ABB CR-P230AC2 Interface Relay 230 V AC 2 c/o 8 A

Description

CR-P230AC2: slim mains-coil relay with two 8 A changeover contacts

CR-P230AC2 is the 230 V AC, two-contact member of the CR-P range. It combines two changeover (SPDT) contacts rated 8 A at 250 V with a 0.75 VA coil, in a body of 12.7 x 29 x 15.7 mm that is 15.5 mm wide on the socket.

The relay is made for isolation and signal matching between a mains-level control signal and field devices. Because the coil draws only 0.75 VA, even small contacts such as pressure switches or float switches can drive it.

Technical specifications

Parameter Specification
Type designation / order code CR-P230AC2 / 1SVR405601R3000
Relay type Pluggable PCB-style interface relay, 2 c/o (SPDT) contacts
Coil voltage Us 230 V AC, 50/60 Hz; pick-up from 184 V, maximum 276 V at 55 C; drop-out at 0.15 Us
Coil power / resistance 0.75 VA / 38,500 ohm (plus or minus 10 %)
Thermal current Ith 8 A; AC12 230 V 8 A; DC12 24 V 8 A
Inductive ratings AC15 230 V 1.5 A, 120 V 3 A; DC13 24 V 2 A
Inrush / AC1 power 15 A / 2000 VA
Life / switching times Mechanical above 30 million cycles; electrical above 100,000 cycles at 8 A 250 V; typical pick-up 7 ms, release 3 ms
Ambient temperature Operation -40 to +70 C for AC coils; storage -40 to +85 C
Isolation 400 V AC; impulse 5 kV coil to contacts, 2.5 kV between contacts; overvoltage category III, pollution degree 3
Contact material / voltage AgNi / Ue 250 V; max switching 300 V DC or 440 V AC; minimum 5 V and 5 mA
Dimensions on socket / weight 12.7 x 29 x 15.7 mm (W x H x D) / 14 g; width on socket 15.5 mm
Protection / mounting IP67 / on a CR-P socket, any mounting position
Approvals and standards UL 508, CSA C22.2 No. 14, VDE, GOST, CCC, RMRS, CE; EN 61810-1

What the AC coil and two contacts mean in practice

The 230 V AC coil pulls in at 184 V and tolerates up to 276 V at 55 C, with drop-out at 15 percent of the rated voltage or more. Typical pick-up and release are 7 ms and 3 ms. The AC-coil version operates from -40 to +70 C ambient.

The two contacts are AgNi, each 8 A thermal, with AC1 breaking power of 2000 VA and making current of 15 A. The data sheet lists 2.5 kV between the two changeover contacts, so they can switch circuits at different potentials if the system voltage allows.

Sockets, modules and accessories

Use the CR-PSS standard screw socket (1SVR405650R1000) or the CR-PLS logical socket with protective separation (1SVR405650R0000). The CR-PJ jumper bar (1SVR405658R5000) joins coil terminals on screw sockets.

For 230 V AC coil protection ABB lists the CR-P/M 82 varistor (1SVR405656R2000) and the CR-P/M 52C RC element (1SVR405653R1000). A gold-contact two-contact version exists as the CR-P…G, for low-level signals.

Documents and quotation

The linked file is the ABB CR-P pluggable interface relays data sheet 2CDC117001D0204. Seven Star LLC supplies the CR-P230AC2 on request from Muscat as an independent supplier; availability and lead time are given in the quotation. More products of this kind are in the Automation Accessories category, and a related item is the ABB CR-M024DC4L interface relay.

Confirm before ordering: the coil voltage on site (AC or DC), the load current and type (resistive or inductive), the number of changeover contacts needed and the socket type.

Datasheets & Documents
  • PDF Datasheet ABB CR-P pluggable interface relays data sheet 2CDC117001D0204 Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB CR-P230AC2 Interface Relay 230 V AC 2 c/o 8 A

Answers from our engineering team on installation, compatibility and integration.

01What is the contact rating of the CR-P230AC2?
Two changeover contacts, 8 A at 250 V.
02What is the coil voltage?
230 V AC, 50/60 Hz, 0.75 VA.
03How wide is it?
15.5 mm on the socket.
04What is the degree of protection?
IP67 according to the data sheet.
05Which module protects the coil?
The CR-P/M 82 varistor, order code 1SVR405656R2000.