- Automation & ControlView all 1,611 products
- AC Drives
- Industrial Communications
- PLC & I/O Cards
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- Industrial Computers
- Servo Drives
- Motor Soft Starters
- HMI Displays
- Pneumatic Cylinders
- Isolator & Barrier
- Automation Software
- Machine Vision
- Robotics
Brand: Danfoss
Danfoss 032L1214 EVR 10 Solenoid Valve, 5/8 in ODF, NC
Description
EVR 10: a 5/8 in brass solenoid valve body for refrigerant liquid lines
Danfoss 032L1214 is an EVR 10 solenoid valve body, normally closed (NC), with 5/8 in (16 mm) ODF solder connections and a brass housing. Inside, a servo diaphragm lifts the main seat when the coil is energised, which lets a small coil control a 10 mm orifice. The Kv value is 2.2 m3/h and the net weight is 0.417 kg.
The ratings on the page are a maximum working pressure of 45.2 bar (655 psig), a medium temperature range of -40 to 105 C and an ambient range of -40 to 80 C. The valve is supplied without a coil: the coil is ordered separately and decides the maximum operating pressure differential.
Technical specifications
| Parameter | Specification |
|---|---|
| Danfoss code number | 032L1214 |
| Type | EVR 10 |
| Ambient temperature | -40 – 80 C |
| Approvals as listed | EAC; UL; UA |
| Body material | Brass |
| Function | NC |
| Inlet connection type | Solder, ODF |
| Inlet size | 5/8 in / 16 mm |
| Kv value | 2.2 m3/h |
| Maximum working pressure | 45.2 bar |
| MaxOPD 10W AC | 38 bar |
| MaxOPD 20W DC | 20 bar |
| MaxOPD coil BJ/BX | 38 bar |
| Medium temperature range | -40 C to 105 C |
| MinODP | 0.03 bar |
| MOPD | Coil Dependent |
| Orifice size | 10 mm |
| Outlet connection type | Solder, ODF |
| Outlet size | 5/8 in / 16 mm |
| Refrigerants | R1234yf; R1234ze(E); R125; R134a; R152a; R22; R290; R32; R404A; R407A; and others listed in the data sheet |
| Type designation | Solenoid valve, Solder |
| UL approved refrigerants | R125; R134a; R152a; R22; R290; R404A; R407A; R407C; R407F; R407H; and others listed in the data sheet |
| Valve operation | Servo-diaphragm |
| Net weight | 0.417 kg |
| EAN | 5702428952880 |
Coil choice and pressure differential
The MaxOPD values printed are 38 bar with a 10 W AC coil, 20 bar with a 20 W DC coil and 38 bar with a BJ/BX coil. The minimum opening differential is 0.03 bar (0.44 psi). Because the coil determines the MOPD, a wrong coil can leave the valve unable to open against the high-side pressure, so check the coil type in the Danfoss accessories list.
The EVR range is made for liquid, suction and hot-gas lines in refrigeration and air-conditioning with fluorinated refrigerants. The code with 10 mm orifice and a Kv of 2.2 m3/h sits in the lower-middle of the series, between the EVR 6 and the EVR 15.
Mounting and ordering checks
Install with the coil upward or within 90 degrees of vertical, and fit a filter-drier ahead of the valve, because particles lodge in the seat. Braze with the body wrapped in wet cloth. Insulate the valve where it is in a cold line. The page lists UL, EAC and UA approvals; 032L5098 appears as an identical product.
Confirm the function (NC or NO), the refrigerant, the coil voltage and the connection size before ordering. The EVR 2 – EVR 40 data sheet covers all sizes, and spare parts for the solenoid valve family are listed.
Other types and sizes from the same Danfoss family that appear in the Danfoss store listing include EVR 3 (032F1156), EVR 2 (032F1201), EVR 18 (032L1004), EVR 40 (032L1045), EVR 32 (032L1103), EVR 6 (032L1209), EVR 15 (032L1224), EVR 20 (032L1240). These are listed for orientation only; each has its own datasheet values, so check size, connection and version before ordering.
Related Danfoss products: Danfoss 032L1188 EVR 10 Solenoid Valve 1/2 in Solder NC, Danfoss 032L1045 EVR 40 Solenoid Valve 2 1/8 in Solder NO, Danfoss 032U7132 EV220B 32 Solenoid Valve G 1 1/4 NC, Danfoss 032U7115 EV220B 15 Solenoid Valve G 1/2 NC EPDM, Danfoss 032U5254 EV250B 18 Solenoid Valve G 3/4 NC 0 bar and Danfoss 032U7150 EV220B 50 Solenoid Valve G 2 NC 40 m3/h.
Documents and quotation
The attached file is the Danfoss Solenoid valve Type EVR 2 – EVR 40 AI249086497583en-001303 (manufacturer, unaltered). It is the manufacturer’s own PDF, hosted here unaltered. Related items sit under solenoid valves. Seven Star LLC is an independent supplier in Muscat; send the code 032L1214 with the quantity and we will quote.
Datasheets & Documents
- Datasheet Danfoss Solenoid valve Type EVR 2 - EVR 40 AI249086497583en-001303 (manufacturer, unaltered) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.
Danfoss company profile
| Founded | 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966) |
|---|---|
| First product | Thermostatic expansion valve for refrigeration |
| Headquarters | Nordborg, Denmark |
| Ownership | Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family |
| Size | About 42,000 employees (2023) |
| Business segments | Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics) |
| Brands in the group | VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls |
Milestones
- 1932–1933: First expansion valve; the company is founded in Nordborg.
- 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
- 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
- 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
- 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
- 2021: Acquisition of Eaton's hydraulics business.
Choosing Danfoss products
For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.
Where Danfoss products are used
In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.
Danfoss products we list
| Family | Examples |
|---|---|
| Variable speed drives and soft starters | VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter |
| Solenoid valves and coils | EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil |
| Pressure switches and thermostats | KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101 |
| Pressure transmitters | MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2 |
| HVAC and refrigeration valves | AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element |
Ordering Danfoss products: what we need
Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.
Facts checked against Danfoss's company history pages and published company data, October 2026.
Browse Danfoss products by category: AC Drives, Pressure Instrumentation, Control Valves, Solenoid Valve.
Related products
Frequently Asked Questions
An EVR 10 normally closed solenoid valve body with 5/8 in (16 mm) ODF connections and brass housing.
No. The coil is ordered separately and determines the maximum operating pressure differential.
2.2 m3/h.
Maximum working pressure 45.2 bar (655 psig); MaxOPD 38 bar with a 10 W AC coil.
The Danfoss EVR 2 - EVR 40 data sheet AI249086497583en-001303.


















Reviews
There are no reviews yet.