity alarm has to be driven directly.

Decoding the code 202732/888-888-101/000

After the 202732 type number, the first block 888 stands for the standard setting of output I (conductivity or resistivity) and the second 888 for output II (temperature), both left at factory defaults and later reprogrammable from the PC setup program. The third block selects the switching output hardware: 101 is the relay with a changeover contact, 177 is two open-collector outputs. The ending 000 means without setup software, while 024 adds it. The datasheet gives the part number 00441865 for this stock code. Stock deliveries are described as three working days after receipt of order.

Technical data for 202732/888-888-101/000

Item Datasheet value
Measured variable Conductivity or resistivity plus temperature
Cell constants K = 0.01, 0.1, 1, 3 and 10 per cm
Ranges 0 to 1 microsiemens per cm up to 0 to 200 millisiemens per cm, depending on cell constant
Temperature range minus 10 to plus 250 degrees Celsius
Reference temperature settable 10 to 40 degrees Celsius, default 25
Compensation natural water EN 27888, ASTM D 1125-95, linear
Analog outputs two, 0(2) to 10 V or 0(4) to 20 mA, isolated
Relay SPDT, 8 A at 250 V AC or 24 V DC resistive
Supply 20 to 30 V DC, up to 3 W
A/D and sampling 14 bit, 500 ms
Protection and weight IP20, approx. 150 g

How 202732/888-888-101/000 differs from other ecoTRANS Lf variants

Versus the Lf 01 and Lf 02 types of data sheet 202731, which split the job between an analog-only Lf 01 and a relay-only Lf 02 with a 4 A changeover contact and teach-in connector, and draw 2 W, this Lf 03 offers two parallel analog outputs, a stronger 8 A relay, resistivity display, temperature probes in 2-, 3- or 4-wire circuits including NTC and KTY types, and USP 645 switching. Compared with its own siblings, 202732/888-888-177/000 replaces the relay by two open-collector outputs (contact rating 100 mA at 35 V DC), and the 024 variant bundles the setup software.

Pharmaceutical and high-purity functions

The USP function evaluates the measured conductivity without temperature compensation against the permitted value for the actual temperature, and raises an alarm or pre-alarm. The cell constant can also be corrected by manual entry in the range 20 to 500 percent or by automatic calibration, a feature useful for cells with a small K that drift with age. The supplied calibration certificate documents the instrument and calibration data.

Installation and commissioning

Mount on the 35 mm rail, wire the cell to terminals 13 and 14 (inner and outer electrode on coaxial cells), connect the Pt100 or Pt1000 on terminals 9 to 12 in the required wiring, and supply 24 V DC from a SELV or PELV source with reverse-polarity protection. Select the measuring range matching the cell constant from the datasheet table, set the reference temperature, and then calibrate. A conductivity simulator from the accessories list helps dry commissioning, and the binary behaviour of the relay can be inverted.

Maintenance of 202732/888-888-101/000

Re-check the cell constant at regular intervals, watch the calibration timer, and keep a record of the configuration saved from the setup program to restore it quickly after a replacement. Long cell cables influence the result above 20 millisiemens per cm, a limitation stated in the datasheet.

Choosing the cell constant for 202732/888-888-101/000

The datasheet lists 17 combinations of cell constant and range, and the choice drives accuracy. For ultrapure water below 20 microsiemens per cm, K = 0.01 per cm is the right cell and the display can be switched to resistivity, up to 99.99 megohm-centimetres; for drinking water and permeate from 100 up to 1000 microsiemens per cm, K = 0.1 or K = 1 per cm is common; for brine, cooling water with high cycles of concentration or process liquids up to 200 millisiemens per cm, K = 10 per cm is used. Because the instrument stores the cell constant and the temperature coefficient, which is selectable between natural water, high-purity water and a linear coefficient, one 202732/888-888-101/000 module can serve many different loops after reprogramming.

Plan the cable between cell and module carefully. The datasheet notes that long cables influence ranges above 20 millisiemens per cm and offers a lead compensation setting, so keep the run short, use the cable specified for the cell, and avoid routing it next to contactors.

Documents and quotation

The JUMO 202732 datasheet is attached to this page. For a quotation on 202732/888-888-101/000, send the full order code, the quantity and your delivery location in Oman or the GCC through the RFQ form.

Documentation and Compliance

Industrial buyers often need more than the hardware. When you order the JUMO 202732/888-888-101/000, tell us which documents your project or quality team requires, such as certificates of origin, conformity declarations, calibration or test records, or hazardous-area certificates where the variant carries them. Mentioning these at the enquiry stage avoids delays at customs and at goods receipt on site. For tenders and project packages, we can also align the quotation with your line-item format so that JUMO liquid analytical systems items can be checked against the bill of materials quickly.

Other Models in the EcoTRANS Lf Conductivity Transmitters Range

Seven Star LLC supplies models from the EcoTRANS Lf Conductivity Transmitters range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
JUMO ecoTRANS Lf 03 202732/888-888-101/000 TransmitterLiquid Analytical SystemsYou are viewing this model
JUMO ecoTRANS Lf 02 202731/02-016/000 Conductivity SwitchLiquid Analytical SystemsView details
Datasheets & Documents
  • PDF Datasheet JUMO ecoTRANS Lf 03 202732/888-888-101/000 Transmitter Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.

Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.

JUMO company profile

Established 1948, Fulda, Germany, by Moritz Kurt Juchheim
First products Glass and contact thermometers; platinum glass sensors from 1966
Ownership Family-owned; renamed JUMO GmbH & Co. KG in 2003
Product families RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments

Milestones

  • 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
  • 1966: Platinum glass temperature sensors are added.
  • 2003: The parent company is renamed JUMO GmbH & Co. KG.

JUMO products we list

Family Models Typical use
RTD and thermocouple probes 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp Temperature measurement in pipes, vessels, machines, HVAC and food plants
Thermowells and inserts 909710 thermowells, 909740 measuring inserts Protecting sensors and replacing them without opening the process
Temperature transmitters dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch Converting sensor signals to 4-20 mA, HART or IO-Link
Pressure and level dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 Pressure in process, hydraulic and OEM systems; tank and well level
Controllers, limiters and recorders DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T Furnace, oven and process control, over-temperature protection and recording
Liquid analysis and flow AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 pH, conductivity, oxygen and turbidity in water treatment; liquid flow

Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.

Where JUMO products are used

In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.

Ordering JUMO products: what we need

Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.

Facts checked against JUMO's company history, October 2026.

FAQ

Questions about the JUMO ecoTRANS Lf 03 202732/888-888-101/000

Answers from our engineering team on installation, compatibility and integration.

01What does the 101 in 202732/888-888-101/000 select?
The third code block 101 selects a relay output with changeover contact, whereas 177 gives two open-collector outputs; both are stock versions with part numbers 00441865 and 00441866.
02Which cells can 202732/888-888-101/000 connect to?
Electrolytic conductivity cells with cell constants K = 0.01, 0.1, 1, 3 and 10 per cm, giving ranges from 0 to 1 microsiemens per cm to 0 to 200 millisiemens per cm.
03Does 202732/888-888-101/000 support pharmaceutical water monitoring?
Yes. It has a USP 645 switching function with alarm and pre-alarm, uses measurement without temperature compensation for that function, and can display resistivity in megohm-centimetres.
04What supply does 202732/888-888-101/000 need?
The supply is 20 to 30 V DC with ripple below 5 percent, power consumption up to 3 W, with reverse polarity protection and operation on SELV or PELV circuits only.
05Which temperature sensors work with 202732/888-888-101/000?
Pt100, Pt1000, and NTC or KTY style probes through a customer-specific characteristic, wired in 2-, 3- or 4-wire circuit, with temperature range minus 10 to plus 250 degrees Celsius.