Brand: JUMO
JUMO MIDAS S22 Ex Miniature Pressure Transmitter for Ex Areas, Type 404720
Description
A miniature intrinsically safe pressure transmitter for zones 1, 2, 21 and 22
The JUMO MIDAS S22 Ex (type 404720) is a miniature pressure transmitter for gases, vapours and liquids that is certified for hazardous areas. It works on the piezoresistive principle and delivers a load-independent 4 to 20 mA signal that is linearly proportional to pressure. According to the datasheet it meets the requirements of device group II in zones 1 and 2 and device group III in zones 21 and 22, with ATEX certificate SEV 21 ATEX 0537 X and IECEx certificate SEV 21.0011X. The welded stainless steel system, ranges from 2.5 to 100 bar in relative or absolute reference and burst pressures up to 400 bar, ten times the span, suit compact installations where space is short.
Technical specifications
| Parameter | Specification |
|---|---|
| Measuring principle | Piezoresistive silicon sensor with stainless steel separating membrane; synthetic oil |
| Relative ranges | 0 to 2.5, 6, 10, 16, 25, 40, 60, 100 bar; -1 to +1.5, +3, +5, +9 bar (0 to 4 bar also in the accuracy table) |
| Absolute ranges | 0 to 2.5, 4, 6, 10, 16, 25, 40, 60, 100 bar |
| Linearity / accuracy | Linearity 0.3 % of span; accuracy 0.5 % at 20 degC; 1.0 to 1.3 % of span over -20 to +80 degC |
| Long-term stability | 0.2 % of span per year or better |
| Overload / burst | Examples: 0 to 10 bar 50 / 60 bar; 0 to 25 bar 120 / 180 bar; 40 to 100 bar 300 / 400 bar; vacuum-proof |
| Output / supply | 4 to 20 mA, 2-wire; DC 16 to 28 V; current 23 mA or less; intrinsically safe circuit |
| Burden | RB (UB – 16 V) divided by 0.022 A; influence 0.01 % per 100 ohm |
| Step response T90 | 3 ms or less |
| Temperatures | Ambient, storage and medium -20 to +85 degC (not front-flush); 10 to 40 degC for front-flush versions |
| Protection | IP68 (DIN EN 60529) |
| Shock / vibration | 20 g for 11 ms and 50 g for 1 ms; 10 g at 10 to 2000 Hz |
| Materials | Process connection 316 Ti; membrane 316 L; housing 304; PUR cable (conductor 0.22 mm2, bending radius 35 mm max.) |
| Weight | Approx. 55 g |
| Approvals as printed | ATEX II 2G Ex ib IIC T6 to T4 Gb and II 2D Ex ib IIIC T70 to T100 degC Db; UKEX EPS 22 UKEX 1 089 X (extra code 085); IECEx SEV 21.0011X |
| Process connection codes | 480 M12 x 1 internal; 481 M12 x 1 with protective cap; 502 G 1/4 DIN EN 837; 530 M8 x 1; 531 M10 x 1; 532 M12 x 1.5 (DIN 3852-1); 544 and 562 7/16-20 UNF; 561 G 1/4 front-flush, double seal |
| Electrical connection | 11 attached cable, blue, 2 m standard; 36 round plug M12 x 1 |
| Extra codes | 085 UKEX; 462 inverted output; 591 choke in channel; 624 oil and grease free; 630 enlarged channel |
| Order example | 404720/000-459-405-502-20-11/000 |
Hazardous-area use and wiring
The datasheet marks the device for intrinsically safe use and requires the user to observe the special conditions for safe use listed in the certificates, which are available for download on the manufacturer website. Supply must come from an intrinsically safe source, and JUMO lists an Ex-i repeater power supply and input isolating amplifier (part no. 00577948) that supplies two-wire transmitters in the hazardous area and passes the 0/4 to 20 mA value to the safe area. Terminal assignment is UB plus or white and 0 V or blue for the attached cable; the round plug uses pin 1 for supply plus and pin 3 for supply minus.
The datasheet cautions that the housing must be grounded through the process connection to protect against electromagnetic fields and charges, and that all connected devices such as pumps and valves should be grounded to the same potential. Cable boxes with a 2 m PVC cable and gold-plated 4-pin M12 contacts are listed as 00404585 (straight) and 00409334 (angled).
Choosing connection and range
Pick range, 4 to 20 mA output (405), process connection and stainless steel material (20), then attached cable or M12 plug. Small thread options such as M8, M10 and M12 x 1.5 to DIN 3852-1 suit compact manifolds, G 1/4 to DIN EN 837 suits standard gauge ports and a front-flush G 1/4 version with double seal is listed for flush mounting, though front-flush versions have a narrower 10 to 40 degC range. The extra codes allow a choke for the pressure channel, an enlarged channel or oil and grease free preparation.
Applications named by JUMO are oil, fuel and natural gas, painting plants and robots, process technology, plant engineering, laboratory testing and the chemical industry. For a non-Ex OEM transmitter of the same MIDAS family see the published MIDAS S05, and browse pressure instrumentation. In an enquiry give the zone, gas or dust group and temperature class needed, the range and reference, medium, process thread and cable length.
Related JUMO products: JUMO MIDAS S21 Ex Pressure Transmitter for Ex Areas, JUMO MIDAS OEM Pressure Transmitter, 1.6 to 100 bar, JUMO MIDAS S05 OEM Pressure Transmitter, JUMO MIDAS C18 SW Titanium Seawater Pressure Transmitter, JUMO dTRANS p33 Ex-Area Pressure Transmitter and JUMO MIDAS DP10 Differential Pressure Transmitter.
Documents and quotation
Hosted for reference is the official JUMO data sheet 404720, version 3.00 dated 2024-06-03, nine pages in English, with approvals, accuracy table, dimensions, wiring and the order code. Seven Star LLC is an independent supplier in Muscat; send the order code and the hazardous-area requirement and we will prepare a quotation. Please include the full order code, the intended medium and the required quantity in your request so that the quotation matches the exact version listed in the data sheet.
Datasheets & Documents
- Datasheet JUMO MIDAS S22 Ex data sheet 404720 V3.00 (EN, 9 pages) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.
Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.
JUMO company profile
| Established | 1948, Fulda, Germany, by Moritz Kurt Juchheim |
|---|---|
| First products | Glass and contact thermometers; platinum glass sensors from 1966 |
| Ownership | Family-owned; renamed JUMO GmbH & Co. KG in 2003 |
| Product families | RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments |
Milestones
- 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
- 1966: Platinum glass temperature sensors are added.
- 2003: The parent company is renamed JUMO GmbH & Co. KG.
JUMO products we list
| Family | Models | Typical use |
|---|---|---|
| RTD and thermocouple probes | 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp | Temperature measurement in pipes, vessels, machines, HVAC and food plants |
| Thermowells and inserts | 909710 thermowells, 909740 measuring inserts | Protecting sensors and replacing them without opening the process |
| Temperature transmitters | dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch | Converting sensor signals to 4-20 mA, HART or IO-Link |
| Pressure and level | dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 | Pressure in process, hydraulic and OEM systems; tank and well level |
| Controllers, limiters and recorders | DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T | Furnace, oven and process control, over-temperature protection and recording |
| Liquid analysis and flow | AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 | pH, conductivity, oxygen and turbidity in water treatment; liquid flow |
Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.
Where JUMO products are used
In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.
Ordering JUMO products: what we need
Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.
Facts checked against JUMO's company history, October 2026.
Browse JUMO products by category: Temperature Instrumentation, Pressure Instrumentation, Liquid Analysis Sensors, Controllers & Data Acquisition, Level Transmitter.
Related products
Frequently Asked Questions
The datasheet states device group II for zones 1 and 2 and device group III for zones 21 and 22.
ATEX SEV 21 ATEX 0537 X, IECEx SEV 21.0011X and UKEX EPS 22 UKEX 1 089 X (with extra code 085).
4 to 20 mA two-wire on DC 16 to 28 V with an intrinsically safe circuit.
Relative from -1 to +9 bar and 0 to 100 bar, and absolute from 0 to 2.5 up to 0 to 100 bar.
Up to 400 bar on the 40 to 100 bar ranges, ten times the span according to the datasheet.