- Automation & ControlView all 2,859 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Honeywell
Honeywell STD735 SmartLine STD700 Differential Pressure Transmitter
Description
Honeywell STD735 in brief
The Honeywell STD735 sits in the middle of the STD700 range and is the model most plants end up stocking, because 100 psi (7.0 bar) of differential covers the large majority of orifice plates, venturis and pump-suction filters found in process piping. A bidirectional span of minus 100 to plus 100 psi lets the same unit read reverse differential, which is useful on bidirectional lines and on flooded tank systems.
What you get is a piezoresistive sensor with on-chip temperature and static pressure measurement, two-wire HART 7 communication and an optional two-line LCD. The minimum span is 1 psi (0.07 bar), so a 20 psi application still enjoys a 20:1 turndown. Seven Star LLC is an independent supplier serving Oman and the wider GCC and is not affiliated with the manufacturer.
What the STD735 brings to a loop
- URL 100 psi (7.0 bar) and LRL minus 100 psi (minus 7.0 bar), a symmetrical window.
- Standard accuracy up to 0.05 percent of span with reference turndown 4:1 and knee C of 25 psi (1.75 bar).
- Temperature effect 0.070 plus 0.015 times URL over span per 28 degC shift.
- Static pressure effect 0.100 plus 0.020 times URL over span per 1,000 psi line pressure.
- Stability 0.020 percent of URL per year for ten years and response time of 100 ms.
- Lightning protection terminal block available as a field-added module.
STD735 datasheet values
| Parameter | Value |
|---|---|
| Model | STD735 (STD700 SmartLine differential pressure) |
| Upper range limit | 100 psi (7.0 bar) |
| Lower range limit | -100 psi (-7.0 bar) |
| Minimum span | 1 psi (0.07 bar) |
| Maximum turndown | 100:1 |
| Reference accuracy | 0.05 percent of span (A 0.005, B 0.045) |
| Reference turndown | 4:1; accuracy knee C = 25 psi (1.75 bar) |
| Temperature effect | 0.070 + 0.015 x URL/span, percent of span per 28 degC |
| Static pressure effect | 0.100 + 0.020 x URL/span, percent of span per 1,000 psi |
| Total performance example | 0.255 percent of span at 20 psi, 5:1 turndown |
| Output / protocol | Two-wire 4 to 20 mA with HART 7 |
| Supply voltage and loop load | 10.8 to 42.4 VDC at the terminals (intrinsically safe versions limited to 30 VDC); load 0 to 1,440 ohms |
| Response time | 100 ms (delay plus time constant); turn-on time 2.5 s |
| Damping | 0 to 32 s in 0.1 s steps, default 0.50 s |
| Ambient temperature (rated) | -40 to 85 degC; storage -55 to 120 degC |
| Meter body temperature (rated) | -40 to 110 degC; operative limit 125 degC |
| Maximum allowable working pressure | 4,500 psi (310 bar); overpressure 1.5 x MAWP |
| Process connection | 1/4-inch NPT, or 1/2-inch NPT with adapter (DIN requirements met) |
| Wetted diaphragm | 316L stainless steel or Hastelloy C-276 |
| Fill fluid | Silicone 200 or CTFE |
| Housing | Polyester powder-coated low-copper aluminium, Type 4X / IP66 / IP67; stainless housing optional |
| Net weight | 8.3 lb (3.8 kg) with aluminium housing |
How STD735 differs from other STD700 variants
Against the STD725 the STD735 trades small-span sensitivity for pressure capacity: its minimum span is 1 psi (0.07 bar) rather than 4 inH2O (10 mbar), and the knee is 25 psi instead of 25 inH2O. Against the STD775 the STD735 has a tighter minimum span, 1 psi versus 30 psi, which is why a 0 to 20 psi flow range is better served by the STD735 than by the 3,000 psi body.
Note the total performance figures in the datasheet: 0.255 percent of span for the STD735 at 20 psi, compared with 0.270 percent for the STD725 at 80 inH2O and 0.252 percent for the STD775 at 600 psi. All three are within a few thousandths of a percent of each other, so choose by range first and accuracy second.
| Model | LRL | URL | Min span |
|---|---|---|---|
| STD725 | -400 inH2O | 400 inH2O | 4 inH2O |
| STD735 | -100 psi | 100 psi | 1 psi |
| STD775 | -100 psi | 3000 psi | 30 psi |
Where STD735 earns its place in Oman and the GCC
Oil and gas facilities in Oman use differential transmitters of this class on separator level legs, heater-treater inlets and pump strainers. Power and desalination plants use them across feedwater flow elements, condenser water boxes and heat-exchanger bundles. In general manufacturing the STD735 is routinely the unit behind a compressed-air flow meter or a process cooling water loop.
Because the display can present a square-root flow value, one STD735 serves both as a pressure device and as a flow indicator on an orifice run.
Choosing and pairing STD735
Select the STD735 when the working differential falls between about 1 and 100 psi and the process may reverse. Verify the wetted material against the medium: barrier diaphragms are 316L stainless steel or Hastelloy C-276, process heads are 316 stainless steel, zinc-plated carbon steel or Hastelloy C-276, and head gaskets are glass-filled PTFE with Viton or graphite as options.
Fill fluid is silicone 200 or CTFE, selected at ordering. Head and bolting choices should follow the line static pressure rating of 4,500 psi, de-rated to 3,000 psi between minus 26 and minus 40 degC and with graphite o-rings.
Mounting, piping and commissioning STD735
Use the two-inch bracket and orient the process heads so vent valves can be reached. Install three-valve or five-valve manifolds with equalising valves, always opening the equalising valve before the block valves when bringing the transmitter on line.
Power the loop from 10.8 to 42.4 VDC, observe the load limit of 1,440 ohms at the highest supply voltage, and configure damping (default 0.50 seconds) from the display or Field Device Manager.
Maintenance, diagnostics and spares
Keep a record of zero shift at each two-year verification. Typical failure indicators are a sensor communication timeout or configuration data corruption; both are flagged as critical diagnostics through HART. The meter body, display and electronics are modular and replaceable individually, which keeps spares inventory low.
Buyer questions on STD735
What is the pressure range of the Honeywell STD735? The STD735 offers a URL of 100 psi (7.0 bar), LRL of minus 100 psi (minus 7.0 bar) and a minimum span of 1 psi (0.07 bar).
What is the static pressure limit of the STD735? The STD700 family is rated to a maximum allowable working pressure of 4,500 psi (310 bar), de-rated to 3,000 psi from minus 26 to minus 40 degC.
Can the STD735 show flow directly? Yes, the optional display can show a calculated square-root flow value in addition to the analog output signal.
What diaphragm materials are available for the STD735? Barrier diaphragms are 316L stainless steel or Hastelloy C-276, with 316 stainless steel, carbon steel or Hastelloy process heads.
How often should the STD735 be verified? The datasheet recommends a calibration verification every two years under normal conditions.
Documents and quotation
The STD700 specification 34-ST-03-121 covers the STD735 accuracy tables, approvals and drawings and is available on request with your enquiry.
For a quote on Honeywell STD735, send part number, quantity, calibrated range, HART or analog option and required hazardous area approval to Seven Star LLC.
Other Models in the STD700 Range
Seven Star LLC supplies models from the STD700 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Honeywell STD725 SmartLine STD700 Differential Pressure Transmitter | Pressure Transmitters | View details |
| Honeywell STD735 SmartLine STD700 Differential Pressure Transmitter | Pressure Transmitters | You are viewing this model |
| Honeywell STD775 SmartLine STD700 High Range DP Transmitter | Pressure Transmitters | View details |
Datasheets & Documents
- Datasheet Honeywell STD735 SmartLine STD700 Differential Pressure Transmitter Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).
Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.
Honeywell company profile
| Origins | 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927 |
|---|---|
| Brands in our range | Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance |
| Gent | Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005 |
| Elster | Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015 |
Milestones
- 1885: The Butz thermostat business starts in Minneapolis.
- 1927: It merges with Mark Honeywell's company.
- 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
- 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.
Honeywell products we list
| Family | Models | Typical use |
|---|---|---|
| Fixed gas detectors | Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID | Flammable, toxic and VOC gas detection in process areas |
| Sensors, flame detection and control | SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel | Replacement sensors, fire detection and gas detection control panels |
| Transmitters and flow | SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis | Process pressure and mass flow measurement |
| Elster gas metering | Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display | Gas meters, volume correction and fiscal flow computing |
| Gent fire alarm systems | Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell | Addressable and conventional fire alarm systems in buildings and plants |
| Chadwick-Helmuth rotor track and balance | 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor | Helicopter rotor track and balance and propeller balancing |
Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.
Where Honeywell products are used
In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.
Ordering Honeywell products: what we need
Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.
Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.
Browse Honeywell products by category: Fire & Gas Detector, Vibration, Flowmeters, Pressure Instrumentation, Temperature Instrumentation.
FAQ
Questions about the Honeywell STD735 SmartLine STD700 Differential
Answers from our engineering team on installation, compatibility and integration.
01What is the pressure range of the Honeywell STD735?
The STD735 offers a URL of 100 psi (7.0 bar), LRL of minus 100 psi (minus 7.0 bar) and a minimum span of 1 psi (0.07 bar).
02What is the static pressure limit of the STD735?
The STD700 family is rated to a maximum allowable working pressure of 4,500 psi (310 bar), de-rated to 3,000 psi from minus 26 to minus 40 degC.
03Can the STD735 show flow directly?
Yes, the optional display can show a calculated square-root flow value in addition to the analog output signal.
04What diaphragm materials are available for the STD735?
Barrier diaphragms are 316L stainless steel or Hastelloy C-276, with 316 stainless steel, carbon steel or Hastelloy process heads.
05How often should the STD735 be verified?
The datasheet recommends a calibration verification every two years under normal conditions.