JUMO CANtrans p Ceramic Pressure Transmitter with CANopen Output, Type 402055
Description
A ceramic pressure transmitter that talks CANopen directly
The JUMO CANtrans p Ceramic (type 402055) measures relative pressure in liquids and gases with a thick-film strain gauge on an alumina ceramic (Al2O3) sensing element and makes the digitised value available on a CANopen bus as a CAN slave. The DS 404 device profile for measuring devices and closed-loop controllers adds useful functions, and every setting can be made with standard CANopen software tools through the object directory (EDS). It is intended for machines and vehicles that already use a CAN network, where an analog 4 to 20 mA signal would otherwise need an extra interface. Ranges run from 0 to 1.6 bar up to 0 to 60 bar, plus vacuum-containing ranges down to -1 bar.
Technical specifications
| Parameter | Specification |
|---|---|
| Measuring principle | Thick-film strain gauge on alumina ceramic (Al2O3, 96 %) |
| Relative ranges | 0 to 1.6, 2.5, 4, 6, 10, 16, 25, 40, 60 bar; -1 to +0.6, +1.5, +3, +5, +9, +15, +24 bar; special ranges (code 999) |
| Output / protocol | CANopen slave per CiA DS 301 V4.02; device profile CiA DS 404 V1.2 |
| Resolution | 12 bit measurement (optionally 11 bit with 0.5 ms cycle); 32-bit value and 8-bit status in the PDO |
| Cycle time | 1 ms; optionally 0.5 ms |
| Baud rate / node ID | 20 kbaud to 1 Mbaud and ID 1 to 127, set via LSS or SDO |
| CANopen services | 1 Tx PDO, 1 SDO, emergency, heartbeat, node guarding, LSS, SYNC, EDS available |
| Supply | DC 10 to 30 V (reference 24 V); approx. 45 mA maximum |
| Deviation from characteristic | 0.5 % of span (limit point adjustment) |
| Hysteresis / repeatability | 0.2 % of span; 0.1 % of span |
| Temperature effect (-20 to +85 degC) | Zero and span typically 0.02 % per degC, maximum 0.04 % per degC |
| Thermal hysteresis / stability | 0.4 % of span; 1 % of span per year |
| Overload / burst | Up to 40 bar: 3 x span overload, 4 x burst; 60 bar: 2 x and 3 x |
| Temperatures | Ambient -20 to +85 degC; medium -20 to +85 degC; storage -40 to +85 degC |
| Shock / vibration | 100 g for 5 ms; 20 g at 15 to 2000 Hz |
| Wetted materials | Stainless steel 1.4305 and ceramic Al2O3 96 %; seal FPM or FFPM |
| Housing / protection | Stainless steel 1.4305; IP67 with connector screwed on; M12 plug |
| Weight | 95 g with G 1/4 connection |
| EMC | DIN EN 61326-1:2013 and 61326-2-3:2013; emission class B; industrial immunity |
| Process connections | 502 G 1/4 DIN EN 837; 511 1/4-18 NPT; 521 G 1/4 DIN 3852-11; 523 G 1/2 DIN 3852-11 |
| Order example | 402055/00-462-450-502-20-601-36/000 (code 6: 601 FPM or 604 FFPM; code 8: 000 or 100 customer configuration) |
Useful functions built into the CANopen firmware
The block diagram lists the functions that distinguish the device from a simple converter. The ceramic signal is digitised at 12 bits and calibrated digitally at the factory. Sensor monitoring sends high-priority emergency telegrams on probe break or short circuit. The reading can be scaled to any engineering unit or to percent of range, an adjustable filter suppresses signal fluctuation, and the decimal place is freely selectable. Fine calibration offers an auto-zero function and an adjustable shift of the characteristic, range monitoring with freely chosen upper and lower limits reports results in a status byte, and a drag pointer stores the minimum and maximum pressure.
The date and name of the last service can be stored inside the transmitter. Measured values can be sent on different trigger conditions or only on a SYNC command, and heartbeat or node guarding supervise the device itself. NMT telegrams control its operating state. Further CANopen transmitters from JUMO are referenced as data sheets 402056 (pressure) and 902910 (temperature).
Wiring, accessories and enquiry details
Mechanical choices are limited by design. The wetted parts are stainless steel 1.4305 with the ceramic cell, and the process connection is chosen from four threads, G 1/4 and G 1/2 to DIN 3852-11 or G 1/4 to DIN EN 837 and 1/4-18 NPT. Profile seal rings are shown for the G 1/4 and G 1/2 DIN 3852 versions, and other connections are available on request. The nominal mounting position is unrestricted. The datasheet limits the medium temperature to -20 to +85 degC, so check the process against that limit.
The M12 plug has five pins: shield on 1, V plus on 2, V minus on 3, CAN_H on 4 and CAN_L on 5, and the datasheet recommends a screened 5-wire cable. Accessories include M12 line sockets (00337625, 00375164, 00419130 and 00419133), a tee-piece (00419129), a 2 m extension cable (00461589), a bus termination resistor (00461591) and a PC CAN interface with configuration software for USB (00449941).
For an analog alternative in a similar size see the published dTRANS p30 and the pressure instrumentation category. When you enquire, state the pressure range, process connection, seal material (FPM or FFPM, which has PTFE-like properties), CAN baud rate and node ID needs, and whether a customer-specific configuration is required.
Related JUMO products: JUMO dTRANS p20 Process Pressure Transmitter with HART, JUMO dTRANS p33 Ex-Area Pressure Transmitter, JUMO dTRANS p31 Hygienic Pressure Transmitter, JUMO dTRANS p30 Pressure Transmitter, JUMO Wtrans p Wireless Pressure Transmitter and JUMO MIDAS OEM Pressure Transmitter, 1.6 to 100 bar.
Documents and quotation
Hosted for reference is the official JUMO data sheet 402055, version 2.00 dated 2023-10-10, six pages with English text, covering the CANopen functions, technical data, wiring, order code and accessories. Seven Star LLC is an independent supplier in Muscat; send the order code and we will prepare a quotation.
Datasheets & Documents
- Datasheet JUMO CANtrans p Ceramic data sheet 402055 V2.00 (EN text, 6 pages) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.
Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.
JUMO company profile
| Established | 1948, Fulda, Germany, by Moritz Kurt Juchheim |
|---|---|
| First products | Glass and contact thermometers; platinum glass sensors from 1966 |
| Ownership | Family-owned; renamed JUMO GmbH & Co. KG in 2003 |
| Product families | RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments |
Milestones
- 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
- 1966: Platinum glass temperature sensors are added.
- 2003: The parent company is renamed JUMO GmbH & Co. KG.
JUMO products we list
| Family | Models | Typical use |
|---|---|---|
| RTD and thermocouple probes | 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp | Temperature measurement in pipes, vessels, machines, HVAC and food plants |
| Thermowells and inserts | 909710 thermowells, 909740 measuring inserts | Protecting sensors and replacing them without opening the process |
| Temperature transmitters | dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch | Converting sensor signals to 4-20 mA, HART or IO-Link |
| Pressure and level | dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 | Pressure in process, hydraulic and OEM systems; tank and well level |
| Controllers, limiters and recorders | DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T | Furnace, oven and process control, over-temperature protection and recording |
| Liquid analysis and flow | AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 | pH, conductivity, oxygen and turbidity in water treatment; liquid flow |
Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.
Where JUMO products are used
In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.
Ordering JUMO products: what we need
Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.
Facts checked against JUMO's company history, October 2026.
Browse JUMO products by category: Temperature Instrumentation, Pressure Instrumentation, Liquid Analysis Sensors, Controllers & Data Acquisition, Level Transmitter.
Related products
Frequently Asked Questions
CANopen as a CAN slave according to CiA DS 301 V4.02 with device profile CiA DS 404 V1.2.
Relative 0 to 1.6 up to 0 to 60 bar and compound ranges from -1 to +0.6 up to -1 to +24 bar.
Baud rate from 20 kbaud to 1 Mbaud and node ID 1 to 127 are set via LSS or SDO.
FPM (code 601) or FFPM (code 604), the latter with PTFE-like characteristics.
IP67 with the connector screwed on, in a stainless steel 1.4305 housing.


















Reviews