Brand: JUMO
JUMO MIDAS S06 Low-Pressure OEM Pressure Transmitter, 401011
Description
A seal-less low-pressure transmitter from 100 mbar for filters and air systems
The JUMO MIDAS S06 (type 401011) is an OEM pressure transmitter for low pressure, with measuring ranges starting at 100 mbar. It uses a seal-less welded measuring system with a piezoresistive silicon sensor behind a stainless steel separating membrane, which the datasheet describes as extremely overload resistant even in the lowest ranges and able to handle millions of pressure cycles. Parts in contact with media are stainless steel, so the transmitter can measure aggressive liquids and gases in harsh conditions. The datasheet lists HVAC, filter technology, mechanical and plant engineering, level measurement, the bubble-through method and packaging as applications. A QUICKON quick-clamp connector is said to cut device installation time by 60 %.
Technical specifications
| Parameter | Specification |
|---|---|
| Type | 401011/000 MIDAS S06 OEM pressure transmitter, low pressure |
| Measuring ranges | 0 to 100, 160 mbar; 0 to 0.25, 0.4, 0.6 bar; -100 to +100 mbar; -400 to +400 mbar; special range on request |
| Linearity | 0.3 % of span (0.35 % for 100 mbar) |
| Accuracy at 20 °C | 0.7 % to 1.2 % of span depending on range |
| Accuracy -20 to +100 °C | 1.6 % to 2 % of span (0 to 80 °C for the lowest ranges) |
| Long-term stability | Below 1.0 % of span per year on the lowest ranges; below 0.4 % per year on the higher ranges |
| Overload | From ±0.4 bar for the 100 mbar range to ±1 bar for the 0.4 bar and 0.6 bar ranges (burst to 3.6 bar) |
| Outputs | 4 to 20 mA two-wire; DC 0.5 to 4.5 V ratiometric; DC 0 to 10 V; DC 1 to 5 V; DC 1 to 6 V |
| Supply | 4 to 20 mA DC 8 to 30 V; 0 to 10 V DC 11.5 to 30 V; ratiometric DC 3 to 5.25 V; reverse-polarity protected |
| Step response | T90 up to 5 ms |
| Process connections | G 1/8, G 1/4 and G 1/2 to DIN EN 837; 1/4-18 NPT; G 1/4 DIN 3852-11; 7/16-20 UNF, also with valve core handle |
| Materials | Process connection and housing stainless steel 304; membrane 316L; synthetic oil fill; FPM seal on G 1/4 |
| Electrical connection | Attached cable, QUICKON, M12 plug, bayonet connector or line socket |
| Medium temperature | 0 to 80 °C up to 0.25 bar ranges; -20 to +100 °C from 0.4 bar |
| Protection | IP66 for cable, QUICKON and M12; IP67 bayonet; IP65 line socket (with suitable counter piece) |
| Vibration and shock | 20 g at 10 to 2000 Hz; 50 g for 11 ms |
| Weight | About 80 g with G 1/4 connection |
| Accessory | Mounting bracket with hexagon nut, part number 00578663 |
Selecting range, output and connection
Pick the span so that normal duty uses a good part of the range, since the 100 mbar version has a linearity of 0.35 % and the datasheet lists accuracy of 1.2 % at 20 °C for it, against 0.7 % for the 0.4 bar and 0.6 bar versions. A ratiometric 0.5 to 4.5 V output suits a 5 V electronics supply of an OEM controller, while a 4 to 20 mA output suits long cable runs and PLC inputs. The order code builds from the basic type 000, the input code such as 451 for 0 to 0.25 bar, the output code 405 for 4 to 20 mA, and the process connection such as 502 for G 1/4. An extra code 630 adds a pressure channel bore in the process connection, and extra code 933 selects alternative M12 pin assignments such as B1 to B4.
The measuring cell tolerates more than 10 million load changes. Overload capacity is stated as a pressure window, for example -0.4 to +0.4 bar on the 100 mbar range and -1 to +2.4 bar on the 0.6 bar range, which is useful where a blocked filter or a fan surge can briefly raise the pressure far above the normal level. Vibration resistance of 20 g from 10 to 2000 Hz and shock of 50 g make it practical on compressors, packaging machines and air-handling units that vibrate in service.
Installation notes
Mount in any position, but the device is calibrated upright with the connection at the bottom, and a zero offset of up to 1.5 mbar can appear with the connection at the top. This matters most for the 100 mbar range, so a zero-point adjustment after installation is good practice. The protection class shown applies only when a suitable counter piece is mounted, and the transmitter must be connected to the plant potential equalisation, through the connector or the process connection. For air and filter service, take the pressure from a clean point away from condensate, and use the bubble-through method for tank level in non-pressurised vessels. Check the compatibility of the FPM seal with the medium.
See pressure instrumentation for related transmitters.
Using the MIDAS S06 in Oman and the GCC
Low-pressure transmitters are used in the region on HVAC systems, filter monitoring, compressed air systems, water treatment skids and pumps where small pressures must be measured reliably. The MIDAS S06 is an OEM transmitter, so it is aimed mainly at machine and skid builders who need a compact, robust device in large numbers.
In outdoor equipment or plant rooms, ambient and medium temperatures can be high in summer, so check the temperature limits and consider the effect of direct sun on the housing. Choose the electrical connection and protection rating to suit dusty or humid sites. Protect the transmitter from pressure peaks, such as water hammer, where these may exceed the overload limit.
For new designs, sending the application and expected operating conditions helps us confirm the range, overload limit and connections before samples are ordered.
Information to send with an enquiry
- Measuring range and pressure type
- Output signal and supply voltage
- Process and electrical connection
- Medium and temperature
- Expected annual quantity
Related JUMO products: JUMO MIDAS H20 HP High-Pressure OEM Pressure Transmitter, JUMO MIDAS S05 OEM Pressure Transmitter, JUMO MIDAS OEM Pressure Transmitter, 1.6 to 100 bar, JUMO dTRANS p20 Process Pressure Transmitter with HART, JUMO MIDAS DP10 Differential Pressure Transmitter and JUMO Wtrans p Wireless Pressure Transmitter.
Documents and quotation
The hosted document is JUMO data sheet 401011 (12 pages, English). It includes dimensions, wiring and order details. Confirm range, output, connection and plug before ordering. Seven Star LLC is an independent supplier in Muscat; send the pressure range, medium and connector for a quotation. To help us prepare an accurate quotation, please include the medium, pressure range, required output signal, process connection and hazardous-area requirements, together with the quantity needed and the delivery location. We will then compare these details with the order information in the datasheet.
Datasheets & Documents
- Datasheet JUMO 401011 data sheet 401011 (EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.
Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.
JUMO company profile
| Established | 1948, Fulda, Germany, by Moritz Kurt Juchheim |
|---|---|
| First products | Glass and contact thermometers; platinum glass sensors from 1966 |
| Ownership | Family-owned; renamed JUMO GmbH & Co. KG in 2003 |
| Product families | RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments |
Milestones
- 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
- 1966: Platinum glass temperature sensors are added.
- 2003: The parent company is renamed JUMO GmbH & Co. KG.
JUMO products we list
| Family | Models | Typical use |
|---|---|---|
| RTD and thermocouple probes | 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp | Temperature measurement in pipes, vessels, machines, HVAC and food plants |
| Thermowells and inserts | 909710 thermowells, 909740 measuring inserts | Protecting sensors and replacing them without opening the process |
| Temperature transmitters | dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch | Converting sensor signals to 4-20 mA, HART or IO-Link |
| Pressure and level | dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 | Pressure in process, hydraulic and OEM systems; tank and well level |
| Controllers, limiters and recorders | DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T | Furnace, oven and process control, over-temperature protection and recording |
| Liquid analysis and flow | AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 | pH, conductivity, oxygen and turbidity in water treatment; liquid flow |
Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.
Where JUMO products are used
In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.
Ordering JUMO products: what we need
Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.
Facts checked against JUMO's company history, October 2026.
Browse JUMO products by category: Temperature Instrumentation, Pressure Instrumentation, Liquid Analysis Sensors, Controllers & Data Acquisition, Level Transmitter.
FAQ
Questions about the JUMO MIDAS S06 Low-Pressure OEM Pressure
Answers from our engineering team on installation, compatibility and integration.
01What ranges does the MIDAS S06 offer?
From 0 to 100 mbar up to 0 to 0.6 bar, plus -100 to +100 mbar and -400 to +400 mbar.
02Which outputs are available?
4 to 20 mA, DC 0.5 to 4.5 V ratiometric, DC 0 to 10 V, DC 1 to 5 V and DC 1 to 6 V.
03Does it have a seal-less measuring system?
Yes, the welded measuring system has no seal, and wetted parts are stainless steel.
04What is the QUICKON connector?
A quick-clamp connector that the datasheet says reduces device installation time by 60 %.
05Which applications does it suit?
HVAC, filter monitoring, level measurement with the bubble-through method, machinery and packaging.


















Reviews