Honeywell SPXCDALMRX Sensepoint XCD IR Methane Detector
Description
A catalytic detector reads flammable gas by burning it on a bead. Honeywell SPXCDALMRX does the job with light instead. It is the Sensepoint XCD point detector fitted with a plug-in infrared sensor linearised to methane, mounted in an LM25 aluminium ATEX and IECEx housing with M20 entries. Choosing infrared rather than catalytic removes poisoning concerns and allows operation in atmospheres with little or no oxygen, which is why this part is requested for inerted vessels, biogas and landfill plant, and gas metering stations.
SPXCDALMRX in numbers
| Parameter | Value |
|---|---|
| Sensor | Plug-in infrared hydrocarbon sensor, linearised to methane |
| Range | 0 to 100 percent LEL default; selectable full scale 20 to 100 percent LEL in 10 percent steps |
| Calibration | Default 50 percent LEL; calibration gas 30 to 70 percent of the selected full scale |
| Response T90 | Less than 30 s |
| Accuracy | Better than +/-1.5 percent LEL |
| Temperature | -20 to +55 degrees C |
| Alarms | 20 percent LEL and 40 percent LEL, rising |
| Power | Up to 3.7 W |
| Output | 4 to 20 mA sink or source; 3 relays; Modbus RTU optional |
| Housing | LM25 aluminium, 2.0 kg, IP66 |
| Spare cartridge | SPXCDXSRXSS |
Why SPXCDALMRX differs from SPXCDALMPX and SPXCDALMFX
The SPXCDALMRX is linearised to methane, while the SPXCDALMPX is linearised to propane and carries linear cross-sensitivity factors for ethylene, butane and pentane. The catalytic SPXCDALMFX instead addresses gas types 1 to 8. The infrared units have a response time of under 30 seconds, a narrower operating limit than catalytic units, and they cannot take advantage of the extended low-temperature range because the datasheet excludes the infrared and hydrogen sensors from it.
Best-fit applications
- Natural gas receiving and metering stations where methane is the hazard.
- Biogas digesters and landfill gas compressors in waste treatment plants.
- Gas turbine enclosures and generator buildings fuelled with natural gas.
- Inert-blanketed tanks and vessels, where catalytic beads need oxygen.
- Plants in which silicone or sulphur compounds would degrade a catalytic bead.
Installing SPXCDALMRX
The SPXCDALMRX mounts with four M8 holes or on a 1.5 to 3 inch pipe. Honeywell’s cable table for infrared XCD detectors, with a 24 VDC supply, shows 420 metres at 0.5 mm squared, 793 at 1.0, 1217 at 1.5, 1531 at 2.0 and 1932 at 2.5 mm squared. The terminal block takes 15 connections and removes as a plug to make wiring easier. A sink or source switch on the rear of the display module selects the loop style.
The infrared detector measures hydrocarbons by their absorption of infrared radiation, so the reading is independent of oxygen concentration. Honeywell lists two IR hydrocarbon sensors for the XCD range, one linearised to methane and one to propane, plus a carbon dioxide infrared sensor, which makes it possible to standardise on a single transmitter and housing. The methane sensor in SPXCDALMRX is the one to use when the primary hazard is natural gas, and it remains stable in environments where catalytic beads can be affected by contaminants in the process air. As with all infrared point detectors, keep the optical window clean and do not paint over or cover the sensor filter.
Operating temperature is -20 to +55 degrees C, and the datasheet’s note about the extended range to -40 degrees C does not apply to this sensor, so for exposed outdoor locations in a hot climate you should consider sunshade SPXCDSDP, which Honeywell describes as sunshade and deluge protection. In humid coastal locations the weatherproof cap supplied with the detector and IP66 enclosure protect the electronics.
Setup and configuration
The user interface of the SPXCDALMRX consists of the LCD and magnet switches. Range, alarm points, relay behaviour and the electronic tag can be changed without opening the cover, and the outputs are inhibited while changes are made. The transmitter auto-recognises the infrared sensor on its mV-type board, so the range defaults apply as soon as the sensor is plugged in.
Maintenance of the infrared sensor
The infrared cartridge is replaced as a plug-in module, SPXCDXSRXSS, a 316 stainless steel sensor with a methane 0 to 100 percent LEL range. Calibration uses a gas flow of 500 ml per minute through the cup S3KCAL, as stated for IR, toxic and oxygen sensors in the datasheet. Hot work permits are not required for sensor replacement.
Power consumption for infrared versions is up to 3.7 W with a maximum inrush current of 800 mA at 24 VDC, which is lower than the 4.9 W of the catalytic detector. The input range is 16 to 32 VDC for the ATEX and IECEx unit, and current output behaviour matches the rest of the XCD family: 4 to 20 mA for measurement, 22 mA for over range, less than 1 mA for a fault, and 2 or 4 mA during inhibit. For a project comparing detectors, the SPXCDALMRX is therefore a lower-power and poison-free alternative to SPXCDALMFX at the cost of a narrower low-temperature limit.
Ordering options for SPXCDALMRX
Before ordering the SPXCDALMRX, confirm the target gas: if the hazard is propane, butane or pentane, the propane-linearised SPXCDALMPX is the better match, and if several gases are present the catalytic SPXCDALMFX with its gas selection may fit. Add M for Modbus RTU, giving SPXCDALMRXM. A 316 stainless steel version exists as SPXCDASMRX. UL and CSA versions replace the certification letter and entry type in the code. Accessories include a pipe bracket, collecting cone for lighter-than-air gases such as methane, sunshade and deluge protection, and a duct mounting kit.
Documents and quotation
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Request the XCD datasheet with your quotation and send an RFQ with part number SPXCDALMRX, quantity and delivery location.
Typical Questions From Maintenance Teams
Maintenance engineers replacing a Honeywell SPXCDALMRX usually ask whether the new unit is a direct fit, whether settings can be copied from the old one, and whether any accessories must be ordered separately. The answer depends on the exact order code and the generation of the installed fire & gas detectors, so the nameplate details are the best starting point. Send them with your request and we will check the match, point out any differences in connections or options, and list the parts needed so that the job can be finished in one visit.
Other Models in the Xcd Detector Range
Seven Star LLC supplies models from the Xcd Detector range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Honeywell SPXCDALMHX Sensepoint XCD H2S Detector LM25 | Fire & Gas Detectors | View details |
| Honeywell SPXCDASMHX Sensepoint XCD H2S Detector 316SS | Fire & Gas Detectors | View details |
| Honeywell SPXCDALMFX Sensepoint XCD Flammable Detector | Fire & Gas Detectors | View details |
| Honeywell SPXCDALMRX Sensepoint XCD IR Methane Detector | Fire & Gas Detectors | You are viewing this model |
Datasheets & Documents
- Datasheet Sensepoint XCD Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).
Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.
Honeywell company profile
| Origins | 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927 |
|---|---|
| Brands in our range | Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance |
| Gent | Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005 |
| Elster | Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015 |
Milestones
- 1885: The Butz thermostat business starts in Minneapolis.
- 1927: It merges with Mark Honeywell's company.
- 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
- 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.
Honeywell products we list
| Family | Models | Typical use |
|---|---|---|
| Fixed gas detectors | Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID | Flammable, toxic and VOC gas detection in process areas |
| Sensors, flame detection and control | SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel | Replacement sensors, fire detection and gas detection control panels |
| Transmitters and flow | SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis | Process pressure and mass flow measurement |
| Elster gas metering | Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display | Gas meters, volume correction and fiscal flow computing |
| Gent fire alarm systems | Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell | Addressable and conventional fire alarm systems in buildings and plants |
| Chadwick-Helmuth rotor track and balance | 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor | Helicopter rotor track and balance and propeller balancing |
Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.
Where Honeywell products are used
In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.
Ordering Honeywell products: what we need
Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.
Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.
Browse Honeywell products by category: Fire & Gas Detector, Vibration, Flowmeters, Pressure Instrumentation, Temperature Instrumentation.
FAQ
Questions about the Honeywell SPXCDALMRX Sensepoint XCD IR Methane
Answers from our engineering team on installation, compatibility and integration.
01What gas is Honeywell SPXCDALMRX set up for?
It uses a plug-in infrared sensor linearised to methane, with a default range of 0 to 100 percent LEL, in an LM25 aluminium XCD housing.
02How does SPXCDALMRX differ from SPXCDALMFX?
SPXCDALMRX uses an infrared sensor and draws up to 3.7 W, while SPXCDALMFX uses a catalytic bead and draws up to 4.9 W. Infrared does not need oxygen to measure.
03What is the response time of SPXCDALMRX?
The XCD datasheet gives a T90 below 30 seconds for the infrared methane sensor, with accuracy better than plus or minus 1.5 percent LEL.
04Does the SPXCDALMRX have an extended low temperature range?
No. The datasheet says the extended range down to -40 degrees C applies to all sensors except infrared and hydrogen, so the SPXCDALMRX is specified from -20 to +55 degrees C.
05Which spare sensor fits SPXCDALMRX?
The spare plug-in methane infrared cartridge is SPXCDXSRXSS, listed for 0 to 100 percent LEL.