Brand:

Honeywell STG89L SmartLine STG800 Gauge Pressure Transmitter

Description

Honeywell STG89L overview

Honeywell STG89L tops the STG800 SmartLine gauge range at 10,000 psi (689.47 bar). Whereas the lower models of the line are chosen for process control, the STG89L is a specialist unit for ultra-high-pressure hydraulics, intensifiers and test rigs. The datasheet gives it a minimum span of 100 psi (6.89 bar), a maximum turndown of 100:1 and an overpressure limit of 15,000 psi (1,035 bar).

Accuracy is stated as 0.055 percent of span standard and 0.040 percent optional, higher than the 0.030 percent of the other L models because of its wider range. A special 10,150 psi (700 bar) variant is mentioned in the datasheet and must be arranged through a sales representative.

STG89L: what it offers

  • Range minus 14.7 to 10,000 psi (minus 1.01 to 689.47 bar).
  • Standard accuracy 0.055 percent, optional 0.040 percent; A term 0.015, B 0.040 standard or 0.025 optional.
  • Knee C of 1,000 psi (68.94 bar).
  • Total performance 0.093 percent of span at 2,000 psi.
  • Overpressure limit 15,000 psi (1,035 bar).

STG89L datasheet values

Parameter Value
Model STG89L (STG800 SmartLine gauge pressure, L-suffix)
Upper / lower range limit 10000 psi (689.47 bar) / -14.7 psi (-1.01 bar)
Minimum span 100 psi (6.89 bar)
Maximum turndown 100:1
Accuracy (standard / optional) 0.055 / 0.040 percent of span
Stability (percent of URL per year, 15 years) Up to 0.010 for the STG800 family
Reference turndown (standard / high accuracy) 10:1 / 10:1
Accuracy knee C 1000 psi (68.94 bar)
Temperature coefficients (D / E / F) 0.0400 / 0.025 / 0.01
Total performance example 0.093 percent of span at 2000 psi
MAWP 10000 psi (690 bar)
Overpressure limit 15000 psi (1035 bar)
Output / protocols 4 to 20 mA, Honeywell DE, HART 7 or FOUNDATION Fieldbus
Supply voltage HART: 10.8 to 42.4 VDC (load 0 to 1,440 ohms); DE: 15 to 49.3 VDC; FOUNDATION Fieldbus: 9.0 to 32.0 VDC
Response time As fast as 80 ms
Rated ambient / meter body temperature -40 to 85 degC / -40 to 110 degC (operative limit 125 degC)
Process connections (STG80L inline) 1/2-inch NPT female, 1/2-inch NPT male, 9/16-18 high-pressure cone and thread female, G1/2-B male, DIN 19213 (except STG89L)
Wetted parts (STG80L) 316L stainless steel or Hastelloy C-276 diaphragm and process head
Fill fluid Silicone 200, CTFE, NEOBEE M-20 or Silicone 704
Housing Polyester powder-coated low-copper aluminium, Type 4X / IP66 / IP67; stainless housing optional
Net weight (STG80L) 3.6 lb (1.6 kg) with aluminium housing
Additional features Plugged impulse line detection option; NAMUR NE-107 diagnostics (HART, FF); display languages EN, DE, FR, IT, ES, RU, UK, TR, CN, JP

STG89L compared with the rest of the STG800 L-suffix line

The STG89L is the odd one in the L series on three counts. First, accuracy: 0.055 percent standard versus 0.030 for the STG84L, STG87L and STG88L. Second, turndown: 100:1 versus 200:1. Third, the DIN 19213 connection is not offered, while it is available on the other L models.

Its minimum span of 100 psi is more than three times that of the STG88L (30 psi) and forty times that of the STG84L (2.5 psi). If your normal pressure is below 3,000 psi, a lower range will give better resolution.

Model URL Max turndown Std accuracy DIN 19213
STG84L 500 psi 200:1 0.030% Yes
STG88L 6000 psi 200:1 0.030% Yes
STG89L 10000 psi 100:1 0.055% No

Where STG89L fits in Oman and the GCC

Typical STG89L uses are waterjet cutting, hydrostatic testing of pipe and pressure vessels, autofrettage and intensifier circuits, high-pressure injection of chemicals into wells and laboratory pressure systems. In the GCC it is found in service company workshops and test benches rather than in the main process.

Where hydrostatic test certificates are needed, a transmitter like this works alongside the dead-weight tester to record pressure electronically.

Selection notes for STG89L

Confirm that the mating fitting is rated for 10,000 psi: the usual choice is 9/16-18 high-pressure cone and thread female. Check the wetted parts (316L stainless steel or Hastelloy C-276) against the medium, decide the fill fluid and ask about the 700 bar variant if your test standard is 10,150 psi.

As with other high-range devices, do not select 10,000 psi where 6,000 psi would suffice.

Setting up STG89L

Because of the pressures involved, only trained staff should connect the unit. Use rated tubing, supports and safety shields where your site rules require, pressurise gradually and check connections with a leak solution. Configure the range and damping only after the pressure has stabilised.

Observe the loop supply limits for your protocol.

Inspection, diagnostics and spares

Inspect the high-pressure fitting at every disassembly and replace sealing components where specified; calibrate against a dead-weight tester at defined intervals. HART and fieldbus diagnostics provide condition information.

Buyer FAQ for STG89L

What is the range of the Honeywell STG89L? It spans minus 14.7 psi to 10,000 psi (minus 1.01 to 689.47 bar), with a minimum span of 100 psi (6.89 bar).

What is the overpressure limit of the STG89L? The STG800 datasheet gives an overpressure limit of 15,000 psi (1,035 bar) for the STG89L.

Is there a 700 bar version of the STG89L? The datasheet notes a special 10,150 psi (700 bar) option; contact your supplier for availability.

What accuracy does the STG89L have? Standard accuracy is 0.055 percent of span, with 0.040 percent available as the high-accuracy option.

Which connections does the STG89L offer? The L models list NPT female or male, 9/16-18 high-pressure cone and thread female and G1/2-B male, but DIN 19213 is excluded for the STG89L.

Documents and quotation

The STG800 specification 34-ST-03-83 covers the STG89L; it is available with the quotation.

To request a quotation for Honeywell STG89L, send part number, quantity, range, connection style and approval to Seven Star LLC.

Installation and Commissioning Planning

Planning ahead shortens downtime when a Honeywell STG89L goes into service. Confirm the available mounting space, cable entry or process connection, and the tools and spare seals needed on the day. Keep the existing configuration or calibration data so the new unit can be set up to match, and check that loop drawings and the asset register are updated after the swap. If the installation has to fit a short shutdown window, tell us the date when you request a quotation so that delivery of the Honeywell equipment can be planned around it.

Other Models in the STG800L Range

Seven Star LLC supplies models from the STG800L range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Honeywell STG83L SmartLine STG800 Gauge Pressure TransmitterPressure TransmittersView details
Honeywell STG84L SmartLine STG800 Gauge Pressure TransmitterPressure TransmittersView details
Honeywell STG88L SmartLine STG800 Gauge Pressure TransmitterPressure TransmittersView details
Honeywell STG89L SmartLine STG800 Gauge Pressure TransmitterPressure TransmittersYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Honeywell STG89L SmartLine STG800 Gauge Pressure Transmitter Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).

Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.

Honeywell company profile

Origins 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927
Brands in our range Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance
Gent Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005
Elster Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015

Milestones

  • 1885: The Butz thermostat business starts in Minneapolis.
  • 1927: It merges with Mark Honeywell's company.
  • 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
  • 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.

Honeywell products we list

Family Models Typical use
Fixed gas detectors Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID Flammable, toxic and VOC gas detection in process areas
Sensors, flame detection and control SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel Replacement sensors, fire detection and gas detection control panels
Transmitters and flow SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis Process pressure and mass flow measurement
Elster gas metering Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display Gas meters, volume correction and fiscal flow computing
Gent fire alarm systems Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell Addressable and conventional fire alarm systems in buildings and plants
Chadwick-Helmuth rotor track and balance 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor Helicopter rotor track and balance and propeller balancing

Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.

Where Honeywell products are used

In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.

Ordering Honeywell products: what we need

Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.

Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.

FAQ

Questions about the Honeywell STG89L SmartLine STG800 Gauge Pressure

Answers from our engineering team on installation, compatibility and integration.

01What is the range of the Honeywell STG89L?
It spans minus 14.7 psi to 10,000 psi (minus 1.01 to 689.47 bar), with a minimum span of 100 psi (6.89 bar).
02What is the overpressure limit of the STG89L?
The STG800 datasheet gives an overpressure limit of 15,000 psi (1,035 bar) for the STG89L.
03Is there a 700 bar version of the STG89L?
The datasheet notes a special 10,150 psi (700 bar) option; contact your supplier for availability.
04What accuracy does the STG89L have?
Standard accuracy is 0.055 percent of span, with 0.040 percent available as the high-accuracy option.
05Which connections does the STG89L offer?
The L models list NPT female or male, 9/16-18 high-pressure cone and thread female and G1/2-B male, but DIN 19213 is excluded for the STG89L.