Brand:

Danfoss 032L1104 EVR 32 Solenoid Valve, 1 5/8 in ODF, NC

Description

EVR 32: a cast-iron servo-piston solenoid valve for large refrigerant lines

Danfoss 032L1104 is an EVR 32 normally closed solenoid valve with 1 5/8 in ODF connections. Unlike the smaller brass EVR 10 and EVR 20, the body is cast iron and the valve uses a servo piston instead of a diaphragm. The orifice is 22.23 mm, the Kv value is 16.7 m3/h and the net weight is 4.42 kg.

The maximum working pressure is 45.2 bar (655 psig), the medium range is -40 to 105 C and the ambient limit -40 to 80 C. The minimum opening differential is 0.2 bar (2.9 psi), higher than for the diaphragm types, and MaxOPD is 38 bar with a 10 W AC coil, 31 bar with a BJ/BX coil and 17 bar with a 20 W DC coil.

Technical specifications

Parameter Specification
Danfoss code number 032L1104
Type EVR 32
Ambient temperature -40 – 80 C
Approvals as listed EAC; UL; UA
Body material Cast iron
Function NC
Inlet connection type Solder, ODF
Inlet size 1 5/8 in
Kv value 16.7 m3/h
Maximum working pressure 45.2 bar
MaxOPD 10W AC 38 bar
MaxOPD 20W DC 17 bar
MaxOPD coil BJ/BX 31 bar
Medium temperature range -40 C to 105 C
MinODP 0.2 bar
MOPD Coil Dependent
Orifice size 22.23 mm
Outlet connection type Solder, ODF
Outlet size 1 5/8 in
Refrigerants R1234ze(E); R125; R134a; R22; R404A; R407A; R407C; R407F; R410A; R448A; and others listed in the data sheet
Type designation Solenoid valve, Solder
UL approved refrigerants R125; R134a; R152a; R22; R404A; R407A; R407C; R407F; R410A; R448A; and others listed in the data sheet
Valve operation Servo-piston
Net weight 4.42 kg
EAN 5702428943192

Servo-piston construction and its consequences

A piston valve tolerates dirty lines and large flows better than a diaphragm design, which suits discharge, liquid and suction lines on bigger commercial and light industrial plants. The price for this robustness is the 0.2 bar minimum differential: the valve needs that pressure difference to hold open, so check this in suction lines.

With an inlet of 1 5/8 in the valve is for line sizes of that class; the orifice and Kv value tell the engineer that this valve passes roughly eight times the flow of the EVR 10. Capacity tables for liquid, hot gas and suction are in the EVR 2 – EVR 40 data sheet.

Mounting and ordering checks

Support the pipe and the weight of the 4.4 kg valve; do not let the coil carry any load. Fit with the coil vertical or up to 90 degrees from vertical, and keep the piston area clean with an upstream filter. Brazing on the cast iron body needs a low-heat procedure.

Order the coil separately, in the voltage and power class that gives the opening differential you need. Check the refrigerant, function (NC) and connections before ordering. UL, EAC and UA approvals are listed on the page.

Other types and sizes from the same Danfoss family that appear in the Danfoss store listing include EVR 3 (032F1156), EVR 2 (032F1201), EVR 18 (032L1004), EVR 40 (032L1045), EVR 10 (032L1188), EVR 6 (032L1209), EVR 15 (032L1224), EVR 20 (032L1240). These are listed for orientation only; each has its own datasheet values, so check size, connection and version before ordering.

Related Danfoss products: Danfoss 032L1045 EVR 40 Solenoid Valve 2 1/8 in Solder NO, Danfoss 032L1188 EVR 10 Solenoid Valve 1/2 in Solder NC, Danfoss 032U7132 EV220B 32 Solenoid Valve G 1 1/4 NC, Danfoss 032U7115 EV220B 15 Solenoid Valve G 1/2 NC EPDM, Danfoss 032U3806 EV225B 20 Steam Solenoid Valve G 3/4 NC and Danfoss 032U7150 EV220B 50 Solenoid Valve G 2 NC 40 m3/h.

Documents and quotation

Attached for download: Danfoss Solenoid valve Type EVR 2 – EVR 40 AI249086497583en-001303 (manufacturer, unaltered), the manufacturer’s unaltered PDF. Browse comparable products in solenoid valves. To order, send us 032L1104 and the required quantity; Seven Star LLC is an independent supplier based in Muscat.

Datasheets & Documents
  • PDF Datasheet Danfoss Solenoid valve Type EVR 2 - EVR 40 AI249086497583en-001303 (manufacturer, unaltered) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.

Danfoss company profile

Founded 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966)
First product Thermostatic expansion valve for refrigeration
Headquarters Nordborg, Denmark
Ownership Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family
Size About 42,000 employees (2023)
Business segments Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics)
Brands in the group VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls

Milestones

  • 1932–1933: First expansion valve; the company is founded in Nordborg.
  • 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
  • 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
  • 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
  • 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
  • 2021: Acquisition of Eaton's hydraulics business.

Choosing Danfoss products

For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.

Where Danfoss products are used

In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.

Danfoss products we list

Family Examples
Variable speed drives and soft starters VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter
Solenoid valves and coils EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil
Pressure switches and thermostats KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101
Pressure transmitters MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2
HVAC and refrigeration valves AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element

Ordering Danfoss products: what we need

Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.

Facts checked against Danfoss's company history pages and published company data, October 2026.

Frequently Asked Questions

What is Danfoss 032L1104?
An EVR 32 normally closed solenoid valve, cast iron body, 1 5/8 in ODF, servo piston.
What is its Kv value?
16.7 m3/h.
Why is the minimum differential higher?
The servo-piston design needs 0.2 bar (2.9 psi), compared with 0.03 bar for the smaller diaphragm types.
Is the coil included?
No, it must be ordered separately.
Which document is attached?
The Danfoss EVR 2 - EVR 40 data sheet AI249086497583en-001303.