Brand:

AUMA SAR 07.2 Modulating Multi-Turn Actuator

Description

Overview

AUMA SAR 07.2 is an AUMA NORM multi-turn actuator for modulating duty (class C, ISO 22153) with a tripping-torque window of 15 to 30 Nm and 10 output speeds from 4 to 90 rpm. SAR 07.2 is the smallest modulating AUMA SAR actuator. It combines a 15 to 30 Nm tripping-torque window with intermittent S4-25 percent duty, class C according to ISO 22153, for valves that must be positioned continuously rather than just opened and closed.

Seven Star LLC, a trusted supplier of AUMA products for Oman and the GCC, supplies the SAR 07.2 as genuine factory product and supports control-loop commissioning from its Muscat office.

Operating Principle

Short motor pulses from an AM or AC positioner move the SAR 07.2, which holds position by self-locking. Duty is S4 – 25 percent, class C, with a modulating torque of 15 Nm and up to 1,500 starts per hour at 4 to 45 rpm. The minimum pulse is 50 ms.

Engineering Design of the AUMA SAR 07.2

Starts per hour are limited to 1,500 up to 45 rpm and 1,200 at 63 and 90 rpm, with a minimum pulse duration of 50 ms. For reversal of rotation direction the motor must be powered for 260 ms at 4 rpm, shortening to 60 ms at 90 rpm, which should be considered in the positioner dead-band.

Key Features

Specifying the SAR 07.2 comes down to these points:

  • Compact modulating multi-turn actuator for small control valves.
  • Torque switches can be set from 15 up to 30 Nm, giving a 2.0:1 adjustment span.
  • At 20 Nm the S4 – 50 percent figure sits at 67 percent of the highest tripping torque.
  • Dividing the top torque by the quoted weight gives 1.5 to 1.6 Nm/kg.
  • An illustrative stroke of 12 turns takes about 32.7 seconds at 22 rpm.
  • It is the smallest torque class in this series and is followed by the SAR 07.6.
  • Separate AUMA documents list the dimensions and the electrical data.

Selecting the AUMA SAR 07.2

A modulating actuator is specified differently from an open-close unit. For the AUMA SAR 07.2, the permissible torque during continuous positioning is only 15 Nm at S4-25 percent and 10 Nm at S4-50 percent, which is lower than the 30 Nm maximum tripping torque. The tripping torque protects the valve in the end positions; the modulating torque is what the valve must need while it is being throttled. Always compare the valve’s running torque, not its seating torque, with the modulating column.

Typical partners are small globe control valves, needle and stop valves used for flow regulation, small modulating gate valves and dosing valves where a rising-stem control element needs a 4 to 20 mA position set-point.

The first question on a modulating actuator is whether the valve really needs it. A small control valve that is moved only a few times per shift can run on a SA 07.2 with a simple open-close control, while the AUMA SAR 07.2 pays off when the loop acts every few seconds. In that case the position transmitter, the dead band of the positioner and the minimum pulse of 50 ms decide the accuracy. Setting the dead band too tight makes the actuator hunt and wastes motor life, so start with a dead band of about 0.5 to 1 percent of stroke and tighten only if the process requires it.

Sizing example for the AUMA SAR 07.2

Consider an illustrative small control valve that needs 12 Nm continuous running torque at the plug and 24 Nm at the seat. The running torque is below the 15 Nm modulating limit at S4-25 percent, and the seat torque is below the 30 Nm tripping limit, so the AUMA SAR 07.2 is suitable. Because the S4-50 percent limit is only 10 Nm, this valve cannot be run at the higher duty ratio. A 15-turn stroke at 11 rpm takes about 82 seconds, so 1 percent of stroke is moved in less than a second. These numbers are an illustrative calculation and not AUMA data.

Installation and Mounting of the AUMA SAR 07.2

At 19 to 20 kg the AUMA SAR 07.2 can be lifted by one technician. The F07 or F10 flange and the 26 or 34 mm stem bore suit small control valves, and the 160 mm handwheel is used for setting and emergency operation only. Always mount the actuator with the plug/socket connector pointing down or sideways, and combine it with AUMA MATIC AM or AUMATIC AC controls, because the AUMA NORM version needs external controls.

Industrial Applications

In Oman the AUMA SAR 07.2 suits desalination dosing skids, boiler blow-down and feed-water trim valves, district-cooling bypass valves in Muscat buildings and small flow-control valves at gas and utility stations in industrial estates. Its F07 and F10 interface and IP68 enclosure allow installation on compact skids without a protective cabinet.

Alongside the SAR 07.2, our genuine AUMA range includes the AUMA SAR 14.1 multi-turn actuator, the AUMA MATIC AM/AC integral actuator controls and the AUMA SAREx explosion-proof modulating actuator.

Neighbouring sizes and counterparts: AUMA SAR 07.6 modulating actuator, AUMA SA 07.2 multi-turn actuator and AUMA SAREx 07.2 explosion-proof modulating actuator.

Technical Specifications

Data of the AUMA SAR 07.2 from the AUMA technical data sheet for 3-phase AC motors.

Parameter Specification
Model AUMA SAR 07.2
Trip torque range (S4 – 25 percent) 15 to 30 Nm
S4 – 50 percent limit 20 Nm
Permitted modulating torque 15 Nm (S4-25%) and 10 Nm (S4-50%)
Starts/h, max. 1,500 per hour (1,200 per hour at 63 and 90 rpm)
Minimum motor pulse 50 ms
Pulse on reversal, max. 260 ms at 4 rpm down to 60 ms at 90 rpm
Output speed steps 4 to 90 rpm at 50 Hz, 4.8 to 108 rpm at 60 Hz, 10 steps
Mounting flange EN ISO 5210 F07 and F10; DIN 3210 G0 (option; not offered with F07)
Rising-stem bore 26 mm (34 mm with the F10 flange; 30 mm maximum with the PMMA stem protection tube)
Manual wheel 160 mm
Unit weight 19 to 20 kg
Housing protection IP68
Back-drive protection Yes

Setpoint guide for the SAR 07.2 (illustrative calculation, not AUMA data)

Breakaway torque (Nm) Setpoint at +25 percent (Nm)
12 15
14 18
16 20
18 23
22 28
24 30

Stroking time for 12 turns at the SAR 07.2 (illustrative calculation, not AUMA data)

rpm at 50 Hz rpm at 60 Hz Seconds for 12 turns at 50 Hz
4 4.8 180
5.6 6.7 129
8 9.6 90
11 13 65
16 19 45
22 26 33
32 38 23
45 54 16
63 75 11
90 108 8

Ordering details for SAR 07.2

The SAR 07.2 technical data lists the valve mounting arrangement as F07 / F10 (ISO 5210), DIN 3210 G0. Identify the modulating duty, starts per hour and output speed at the installation frequency on the enquiry.

Technical reference

Request a Quote for AUMA SAR 07.2

Send Seven Star LLC your valve data and loop requirements to receive a quotation for the AUMA SAR 07.2. The AUMA datasheet can be downloaded from this page.

Datasheets & Documents
  • PDF Datasheet AUMA SAR 07.2 - SAR 16.2 Technical Data Sheet (covers AUMA SAR 07.2) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

AUMA builds electric actuators for industrial valves, gates and dampers. The company was founded in 1964 near Stuttgart by Werner Riester and Rudolf Dinse, moved its headquarters to Müllheim in south-west Germany in the early 1970s, and still trades as the owner-managed AUMA Riester GmbH & Co. KG. Its actuators run isolation and control valves in water, power, oil and gas and process plants worldwide.

Seven Star LLC is an independent supplier listing AUMA multi-turn and part-turn actuators, actuator controls, gearboxes and spare parts for buyers in Oman and the GCC. We work from the nameplate data so that a replacement matches the installed actuator, controls and gearbox.

AUMA company profile

Origin Founded in 1964 by Werner Riester (engineering) and Rudolf Dinse (sales and finance); registered as Riester KG in Esslingen. Water and wastewater plants were the first customers.
Headquarters Müllheim, Baden-Württemberg, Germany (since the early 1970s). Production in Germany, with further plants in India, the USA and China, and around 30 sales and service companies worldwide.
Ownership Privately held, owner-managed company: AUMA Riester GmbH & Co. KG
Torque and thrust range Multi-turn, part-turn and linear actuators from 1.5 Nm to 675,000 Nm with gearboxes, and linear thrust up to 217 kN, as published by AUMA
Design principle Modular: actuator, integral controls and gearbox are combined to suit the valve, so one actuator size can serve open-close, modulating, fieldbus or explosion-proof duty

Milestones

  • 1964: Werner Riester and Rudolf Dinse found AUMA near Stuttgart; the first actuator range follows, with water and sewage plants as the first customers.
  • Early 1970s: Lack of space in Nellingen leads to the move to Müllheim in south-west Germany.
  • 1974: AUMA Benelux, the first foreign subsidiary, is founded.
  • Today: About 2,800 employees worldwide, around 850 of them in Müllheim, according to AUMA.

AUMA actuator, controls and gearbox series

Series Type Typical use
SA 07.2 to SA 16.2, SA 25.1 to SA 40.1 Multi-turn actuators, open-close duty Gate and globe valves, sluice gates and penstocks; SA 07.2 to 16.2 cover roughly 10 to 1,000 Nm, the .1 sizes go far higher
SAR 07.2 to SAR 30.1 Multi-turn actuators, modulating duty Control valves that receive a continuous position setpoint and many starts per hour
SAV, SARV, SQV, SQRV Variable-speed actuators Slow approach to the seat to limit water hammer, fast travel elsewhere
SQ 05.2 to SQ 14.2, SQR Part-turn actuators Ball, butterfly and plug valves and dampers, about 50 to 2,400 Nm; SQR for modulating duty; FQM fail-safe unit for spring-return action
SAEx, SAREx, SQEx, PROFOX-MX, TIGRON Explosion-proof actuators Hazardous areas in oil, gas and chemical plants, with ATEX and IECEx certified versions
AUMA MATIC AM, AUMATIC AC, ACExC 01.2, AMExC 01.1, AC 01.2-SIL Integral actuator controls AM for simple parallel wiring; AC for positioning, diagnostics and fieldbus (PROFIBUS DP, PROFINET, Modbus, FOUNDATION Fieldbus, HART depending on version); SIL version for safety functions
GS, GHE, SA + GS combination Part-turn worm gearboxes Large butterfly and ball valves, from GS 63.3 up to GS 630.3 at 675,000 Nm
GK, GST, GHT, GP Multi-turn gearboxes (bevel, spur, worm, planetary) Offset or right-angle drives and very high multi-turn torque
LE, SVC/SVCR, PROFOX-L Linear actuators and thrust units Globe and control valves with a rising stem, up to 217 kN
PROFOX-M, PROFOX-Q Compact smart actuators Small valves where a full SA or SQ is oversized
SA-UW, SGM/SGMR, SVM/SVMR, SAN/SARN Special versions Submerged valves, seawater-exposed ship and offshore duty, nuclear plant service
SIMA2 Master station Fieldbus network management for many actuators on one plant

Where AUMA actuators are used

Water transmission and treatment is the largest use: pipeline isolation valves, pumping stations, desalination plants and sluice gates. AUMA actuators also run valves in power plant steam, feedwater and cooling systems, pipelines and tank farms, refineries and chemical plants, and on ships and offshore platforms. In the Gulf, check the ambient temperature rating, since actuators in direct sun can exceed 50 °C, and specify the enclosure protection for sand and humidity.

Ordering AUMA actuators and spare parts: what we need

For a replacement, send photos of the actuator, motor and controls nameplates: type designation, commission or order number, serial number and wiring diagram number. AUMA identifies the original build from the commission number. For a new actuator, add the valve type, required torque or thrust at the worst case, number of turns or swing angle, operating time, mounting flange to ISO 5210 or ISO 5211, stem or shaft dimensions, duty (open-close or modulating), supply voltage and frequency, control signals or fieldbus, and the hazardous-area marking required on site.

Facts checked against AUMA product information and the company history published by AUMA, October 2026.

FAQ

Questions about the AUMA SAR 07.2 Modulating Multi-Turn Actuator

Answers from our engineering team on installation, compatibility and integration.

01What is the torque range of the AUMA SAR 07.2?
The tripping torque of the AUMA SAR 07.2 is adjustable between 15 and 30 Nm at S4 - 25 percent and up to 20 Nm at S4 - 50 percent.
02What modulating performance does the AUMA SAR 07.2 offer?
The AUMA SAR 07.2 is rated for S4 - 25 percent modulating duty, class C, with a modulating torque of 15 Nm (S4-25%) and 10 Nm (S4-50%). It allows 1,500 per hour (1,200 per hour at 63 and 90 rpm), with a minimum pulse of 50 ms and a reversal delay of 260 ms at 4 rpm down to 60 ms at 90 rpm.
03Which valve flange and stem size does the AUMA SAR 07.2 fit?
The AUMA SAR 07.2 uses EN ISO 5210 F07 or F10 flanges with rising-stem capacity of 26 mm (34 mm on F10, 30 mm with the PMMA stem protection tube), and DIN 3210 G0 as an option on F10. The handwheel is 160 mm in diameter.
04When should I choose the AUMA SAR 07.2 instead of a neighbouring size?
Choose the AUMA SAR 07.2 when the valve's maximum torque is below about 30 Nm and its running torque during throttling stays under 15 Nm. If the valve is stiffer, the SAR 07.6 (30 to 60 Nm) uses the same flange and handwheel and doubles the available torque.
05Is Seven Star LLC a trusted supplier for AUMA products?
Yes. Seven Star LLC supplies genuine AUMA products across Oman and the GCC. The AUMA SAR 07.2 is supplied as genuine AUMA product with documentation and regional technical support from our Muscat team.