Honeywell STG73S SmartLine STG700 Gauge Pressure Transmitter
Description
Overview of the Honeywell STG73S
The Honeywell STG73S is listed in the STG700 specification as a separate model row from the STG735, even though both cover 50 psi (3.5 bar). The S-suffix part number is the one to look for when the installed base or the purchase specification names it exactly; ordering a STG735 against an STG73S tag changes the temperature and turndown figures.
For a low-pressure gauge application the STG73S gives a minimum span of 0.5 psi (0.035 bar), a lower range limit of minus 14.7 psi (minus 1.0 bar) and HART 7 communication. The published coefficients, a reference turndown of 8:1 and a knee of 6 psi (0.42 bar), position it as the more economical, slightly less refined companion to the STG735.
STG73S feature highlights
- Range from minus 14.7 psi to 50 psi (minus 1.0 to 3.5 bar).
- Reference turndown 8:1; knee C of 6 psi (0.42 bar).
- Temperature effect 0.100 plus 0.015 times URL over span per 28 degC.
- Total performance 0.187 percent of span at 10 psi.
- Overpressure 1.5 times the 50 psi MAWP.
Datasheet values for STG73S
| Parameter | Value |
|---|---|
| Model | STG73S (STG700 SmartLine gauge pressure) |
| Upper range limit | 50 psi (3.5 bar) |
| Lower range limit | -14.7 psi (-1.0 bar) |
| Minimum span | 0.5 psi (0.035 bar) |
| Maximum turndown | 100:1 |
| Reference accuracy | 0.065 percent of span (A 0.005, B 0.060) |
| Accuracy knee C | 6 psi (0.42 bar) |
| Temperature effect | 0.100 + 0.015 x URL/span, percent of span per 28 degC |
| Total performance example | 0.187 percent of span at 10 psi |
| Stability | 0.020 percent of URL per year, quoted over ten years |
| MAWP | 50 psi (3.5 bar) |
| Output / protocol | Two-wire 4 to 20 mA with HART 7 |
| Supply voltage and loop load | 10.8 to 42.4 VDC at the terminals (intrinsically safe versions limited to 30 VDC); load 0 to 1,440 ohms |
| Response time | 100 ms; turn-on time 2.5 s; damping 0 to 32 s, default 0.5 s |
| Rated ambient / meter body temperature | -40 to 85 degC / -40 to 110 degC (operative limit 125 degC) |
| Overpressure | 1.5 x MAWP of the model |
| Process connections | Dual head: 1/2-inch NPT female. Inline: 1/2-inch NPT female or male, 9/16-18 high-pressure cone and thread female, G1/2-B male |
| Wetted diaphragm / head | 316L stainless steel or Hastelloy C-276 diaphragm; heads in carbon steel (zinc plated), 316 SS or Hastelloy C-276 (dual head), 316L SS or Hastelloy C-276 (inline) |
| Fill fluid | Silicone or CTFE |
| Housing | Polyester powder-coated low-copper aluminium, Type 4X / IP66 / IP67; stainless housing optional |
| Net weight | Dual head 8.3 lb (3.8 kg); inline 3.6 lb (1.6 kg), with aluminium housing |
How STG73S differs from other STG700 variants
The STG73S and STG735 are the same range and share the same 0.5 psi minimum span. They differ in the performance coefficients: reference turndown 8:1 against 16.7:1, knee 6 psi against 3 psi, D coefficient 0.100 against 0.070 and E coefficient 0.015 against 0.008. In total-performance terms that is 0.187 percent of span against 0.128 percent at 10 psi.
Against the STG74S (500 psi) the STG73S has the finer range; against the STG77S, STG78S and STG79S it is the only one rated for sub-100 psi use.
| Parameter | STG73S | STG735 |
|---|---|---|
| Reference turndown | 8:1 | 16.7:1 |
| Knee C | 6 psi (0.42 bar) | 3 psi (0.21 bar) |
| Temperature D + E | 0.100 + 0.015 | 0.070 + 0.008 |
| Total perf. at 10 psi | 0.187% | 0.128% |
Oman and GCC uses for STG73S
The STG73S is typically placed on utility pressure points where trending matters more than tight accuracy: instrument air receivers in oil terminals, nitrogen headers, boiler fuel gas supply and the discharge of low-head process air blowers in wastewater plants.
It is also suitable for tank blanket pressure on chemical storage in industrial zones around Sohar and Duqm, and as a replacement where an existing STG73S tag is already documented.
Selection checklist for STG73S
When replacing an existing STG73S keep the model code, since the S suffix is part of the model designation. Confirm the process connection style of the unit being replaced (the datasheet shows dual head with 1/2-inch NPT female and inline with NPT, cone-and-thread or G1/2-B male options).
Specify stainless steel housing if the site is on the coast and washdown is frequent.
Commissioning STG73S step by step
Install with a short impulse line and isolation valve. For vacuum measurements fit the transmitter below the tap and use the lowest range available. Observe the minimum supply voltage of 10.8 VDC and the 1,440 ohm maximum load.
Perform a zero trim at atmospheric pressure after warm-up.
Maintenance and diagnostics
Check the zero annually and perform a full verification every two years. A transmitter reading below zero at vented conditions typically needs only a zero trim.
Delivery to Sites in Oman and the GCC
Delivery of the Honeywell STG73S is arranged to suit the site, whether that is a plant in Sohar or Duqm, an oilfield location in the interior, or a project elsewhere in the GCC. Tell us the delivery point, any site access or gate-pass requirements, and the person who will receive the goods. Goods are packed to protect sensitive pressure transmitters equipment during road or air transport, and shipping details are shared once the order is dispatched so that your stores team can plan receipt and inspection.
Selection Notes for the Honeywell STG73S
When comparing the Honeywell STG73S with alternatives, start from the duty it must perform: the measured or controlled variable, the range and accuracy you need, the environment at the mounting point and the interface to your control system. Check the electrical and mechanical connections against the installed equipment, and confirm any hazardous-area or ingress-protection requirements for the location. If any point is unclear, send a photo of the nameplate and a short description of the application, and we will compare it with the Honeywell pressure transmitters range and confirm the correct order code before you commit.
Frequently asked about STG73S
What is the difference between the Honeywell STG73S and STG735? Both cover 50 psi, but the STG73S has 8:1 reference turndown and 0.187 percent total performance at 10 psi versus 16.7:1 and 0.128 percent for the STG735.
What range does the STG73S offer? It spans minus 14.7 psi to 50 psi (minus 1.0 to 3.5 bar), with a minimum span of 0.5 psi (0.035 bar).
What is the MAWP of the STG73S? The datasheet gives a maximum allowable working pressure of 50 psi (3.5 bar), the same as its upper range limit.
Does the STG73S support HART? Yes, it provides HART 7 digital communication superimposed on a two-wire 4 to 20 mA loop.
What stability is stated for the STG73S? The STG700 datasheet quotes stability of 0.020 percent of URL per year, stated over a ten-year period.
Documents and quotation
The STG700 datasheet is available with your quote.
To get an offer for Honeywell STG73S, send part number, quantity, range and approvals to Seven Star LLC.
Other Models in the STG700 Range
Seven Star LLC supplies models from the STG700 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Honeywell STG735 SmartLine STG700 Gauge Pressure Transmitter | Pressure Transmitters | View details |
| Honeywell STG745 SmartLine STG700 Gauge Pressure Transmitter | Pressure Transmitters | View details |
| Honeywell STG775 SmartLine STG700 Gauge Pressure Transmitter | Pressure Transmitters | View details |
| Honeywell STG73S SmartLine STG700 Gauge Pressure Transmitter | Pressure Transmitters | You are viewing this model |
| Honeywell STG78S SmartLine STG700 Gauge Pressure Transmitter | Pressure Transmitters | View details |
| Honeywell STG79S SmartLine STG700 Gauge Pressure Transmitter | Pressure Transmitters | View details |
Datasheets & Documents
- Datasheet Honeywell STG73S SmartLine STG700 Gauge Pressure Transmitter Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).
Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.
Honeywell company profile
| Origins | 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927 |
|---|---|
| Brands in our range | Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance |
| Gent | Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005 |
| Elster | Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015 |
Milestones
- 1885: The Butz thermostat business starts in Minneapolis.
- 1927: It merges with Mark Honeywell's company.
- 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
- 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.
Honeywell products we list
| Family | Models | Typical use |
|---|---|---|
| Fixed gas detectors | Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID | Flammable, toxic and VOC gas detection in process areas |
| Sensors, flame detection and control | SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel | Replacement sensors, fire detection and gas detection control panels |
| Transmitters and flow | SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis | Process pressure and mass flow measurement |
| Elster gas metering | Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display | Gas meters, volume correction and fiscal flow computing |
| Gent fire alarm systems | Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell | Addressable and conventional fire alarm systems in buildings and plants |
| Chadwick-Helmuth rotor track and balance | 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor | Helicopter rotor track and balance and propeller balancing |
Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.
Where Honeywell products are used
In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.
Ordering Honeywell products: what we need
Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.
Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.
Browse Honeywell products by category: Fire & Gas Detector, Vibration, Flowmeters, Pressure Instrumentation, Temperature Instrumentation.
FAQ
Questions about the Honeywell STG73S SmartLine STG700 Gauge Pressure
Answers from our engineering team on installation, compatibility and integration.
01What is the difference between the Honeywell STG73S and STG735?
Both cover 50 psi, but the STG73S has 8:1 reference turndown and 0.187 percent total performance at 10 psi versus 16.7:1 and 0.128 percent for the STG735.
02What range does the STG73S offer?
It spans minus 14.7 psi to 50 psi (minus 1.0 to 3.5 bar), with a minimum span of 0.5 psi (0.035 bar).
03What is the MAWP of the STG73S?
The datasheet gives a maximum allowable working pressure of 50 psi (3.5 bar), the same as its upper range limit.
04Does the STG73S support HART?
Yes, it provides HART 7 digital communication superimposed on a two-wire 4 to 20 mA loop.
05What stability is stated for the STG73S?
The STG700 datasheet quotes stability of 0.020 percent of URL per year, stated over a ten-year period.