Brand:

Yokogawa S9185FA Battery Pack

Description

Overview

The Yokogawa S9185FA Battery Pack is an essential industrial power backup component used in Yokogawa automation and control systems, especially in Distributed Control Systems (DCS) and PLC environments such as the ProSafe-RS safety control units. It delivers stable 3.6 V DC output to back up the processor module’s storage memory during power interruptions. 

Manufactured to meet the demanding requirements of process control facilities, manufacturing plants, and utility infrastructure applications, this primary battery pack ensures that vital automation components remain operational and protected against unexpected power loss. It is commonly installed directly on boards or as a replaceable backup battery in power modules where ongoing data integrity is paramount. 

Battery Construction & Chemistry

The S9185FA battery pack typically uses a lithium thionyl chloride (Li-SOCl₂) chemistry, providing:

  • Long shelf life and high energy density suitable for industrial control applications. 

  • Defined replacement interval: Yokogawa recommends replacing the battery every 3 years at an average ambient temperature of 30 °C or less. 

  • Non-rechargeable design focusing on safety and memory backup reliability. 

This battery technology is chosen for industrial applications because it resists self-discharge better than many alternatives, retains charge for extended durations, and supports long-term backup without frequent replacements. 

Key Functional Benefits

The Yokogawa S9185FA Battery Pack offers several advantages for industrial control systems:

  • Reliable Backup Power: Backs up the processor module’s management information held in storage memory during power outages. 

  • Reduced Downtime Risk: Protects against data loss, system resets, and unscheduled process disruptions. 

  • Industrial-Grade Design: A non-rechargeable primary cell intended for memory backup in industrial control equipment. 

  • Direct Replacement: Specified by Yokogawa as the memory-backup battery of the SCP461 processor module (ProSafe-RS), including S2SC70S/S2SC70D units fitted with SCP461. The S2CP471 processor module uses a different battery, S9450FE. 

Typical Industrial Applications

This backup battery pack is critical in automation systems where reliable power retention ensures safety and continuity:

  • Process control systems in chemical, oil & gas, power generation, and refining sectors. 

  • Distributed Control Systems (DCS) and PLC logic modules requiring memory backup. 

  • Manufacturing automation installations where loss of controller data can halt production. 

  • Utility and infrastructure automation where continuous system uptime is mandatory. 

By providing stable backup power, the S9185FA plays a key role in minimizing system failures, upholding process integrity, and supporting high-availability control architectures.

Chemistry and Transport Classification

Yokogawa’s own safety documentation for this battery confirms a lithium thionyl chloride cell chemistry (containing thionyl chloride and aluminium chloride as active materials), consistent with the long-shelf-life, high-energy-density lithium primary cells widely used across the industry for DCS/PLC memory-backup duty. As a lithium metal cell, the S9185FA is classified under UN 3090 for transport as a dangerous good, which affects how replacement units must be packaged, labeled, and shipped — a detail that matters for GCC customers ordering spares internationally, since improperly declared lithium battery shipments can be delayed or refused by couriers and customs.

Technical Specifications

Parameter Value
Manufacturer Yokogawa
Part Number S9185FA
Product Type Backup battery pack (3.6 V lithium primary cell)
Output Voltage 3.6 V DC
Design Non-rechargeable (primary)
Compatible Systems Yokogawa ProSafe-RS safety control units: SCP461 processor module, including S2SC70S/S2SC70D units fitted with SCP461 (S2CP471 uses battery S9450FE), per Yokogawa General Specifications
Chemistry Thionyl chloride lithium (primary cell), per Yokogawa SDS
Quantity per Unit 1 pc for S2SC70S; 2 pcs for S2SC70D (processor module is delivered without battery)
Recommended Replacement Cycle 3 years at an average ambient temperature of 30 °C or less
Transport Classification UN 3090 Lithium batteries, Class 9, Packing Group II (UN 3091 when contained in or packed with equipment)
Conditions to Avoid Heat above 70 °C, incineration, crushing, piercing, disassembly, recharging, short circuit, long exposure to humidity
Storage Cool, dry, well-ventilated area away from water, heat and ignition sources
Fire Fighting Dry agent; do not use water

Replacement and Handling Notes

Because this is a non-rechargeable primary cell dedicated to memory backup, it should be replaced on a preventive schedule rather than waited out until failure, since a fully depleted backup battery risks loss of controller configuration and time-stamped data during any subsequent power interruption to the host card. As with all lithium primary cells, used units should be disposed of through a proper battery-recycling/hazardous-waste channel rather than general waste, and replacement should only be performed with the system powered down per Yokogawa’s maintenance procedure for the specific card or module involved, to avoid disturbing other battery-backed circuits on the same board.

Why Backup Battery Health Matters

A backup battery in a DCS or PLC card is easy to overlook precisely because it does nothing visible while the system is running normally on mains power — its role only becomes critical the moment external power is interrupted. If the backup cell has already been depleted by that point, a card can lose its stored configuration, calibration parameters, or time-stamped historical data, turning a brief power blip into a much longer recovery effort involving reconfiguration or re-commissioning of the affected module. For process plants where the automation system is expected to run for years between planned shutdowns, tracking battery age and replacing on a preventive interval is a small, low-cost safeguard against a disproportionately expensive recovery scenario.

Many Yokogawa systems provide a low-battery alarm or diagnostic indication well before the cell is fully depleted, and maintenance teams are advised to treat that alarm as a scheduling trigger rather than something to defer, since the remaining margin after the alarm activates is deliberately conservative but not unlimited, and availability and lead time for the correct genuine replacement part should be confirmed in advance rather than at the moment the alarm is already active.

Documented Use in ProSafe-RS Safety Controllers

Replacement Interval and Safe Handling

Why Seven Star LLC

Seven Star LLC supplies genuine Yokogawa spare batteries, including the S9185FA, to process-control and DCS maintenance programs across Oman and the wider GCC, and confirms the exact host card or module the battery is intended for before shipment, along with correct dangerous-goods packaging and documentation for international spares logistics.

Request a Quote for Yokogawa S9185FA Battery Pack

Request a quote or technical inquiry for the Yokogawa S9185FA Battery Pack to ensure uninterrupted memory backup and reliable power retention for your industrial automation systems.

Ordering Notes

When quoting the S9185FA, Seven Star LLC confirms the exact host card, module, or controller family the battery is being sourced for, since Yokogawa battery part numbers are specific to a given card design and are not universally interchangeable across different DCS or PLC generations.

Related Products

Datasheets & Documents
  • PDF Document Yokogawa S9185FA Lithium Battery Safety Data Sheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.

Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.

Yokogawa at a glance

Established 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki
Milestones Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986
Headquarters Tokyo, Japan
Product families Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers

Yokogawa products we list

Family Models Typical use
Pressure and DP transmitters EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable Pressure, level and DP flow measurement in process plants
Temperature transmitters YTA610, YTA710 RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus
Flowmeters ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 Water and conductive liquids, mass flow of hydrocarbons, steam and gas
Analysers TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen
Controllers and recorders UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 Single-loop control, furnace programs and data recording
Control and safety systems CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 Spares and expansions for CENTUM DCS, safety systems and STARDOM
Battery packs S9129FA, S9185FA, S9548FA Memory backup batteries for DCS and controller modules

The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.

Where Yokogawa products are used

In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.

Ordering Yokogawa products: what we need

Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.

Facts checked against Yokogawa's corporate history, October 2026.

FAQ

Questions about the Yokogawa S9185FA Battery Pack

Answers from our engineering team on installation, compatibility and integration.

01What is the Yokogawa S9185FA Battery Pack used for?
It is used as a backup battery for Yokogawa DCS/PLC controllers to maintain memory and real-time clock functions during power interruptions. 
02What voltage and type does this battery provide?
The S9185FA typically delivers 3.6 V DC and is based on high-energy lithium battery chemistry. 
03Does it support harsh environments?
Yes — it is designed to perform reliably across a broad industrial temperature range and under vibration conditions common in control cabinets. 
04How do I request a quotation for Yokogawa S9185FA Battery Pack?
Send the model number, required quantity and delivery location through the quote request form or by email to Seven Star LLC. The sales team replies with availability, lead time and commercial terms for your Oman or GCC project.
05What information should I provide when ordering Yokogawa S9185FA Battery Pack?
Provide the full model or part number, quantity, the application and any required options or certifications. This lets the team confirm the exact configuration and avoid ordering a wrong variant.