Brand: ABB
ABB 1SVR405614R1100 CR-M024DC4LD Relay 24 V DC, LED and Diode
Description
ABB 1SVR405614R1100: 24 V DC relay with LED and free-wheeling diode
ABB 1SVR405614R1100 is the CR-M024DC4LD, the only member of the standard CR-M range that has both a status LED and a free-wheeling diode built into the 4 c/o version. The coil is 24 V DC, and the four silver-nickel contacts are rated 6 A at 250 V. In the order tables ABB lists it as a separate group, “interface relays with LED and free wheeling diode”, because the diode changes how the relay behaves on the control side.
A relay coil is an inductor. When a transistor output switches it off, the collapsing field produces a voltage spike that can stress or destroy the output stage. The diode across the coil of 1SVR405614R1100 clamps that spike, so the relay can be driven directly from PLC transistor outputs, small DCS cards or open-collector drivers without an external suppressor. The LED makes the coil state visible from the front of the cabinet.
Features of the 1SVR405614R1100
- 24 V DC coil, 0.9 W, 640 ohm at 20 degrees C.
- LED indication and integrated free-wheeling diode in the same relay.
- Four c/o contacts, AgNi, 6 A thermal current, 250 V rated voltage.
- Removable blue test button with a locking position.
- Standard and logical CR-M sockets, 27 mm wide on the socket.
- Operating range -40 to +70 degrees C for DC coil types.
1SVR405614R1100 specification summary
| Order code | 1SVR405614R1100 |
|---|---|
| Type | CR-M024DC4LD |
| Coil voltage | 24 V DC |
| Make / maximum coil voltage | 19.2 V DC / 26.4 V DC |
| Coil power / resistance | 0.9 W / 640 ohm |
| Break voltage | 0.1 x Us or higher |
| Indicators | LED plus mechanical status |
| Coil protection | free-wheeling diode |
| Contacts | 4 c/o AgNi |
| Thermal current | 6 A |
| DC12 at 24 V | 6 A |
| DC13 at 24 V / 120 V / 250 V | 2 A / 0.22 A / 0.1 A |
| AC15 at 230 V / 120 V | 1 A / 1.5 A |
| Maximum making current | 12 A |
| Mechanical life | more than 20 million cycles |
| Response / release time | typ. 13 ms / typ. 3 ms |
| Operating temperature | -40 to +70 C |
| Standards | EN 60810-1, EN 60255-23, IEC 61810-7 |
| Weight / dimensions | 35 g / 21.2 x 27.5 x 35.6 mm |
Difference between CR-M024DC4LD and its siblings
The step from the plain CR-M024DC4 to CR-M024DC4LD adds two features without altering the contact data: the same 6 A and 12 A inrush ratings apply. Against the plain-LED CR-M024DC4L it adds the diode, and against the gold-contact CR-M024DC4LDG (1SVR405618R1400) it keeps the standard silver-nickel contacts, which are rated for loads from 10 V and 5 mA upward and therefore suit power and relay-coil switching rather than dry-circuit signals.
There is one practical consequence of the diode: the coil becomes polarity-sensitive. Plug-in diode modules such as CR-P/M 22 are listed with A1 positive and A2 negative, and the same convention should be followed here, so check the polarity marking before wiring.
Where to use 1SVR405614R1100
Direct drive from electronic outputs is the natural job. In oil and gas packages, a compact remote I/O card with transistor outputs can switch the coil without a separate suppression board, and the LED helps technicians read the relay state through a panel door in the field. Power utilities use the same arrangement on 24 V DC auxiliary supplies for alarm repeating. Desalination and water-treatment stations in the Gulf use it for pump permissives, where a clamped coil reduces electrical noise on shared supplies.
Sockets and modules for 1SVR405614R1100
The relay is a plug-in part, so one of the four-contact sockets from the CR-M family is required: CR-M4LS or CR-M4LC for logical wiring, CR-M4SS or CR-M4SF for standard wiring. As the diode is already inside, do not add a second diode module across the coil; if an RC element or varistor is wanted for additional protection, check the module data first because it would be redundant on a DC coil.
Commissioning and care
After wiring A1 positive and A2 negative, switch on the 24 V supply and confirm that the LED lights and the contacts transfer. Use the locking test button for loop checks. Typical electrical life at the full 6 A, 250 V resistive rating exceeds 100000 cycles; for the many cycles of light signal duty, the mechanical life of more than 20 million operations is the limit. If the LED stays dark with 24 V present, check polarity first. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Quick answers about 1SVR405614R1100
What do the letters LD mean in CR-M024DC4LD? L stands for the LED indicator and D for the free-wheeling diode built into the relay.
Do I need an external diode with 1SVR405614R1100? No. The free-wheeling diode is part of the relay, so an extra suppressor on the coil is normally not needed for DC operation.
How many contacts and what rating does 1SVR405614R1100 have? Four changeover contacts rated 6 A at 250 V, with a thermal current of 6 A and an inrush limit of 12 A.
Does the polarity of the 24 V DC coil matter on 1SVR405614R1100? Yes, because of the diode the coil should be connected with A1 positive and A2 negative as marked on the housing.
What is the temperature range of 1SVR405614R1100? DC-coil CR-M relays operate from -40 to +70 degrees C and can be stored from -40 to +85 degrees C.
Documents and quotation
The data sheet for the CR-M range is provided with this listing. Request a quotation for ABB 1SVR405614R1100 by sending the part number, the quantity and the delivery location in Oman or the GCC; add the CR-M4 socket part number if you want the relay and socket supplied together.
Other Models in the Abb Cr M Range
Seven Star LLC supplies models from the Abb Cr M range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| ABB 1SVR405613R3000 CR-M230AC4 Interface Relay 230 V AC, 4 c/o | Automation Accessories | View details |
| ABB 1SVR405618R1000 CR-M024DC4G Gold-Contact Interface Relay 24 V DC | Automation Accessories | View details |
| ABB 1SVR405613R4000 CR-M012DC4 Interface Relay 12 V DC, 4 c/o | Automation Accessories | View details |
| ABB 1SVR405611R1100 CR-M024DC2L Interface Relay 24 V DC, 2 c/o, LED | Automation Accessories | View details |
| ABB 1SVR405613R0000 CR-M024AC4 Interface Relay 24 V AC, 4 c/o | Automation Accessories | View details |
| ABB 1SVR405614R1100 CR-M024DC4LD Relay 24 V DC, LED and Diode | Automation Accessories | You are viewing this model |
Datasheets & Documents
- Datasheet ABB 1SVR405614R1100 CR-M024DC4LD Relay 24 V DC, LED and Diode Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB 1SVR405614R1100 CR-M024DC4LD Relay 24 V DC, LED
Answers from our engineering team on installation, compatibility and integration.
01What do the letters LD mean in CR-M024DC4LD?
L stands for the LED indicator and D for the free-wheeling diode built into the relay.
02Do I need an external diode with 1SVR405614R1100?
No. The free-wheeling diode is part of the relay, so an extra suppressor on the coil is normally not needed for DC operation.
03How many contacts and what rating does 1SVR405614R1100 have?
Four changeover contacts rated 6 A at 250 V, with a thermal current of 6 A and an inrush limit of 12 A.
04Does the polarity of the 24 V DC coil matter on 1SVR405614R1100?
Yes, because of the diode the coil should be connected with A1 positive and A2 negative as marked on the housing.
05What is the temperature range of 1SVR405614R1100?
DC-coil CR-M relays operate from -40 to +70 degrees C and can be stored from -40 to +85 degrees C.