Brand:

JUMO 707088/8-06 dTRANS T07 Ex SIL Rail Transmitter

Description

JUMO 707088/8-06: rail-mounted Ex and SIL transmitter

JUMO 707088/8-06 is the most heavily certified code in the dTRANS T07 range: base type 707088, dTRANS T07 T Ex SIL, designed for mounting on a TH 35 rail with both intrinsic-safety and SIL 2/3 approval. The suffix /8-06 keeps the factory default (0 to 100 C, Pt100 three-wire, 4 to 20 mA) and screw terminals. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

The unit is intended to stand in the control room or a cabinet outside the classified area while the sensors sit in the hazardous plant. It is the code to quote for safety instrumented temperature loops that need galvanic separation from the classified area, such as furnace over-temperature, compressor discharge or reactor jacket protection.

Certificates behind 707088/8-06

  • ATEX EPS 17 ATEX 1 129 X: II 2(1)G Ex ib [ia Ga] IIC T6 to T4 Gb, so the sensor side can reach into zone 0 while the device itself is rated for zone 1.
  • IECEx EPS 17.0075X with the same marking.
  • TUV Sued SIL certificate Z10 17 05 01028 0001, SIL 2/3 hardware and software to IEC 61508.
  • UL 61010-1 and CSA C22.2 No. 61010-1.

These marks are tied to the type number; the datasheet lists 707087 and 707088 for the rail Ex marking and 707083, 707086 and 707088 for the SIL certificate, so 707088 sits at the intersection.

Specification table for 707088/8-06

Measuring inputs Two independent inputs: RTD, thermocouple, resistance 10 to 400 or 10 to 2000 ohm, voltage -20 to 100 mV
RTD ranges Pt100 -200 to +850 C; Pt200 -200 to +850 C; Pt500 -200 to +500 C; Pt1000 -200 to +250 C; Ni100/Ni120 -60 to +250 C; Cu50/Cu100 -180 to +200 C
Output 4 to 20 mA or 20 to 4 mA, HART 7 (FSK 0.5 mA, 1200 baud)
Pt100 accuracy Typical 0.08 C digital, 0.1 C at current output (0.1 K class)
Galvanic isolation AC 2 kV input to output
Response time RTD 0.9 to 1.3 s; thermocouple 0.8 s
Sensor current 0.3 mA or less
Alarm levels 3.6 mA or less (low) or 21 mA or more (high, adjustable 21.5 to 23 mA); SIL mode low only
Approvals UL 61010-1 on all types
Supply DC 12 to 42 V; DC 12 to 32 V in SIL operation
Ambient, Ex, zone 1 T6 -40 to +46 C; T5 -40 to +61 C; T4 -40 to +85 C
SIL ambient -40 to +70 C
Protection IP20
Weight About 100 g
Mounting TH 35 rail per DIN EN 60715
Scope of delivery Transmitter, SIL safety manual, Ex safety manual, quick start guide

Why the temperature classes matter for 707088/8-06

A rail Ex device dissipates heat inside a cabinet, so its permitted ambient temperature falls as the required temperature class gets stricter: only +46 C is allowed at T6, +61 C at T5 and the full +85 C at T4. In Gulf installations without cabinet cooling it is worth deciding early which class the sensor-side gas group and ignition temperature require, because the cabinet interior may well exceed 46 C in summer.

How 707088/8-06 differs from other dTRANS T07 variants

Against 707087 (rail, Ex, no SIL) this version adds the SIL certificate and trades some freedom: SIL mode limits supply to 32 V, ambient to +70 C, alarm to the low level (3.6 mA or less) and removes some two-channel modes and the output correction function. Against 707086 (head, Ex and SIL) the electronics are the same, but 707088 is a 100 g IP20 cabinet device instead of a 40 to 50 g puck. Against 707083 it adds hazardous-area approval.

Wiring and commissioning notes for 707088/8-06

Read the Ex safety manual and the SIL safety manual that ship in the box before wiring; the datasheet states that only the operating documents define the permitted connection. The loop is fed from an Ex-i repeater supply or isolating amplifier on the non-Ex side, type 707530/38 in the manufacturer accessory list (part 00577948). Configure through the two 2 mm HART sockets on the front using a communicator or PACTware with the JUMO DTM, and lock parameters with the software password. After a configuration change, verify the loop against the SIL manual procedure.

Sensor lines: three- and four-wire RTDs accept up to 50 ohm per wire, two-wire accepts 0 to 30 ohm compensation. Thermocouples need compatible compensation cable up to the terminals; internal cold-junction compensation uses a Pt100.

Where 707088/8-06 is used in Oman and the GCC

Typical homes are oil and gas processing, petrochemical units, power-plant auxiliary systems and water desalination chemical dosing areas, where intrinsically safe isolation and a verified safety integrity level are specified. Replacement for an existing 707088 on an operating plant avoids repeating a safety loop validation.

Measurement quality: Pt100 typical error 0.08 C digital and 0.1 C analog; long-term drift 0.016 percent of span or 0.04 C after one year. Response time is 0.9 to 1.3 s for RTDs and 0.8 s for thermocouples.

Configuration flexibility remains broad even in a certified device. Beyond the default Pt100 three-wire setup, the same unit accepts thermocouple and resistance sensors, applies a first-order digital filter from 0 to 120 s, corrects the 4 and 20 mA output points when not in SIL operation, and supports multidrop addressing 0 to 63 outside SIL mode. The 50/60 Hz mains frequency filter is built in, interference immunity meets the industrial requirement of the IEC/EN 61326 series and NAMUR NE21, and pollution degree 2 with measurement category II according to IEC 61010-1 applies. Altitude is permitted up to 4000 m, and the housing is polycarbonate with nickel-plated brass terminals and gold-plated contacts.

Documents and quotation

We can send the manufacturer datasheet (707080) with the quotation for 707088/8-06. Please include the exact part number 707088/8-06, the quantity, and the target certification so we can confirm availability through our RFQ process.

Selection Notes for the JUMO 707088/8-06

When comparing the JUMO 707088/8-06 with alternatives, start from the duty it must perform: the measured or controlled variable, the range and accuracy you need, the environment at the mounting point and the interface to your control system. Check the electrical and mechanical connections against the installed equipment, and confirm any hazardous-area or ingress-protection requirements for the location. If any point is unclear, send a photo of the nameplate and a short description of the application, and we will compare it with the JUMO temperature transmitters range and confirm the correct order code before you commit.

Datasheets & Documents
  • PDF Datasheet JUMO 707088/8-06 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.

Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.

JUMO company profile

Established 1948, Fulda, Germany, by Moritz Kurt Juchheim
First products Glass and contact thermometers; platinum glass sensors from 1966
Ownership Family-owned; renamed JUMO GmbH & Co. KG in 2003
Product families RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments

Milestones

  • 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
  • 1966: Platinum glass temperature sensors are added.
  • 2003: The parent company is renamed JUMO GmbH & Co. KG.

JUMO products we list

Family Models Typical use
RTD and thermocouple probes 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp Temperature measurement in pipes, vessels, machines, HVAC and food plants
Thermowells and inserts 909710 thermowells, 909740 measuring inserts Protecting sensors and replacing them without opening the process
Temperature transmitters dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch Converting sensor signals to 4-20 mA, HART or IO-Link
Pressure and level dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 Pressure in process, hydraulic and OEM systems; tank and well level
Controllers, limiters and recorders DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T Furnace, oven and process control, over-temperature protection and recording
Liquid analysis and flow AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 pH, conductivity, oxygen and turbidity in water treatment; liquid flow

Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.

Where JUMO products are used

In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.

Ordering JUMO products: what we need

Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.

Facts checked against JUMO's company history, October 2026.

FAQ

Questions about the JUMO 707088/8-06 dTRANS T07 Ex SIL Rail Transmitter

Answers from our engineering team on installation, compatibility and integration.

01Does 707088/8-06 have both Ex and SIL approval?
Yes. Type 707088 is listed under the ATEX/IECEx Ex marking and the TUV SIL 2/3 certificate according to IEC 61508.
02Which ambient temperature limits apply to Ex use of 707088/8-06?
In zone 1 the rail device allows -40 to +46 C at T6, -40 to +61 C at T5 and -40 to +85 C at T4.
03What restrictions apply in SIL mode on 707088/8-06?
Supply is limited to DC 12 to 32 V, ambient to +70 C, alarm to the low level, and not all two-channel modes are available.
04How is 707088/8-06 powered and supplied in the Ex loop?
As a two-wire loop-powered device through an Ex-i repeater supply or isolating amplifier, such as type 707530/38 from the accessory list.
05What documents ship with 707088/8-06?
The transmitter, a SIL safety manual, an Ex safety manual and a quick start guide.