Honeywell STA840 SmartLine Absolute Pressure Transmitter, 500 psia
Description
Why the Honeywell STA840 suits mid-range absolute pressure loops
Engineers pick the Honeywell STA840 when a process pressure has to be measured against absolute zero and the pressure can climb as high as 500 psia (34.47 bara). That covers compressor suction and discharge, steam headers, gas-lift manifolds, reactor feed lines and boiler-feed systems where an atmospheric reference would add the error of barometric weather to the reading. The STA840 is the dual-head, bracket-mounted absolute model of the SmartLine STA800 range and the one with the widest rangeability: 200:1, from a 500 psia ceiling down to a minimum span of 2.5 psia (0.17 bara).
Inside the STA840 sits a piezoresistive silicon sensor with on-chip temperature compensation, characterised at the factory and stored in the meter body. Honeywell lists a standard reference accuracy of 0.030 percent of span, an optional 0.025 percent, and a long-term stability of 0.010 percent of upper range limit per year over 15 years.
STA840 technical specifications
| Parameter | Value |
|---|---|
| Model | STA840, dual-head absolute pressure |
| Upper range limit | 500 psia (34.47 bara) |
| Lower range limit | 0 psia |
| Minimum span | 2.5 psia (0.17 bara) |
| Maximum turndown | 200:1 |
| Reference accuracy, percent of span | 0.030 standard, 0.025 optional |
| Stability | 0.010 percent of URL per year for 15 years |
| Reference turndown (standard accuracy) | 10:1 |
| Reference turndown (high-accuracy option) | 25:1 |
| Total performance example | 0.058 percent of span at 100 psia, 5:1 turndown, 50 degF (28 degC) shift |
| Meter body temperature, rated | -40 to 110 degC (-40 to 230 degF) |
| Meter body temperature, operative limit | -40 to 125 degC (-40 to 257 degF) |
| Maximum allowable working pressure | 500 psia (35 barA) |
| Overpressure and no-burst | 1.5 times MAWP; no-burst at 3 times MAWP because MAWP is under 2,000 psi |
| Response time | 80 ms HART and DE, 150 ms Fieldbus |
| Weight with aluminium housing | 8.3 lb (3.8 kg) |
Where STA840 differs from the neighbouring STA800 models
Three numbers separate this model from the rest of the family. First, range: the STA822 stops at 780 mmHgA, the STA840 at 500 psia and the STA87L at 3000 psia. Second, turndown: the STA840 is rated 200:1, while the STA822 offers only 15.6:1. Third, accuracy: the STA840 quotes 0.030 percent of span against 0.0375 percent for the STA822, and its total-performance example of 0.058 percent of span at 100 psia is less than a quarter of the STA822 figure.
It also has a sibling, the STA84L, which shares the 500 psia range and the 0.030 / 0.025 accuracy figures but uses an in-line body that weighs 3.6 lb (1.6 kg) and offers more thread choices, including half-inch NPT male, 9/16 Aminco and G half-B. Choose this one when you want a bracket-mounted dual-head unit with vent and drain plugs, process heads in carbon steel, 316 stainless, Hastelloy or Monel, and a DIN 19213 or half-inch NPT female connection.
Materials, fill fluids and options for STA840
- Barrier diaphragm: 316L stainless steel, Hastelloy C-276, Monel 400, tantalum, or gold-plated 316L, Hastelloy and Monel.
- Process head: zinc-plated carbon steel, 316 stainless, Hastelloy C-276 or Monel 400.
- Head gaskets: glass-filled PTFE as standard, with Viton or graphite on request.
- Fill fluid: Silicone 200, CTFE or Silicone 704. Silicone 704 has a minimum temperature rating of 0 degC, while CTFE is rated down to -40 degC.
- Bolting: zinc-plated carbon steel as standard, with 316 stainless, NACE A286 bolts and nuts, or NACE A286 bolts with 304 nuts as options.
- Housing: polyester powder-coated low-copper aluminium, Type 4X and IP66/IP67, with an all-stainless housing optional.
Optional features worth specifying here are the plugged impulse line detection function, up to three customer-specified calibrations stored in the meter body for HART and Fieldbus units, a lightning-protection terminal block, and the advanced graphic display with bar graph or trend view.
Typical STA840 applications in Gulf process industries
In Omani gas processing it is a natural fit for absolute measurement on sales-gas compressor suction, where inlet pressure drifts a few psi either side of atmospheric during start-up. In power and water plants it monitors deaerator and low-pressure feedwater heater shells. In petrochemical units it serves reactor and column pressure measurement where reaction equilibrium depends on absolute pressure, and in manufacturing it is used on vacuum-assisted packaging and sterilisation lines.
Its 200:1 rangeability means a single part number can be re-ranged on site. A plant that stocks one as a spare can cover a 0 to 10 psia vacuum duty today and a 0 to 400 psia duty tomorrow, within the minimum span of 2.5 psia, provided the accuracy at that turndown is acceptable. Use the datasheet total-performance equation to confirm that.
Commissioning checklist for the STA840
- Confirm the order code and the range stamped on the nameplate against the loop sheet.
- Check the loop supply: HART needs 10.8 to 42.4 VDC at the terminals, with load of 0 to 1,440 ohms; intrinsically safe versions are limited to 30 VDC.
- Wire the terminals; polarity does not matter because the connection is polarity insensitive, and the terminal block accepts conductors up to 16 AWG (1.5 mm).
- Perform a loop test and a zero trim against a known absolute reference, remembering that atmospheric pressure is not zero on an absolute scale.
- Set damping and failure mode: standard limits are 3.8 to 20.8 mA, NAMUR NE 43 limits are 3.8 to 20.5 mA, with failure at 3.6 mA or below, or 21.0 mA or above.
- Lock the write-protect and record the final configuration.
Care, calibration and spares for STA840
The datasheet advises verifying calibration every four years. Between visits the transmitter watches its own meter body, electronics, configuration data and sensor communication, and flags tamper attempts. A modular construction lets maintenance staff swap the display, the electronics module or the lightning-protection assembly in the field, while the meter body carries its own characterisation, so a replacement electronics module does not require recalibration of the sensor.
Ordering the Honeywell STA840 from Seven Star LLC
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. This is a model code, so please give us the complete order string from the nameplate where possible, or at least the protocol, housing, approval, diaphragm and fill-fluid choices.
Documents and quotation
Honeywell specification 34-ST-03-85 for the STA840 is attached as the datasheet. Send your RFQ with the part number STA840, quantity, protocol, approvals and any special material requirements, and we will respond with availability and lead time.
Datasheets & Documents
- Datasheet Honeywell STA840 SmartLine Absolute Pressure Transmitter, 500 psia Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).
Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.
Honeywell company profile
| Origins | 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927 |
|---|---|
| Brands in our range | Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance |
| Gent | Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005 |
| Elster | Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015 |
Milestones
- 1885: The Butz thermostat business starts in Minneapolis.
- 1927: It merges with Mark Honeywell's company.
- 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
- 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.
Honeywell products we list
| Family | Models | Typical use |
|---|---|---|
| Fixed gas detectors | Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID | Flammable, toxic and VOC gas detection in process areas |
| Sensors, flame detection and control | SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel | Replacement sensors, fire detection and gas detection control panels |
| Transmitters and flow | SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis | Process pressure and mass flow measurement |
| Elster gas metering | Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display | Gas meters, volume correction and fiscal flow computing |
| Gent fire alarm systems | Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell | Addressable and conventional fire alarm systems in buildings and plants |
| Chadwick-Helmuth rotor track and balance | 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor | Helicopter rotor track and balance and propeller balancing |
Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.
Where Honeywell products are used
In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.
Ordering Honeywell products: what we need
Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.
Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.
Browse Honeywell products by category: Fire & Gas Detector, Vibration, Flowmeters, Pressure Instrumentation, Temperature Instrumentation.
FAQ
Questions about the Honeywell STA840 SmartLine Absolute Pressure
Answers from our engineering team on installation, compatibility and integration.
01What range does the Honeywell STA840 cover?
The STA840 measures 0 to 500 psia (0 to 34.47 bara) with a minimum span of 2.5 psia (0.17 bara), so turndown can reach 200:1.
02What is the accuracy of the STA840?
Standard reference accuracy is 0.030 percent of span and the optional figure is 0.025 percent. At 100 psia with 5:1 turndown and a 28 degC shift, the datasheet total performance is 0.058 percent of span.
03What is the difference between the STA840 and STA84L?
They share range and accuracy figures, but the STA840 is the 3.8 kg dual-head model with a process head, while the STA84L is a 1.6 kg in-line transmitter with several male and female thread options.
04What failure-mode currents does the STA840 use?
Honeywell standard limits are 3.8 to 20.8 mA and NAMUR NE 43 limits are 3.8 to 20.5 mA; failure mode is at or below 3.6 mA or at or above 21.0 mA.
05Can the STA840 handle full vacuum?
It operates within specification above 25 mmHgA (33 mbarA) and short-term exposure to full vacuum, defined as two hours at 70 degC, does not damage it.