Brand: Yokogawa
Yokogawa FLXA202 2-Wire Liquid Analyzer
Description
Yokogawa FLXA202 overview: 2-wire analyzer for pH/ORP, conductivity and dissolved oxygen
The Yokogawa FLXA202 is a 2-wire analyzer from the FLEXA series that offers single or dual sensor measurement. The modular design provides four kinds of measurement, pH/ORP, contacting conductivity (SC), inductive conductivity (ISC) and dissolved oxygen (DO), depending on the sensor module fitted.
In addition to conventional analog sensor connections, the Yokogawa FLXA202 can use digital sensors through the SA11 SENCOM smart adapter. Dual sensor operation allows calculated data and a redundant arrangement in which the output switches to the second sensor if the main sensor fails.
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. We list FLXA202 so that maintenance, instrumentation and procurement teams can quote the exact model code that appears in the manufacturer documentation.
Key features of FLXA202
- Four measurements: pH/ORP, contacting conductivity, inductive conductivity and dissolved oxygen.
- Dual sensor measurement for same-type analog sensors (pH/ORP with pH/ORP, SC with SC, DO with DO), with calculated data and redundancy.
- Touch screen operation with a simple menu structure in 12 languages and a quick setup menu.
- Automatic recognition of the installed sensor module.
- Sensor wellness indication, diagnostics and a logbook of events.
- One 4 to 20 mA DC output with bi-directional HART communication, loop powered.
- Aluminum alloy cast enclosure with epoxy coating, IP66 and NEMA Type 4X protection.
FLXA202 technical specifications
The table below lists values published by the manufacturer for the product family of FLXA202. Where a value depends on the ordered configuration, the model and suffix code table in the General Specifications governs.
| Parameter | Value |
|---|---|
| Model | FLXA202 2-wire analyzer |
| Measurements | pH/ORP, SC, ISC, DO (by sensor module) |
| Sensor inputs | One or two sensor modules |
| Output | One output of 4 to 20 mA DC, tolerance plus or minus 0.02 mA, with HART |
| Burnout (without HART) | Down 3.6 mA; up 22 mA, NAMUR NE43 compliant |
| Power supply, one module | 16 to 40 V DC (analog sensor); 17 to 40 V DC (ISC); 21 to 40 V DC (with SENCOM smart adapter) |
| Power supply, two modules | 22.8 to 40 V DC (analog sensors) |
| Display | LCD with touch screen, 12 message languages |
| Enclosure | Aluminum alloy cast with epoxy coating, IP66 (except Canada), NEMA Type 4X |
| Cable entries | M20 cable gland, 3 pieces |
Typical applications of FLXA202 in Oman and the GCC
- Conductivity monitoring of boiler feedwater, condensate and cooling water in power plants.
- pH and ORP control in effluent, dosing and neutralisation systems.
- Dissolved oxygen measurement in deaerators and wastewater aeration.
- Desalination pre-treatment and post-treatment water quality monitoring.
- Redundant dual-sensor measurement on critical quality loops.
Water and process-liquid analysis is important across Oman and the GCC, where desalination, power-plant water treatment, effluent and wastewater, and industrial cooling circuits all depend on reliable pH, conductivity and dissolved-oxygen readings. A two-wire analyzer such as FLXA202 is attractive because it needs only the 4 to 20 mA loop for power and signal, which simplifies cabling in outdoor installations exposed to heat and dust.
Selection and compatibility notes for FLXA202
The FLXA202 is the 2-wire analyzer with a touch screen and dual-sensor capability; the FLXA21 is a related 2-wire model on the same platform. Choose the sensor module for pH/ORP, SC, ISC or DO and the sensors to match, and state whether HART communication is needed.
Choose FLXA202 together with its sensor: decide which measurement you need (pH or ORP, contacting conductivity, inductive conductivity or dissolved oxygen), whether one or two sensor inputs are required, and whether HART communication or a digital smart adapter is wanted. The sensor modules and options appear as codes in the manufacturer General Specifications, and we use that table to confirm the complete configuration before quoting.
Installation and commissioning
Mount the analyzer on a pipe or wall with the supplied hardware, connect the sensor cables through the glands, supply 16 to 40 V DC on the loop and close the enclosure properly. When HART multi-drop mode is used, the output starts at 4 mA after power-on, so provide enough power for the connected instruments.
Mount the analyzer on a pipe or wall with the supplied hardware, route the sensor cable through the glands with the correct shielding, connect the loop within the stated supply voltage range and keep the enclosure covers closed and sealed after wiring. Let the sensor stabilise in the process, then run the calibration routine described in the manual and record the first calibration values.
Maintenance, calibration and service
Use the sensor wellness indicator and the logbook to schedule calibration and cleaning. Calibrate against standard solutions suited to the measurement.
Maintenance is dominated by the sensor: clean and calibrate it at the interval set by your process experience, review the sensor-wellness and diagnostic indications, and keep the logbook of events as evidence for quality audits. Inspect the enclosure seals and cable glands for ingress, and keep spare sensors or electrolyte on site for critical loops.
Related products and ordering notes for FLXA202
- FLXA21 2-wire analyzer, conductivity sensors and pH sensors from the same manufacturer.
- Mounting hardware and sensor holders.
When you request FLXA202, tell us whether the item is for a new installation, a like-for-like replacement or a spares stock, because that changes which accessories and documents are worth adding to the same quotation. We can also check related codes so that a single RFQ covers the instrument and the parts that go with it.
Frequently asked questions about FLXA202
- What does FLXA202 measure? FLXA202 measures pH/ORP, contacting conductivity, inductive conductivity or dissolved oxygen depending on the sensor module.
- Is FLXA202 loop powered? Yes. It is a 2-wire analyzer with a nominal 24 V DC loop, requiring 16 to 40 V DC for one analog sensor module.
- Can FLXA202 use two sensors? Yes, two sensor modules of the same analog type can be used for dual measurement, calculated data and a redundant system.
- What communication does FLXA202 have? It has one 4 to 20 mA output with bi-directional HART communication.
- How do I order FLXA202? Send Seven Star LLC the measurement type, sensor modules and sensors, quantity and delivery location and we will quote in writing.
Documents and quotation
The manufacturer General Specifications for the family of FLXA202 is available and we can send it with your quotation. To request pricing and lead time, send an RFQ to Seven Star LLC with the part number FLXA202, the quantity, the full model and suffix code or the nameplate details of the unit being replaced, the delivery location and any certificate requirements. We will confirm availability and reply in writing with a quotation for FLXA202.
Datasheets & Documents
- Datasheet Yokogawa FLXA202 2-Wire Liquid Analyzer Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.
Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.
Yokogawa at a glance
| Established | 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki |
|---|---|
| Milestones | Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986 |
| Headquarters | Tokyo, Japan |
| Product families | Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers |
Yokogawa products we list
| Family | Models | Typical use |
|---|---|---|
| Pressure and DP transmitters | EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable | Pressure, level and DP flow measurement in process plants |
| Temperature transmitters | YTA610, YTA710 | RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus |
| Flowmeters | ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 | Water and conductive liquids, mass flow of hydrocarbons, steam and gas |
| Analysers | TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover | Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen |
| Controllers and recorders | UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 | Single-loop control, furnace programs and data recording |
| Control and safety systems | CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 | Spares and expansions for CENTUM DCS, safety systems and STARDOM |
| Battery packs | S9129FA, S9185FA, S9548FA | Memory backup batteries for DCS and controller modules |
The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.
Where Yokogawa products are used
In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.
Ordering Yokogawa products: what we need
Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.
Facts checked against Yokogawa's corporate history, October 2026.
Browse Yokogawa products by category: PLC & I/O Cards, Flowmeters, Pressure Instrumentation, Automation Accessories, Temperature Instrumentation.
FAQ
Questions about the Yokogawa FLXA202 2-Wire Liquid Analyzer
Answers from our engineering team on installation, compatibility and integration.
01What does FLXA202 measure?
FLXA202 measures pH/ORP, contacting conductivity, inductive conductivity or dissolved oxygen depending on the sensor module.
02Is FLXA202 loop powered?
Yes. It is a 2-wire analyzer with a nominal 24 V DC loop, requiring 16 to 40 V DC for one analog sensor module.
03Can FLXA202 use two sensors?
Yes, two sensor modules of the same analog type can be used for dual measurement, calculated data and a redundant system.
04What communication does FLXA202 have?
It has one 4 to 20 mA output with bi-directional HART communication.
05How do I order FLXA202?
Send Seven Star LLC the measurement type, sensor modules and sensors, quantity and delivery location and we will quote in writing.