Brand:

JUMO 707086/8-06 dTRANS T07 Ex SIL Head Transmitter

Description

JUMO 707086/8-06 two-channel head transmitter with Ex and SIL approval

JUMO 707086/8-06 is the head-mounted, intrinsically safe and SIL-approved member of the dTRANS T07 range. The base type 707086 is listed by the manufacturer as dTRANS T07 B Ex SIL, a two-wire transmitter built for terminal head form B, and the suffix /8-06 selects the default configuration (0 to 100 C, Pt100 in three-wire circuit, 4 to 20 mA) with screw terminals. Because it combines two universal sensor inputs, HART 7 communication and both hazardous-area and functional-safety approvals in a puck-sized housing, it is the type that plant engineers reach for when a single sensor head in a classified zone must also feed a safety loop. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Spare and replacement demand for this exact code usually comes from plants that standardised their measuring points on the T07 B Ex SIL and now need an identical unit rather than a re-engineered loop. Quote it with the full code so the configuration and terminal style match what is already installed.

What the 707086/8-06 type designation tells you

  • 707086 is the basic type: head transmitter, Ex approval, SIL approval.
  • The digit 8 in the second block means default settings: measuring range 0 to 100 C, Pt100 three-wire circuit, 4 to 20 mA output.
  • The block 06 is the electrical connection type, screw terminals, rigid or flexible wire up to 2.5 mm2 (14 AWG); the datasheet recommends not using ferrules.

Because the transmitter is fully configurable over HART, the default code does not limit you. The range, sensor type, damping and alarm behaviour can be changed on site with a field communicator carrying the JUMO device description, or with a PC running PACTware and the JUMO DTM driver through a HART modem.

Hazardous-area and safety approvals of 707086/8-06

The Ex family 707085 to 707088 is certified under ATEX (certificate EPS 17 ATEX 1 129 X) and IECEx (EPS 17.0075X). For type 707086 the marking is II 1G Ex ia IIC T6 to T4 Ga and II 2G Ex ia IIC T6 to T4 Gb, so the electronics can sit in zone 0 or zone 1 when the loop is supplied from an associated intrinsically safe supply. The functional-safety approval is SIL 2/3 for hardware and software to IEC 61508, certified by TUV Sued under Z10 17 05 01028 0001, and is valid for types 707081, 707083, 707086 and 707088 only. The optional BD7 plug-on display carries its own ATEX and IECEx approval (II 2G Ex ia IIC T6 to T4 Gb).

In SIL operation the supply range narrows to DC 11 to 32 V, the ambient range to -40 to +70 C, and only the low alarm (3.6 mA or less) is allowed. Not every two-channel mode is available in SIL operation, so the safety manual supplied with this type governs the final configuration.

Technical specifications for 707086/8-06

Measuring inputs Two independent inputs: RTD, thermocouple, resistance 10 to 400 or 10 to 2000 ohm, voltage -20 to 100 mV
RTD ranges Pt100 -200 to +850 C; Pt200 -200 to +850 C; Pt500 -200 to +500 C; Pt1000 -200 to +250 C; Ni100/Ni120 -60 to +250 C; Cu50/Cu100 -180 to +200 C
Output 4 to 20 mA or 20 to 4 mA, HART 7 (FSK 0.5 mA, 1200 baud)
Pt100 accuracy Typical 0.08 C digital, 0.1 C at current output (0.1 K class)
Galvanic isolation AC 2 kV input to output
Response time RTD 0.9 to 1.3 s; thermocouple 0.8 s
Sensor current 0.3 mA or less
Alarm levels 3.6 mA or less (low) or 21 mA or more (high, adjustable 21.5 to 23 mA); SIL mode low only
Approvals UL 61010-1 on all types
Supply (standard) DC 11 to 42 V; SIL operation DC 11 to 32 V
Maximum burden (Ub max minus 11 V) divided by 0.023 A; at least 250 ohm needed for HART
Ambient, Ex zone 1, no display T6 -40 to +58 C; T5 -40 to +75 C; T4 -40 to +85 C
Ambient, Ex zone 0, no display T6 -40 to +46 C; T5 and T4 -40 to +60 C
Ambient, Ex zone 1, with BD7 T6 -40 to +55 C; T5 -40 to +70 C; T4 -40 to +85 C
Enclosure material Polycarbonate body, potted; nickel-plated brass terminals with gold-plated contacts
Protection IP00 as a bare head transmitter; IP66/67 in the optional field enclosure
Vibration 2 to 100 Hz at 4 g
Weight About 40 to 50 g
Switch-on About 10 s to HART, about 28 s to first valid current value

Features that matter on a 707086/8-06 measuring point

Two-channel operation is the main practical advantage. With both inputs wired, the transmitter can switch to the second sensor when the first fails, raise a drift warning when the two sensors disagree beyond a limit, switch between sensors that cover different ranges depending on temperature, or output an average or differential value. Corrosion detection per NAMUR NE89 on four-wire RTDs and thermocouples, wire-break and short-circuit detection, ambient limit monitoring and undervoltage detection (output drops below 3.6 mA for about 5 s and retries) keep the loop honest. Output failure levels follow NAMUR NE43: linear fall from 4.0 to 3.8 mA below range, linear rise from 20.0 to 20.5 mA above range.

Typical applications in Oman and the GCC

The datasheet positions the series for chemicals, oil, gas and power plants. In practice a type like this goes into wellhead and gathering-station skids, gas treatment trains, reformer and heater skin temperature points, and boiler or turbine auxiliary lines where a zone classification and a safety-integrity requirement coincide. Desert ambient temperature is rarely a limit: even the T6 class, the most restrictive, allows operation to +58 C in zone 1 without display, and the T4 class reaches +85 C.

How 707086/8-06 differs from other dTRANS T07 variants

707080 B-head, no Ex, no SIL, ambient -40 to +85 C
707081 B-head, SIL only
707082 and 707083 DIN rail (IP20), without and with SIL
707085 B-head, Ex only
707086/8-06 B-head, Ex and SIL combined; SIL ambient limit -40 to +70 C
707087 and 707088 DIN rail, Ex and Ex plus SIL

Choose the B-head versions when the transmitter sits next to the sensor in an AB7 terminal head (aluminium, M20 x 1.5 cable inlet, M24 x 1.5 protective-fitting thread, 420 g with the head) or in an FG7 field enclosure with two cable inlets. Choose a rail type when the electronics belong in a control cabinet. Only 707086 and 707088 give you both approvals; the head version is the one for field mounting.

Installation and commissioning of 707086/8-06

Mount the transmitter in a form B head per DIN EN 50446 with the spring-loaded screws, route sensor wires to terminals 3 to 7 and the loop to terminals 1 and 2. Use shielded wire from a sensor cable length of 30 m. Two-wire RTD connections allow a line-resistance compensation of 0 to 30 ohm; three- and four-wire circuits tolerate up to 50 ohm per wire. Connect the loop through an Ex-i repeater or isolating amplifier outside the hazardous area; the datasheet lists type 707530/38 for this purpose. Enable hardware write protection with the DIP switch on the BD7 display if fitted, and set a software password for the rest.

Specified long-term drift for a Pt100 is 0.016 percent of span or 0.04 C after one year and 0.028 percent or 0.06 C after five years, whichever is larger. A yearly loop check against a precision decade is enough for most plants; for SIL loops follow the proof-test interval in the safety manual. Accessories include the BD7 display (00672701), AB7 head (00672702), FG7 field housing (00672705), wall and tube mounting sets (00672707, 00672708) and a USB HART modem (00443447).

Typical buyers ask whether the Ex and SIL certificates apply together, which supply range is valid in SIL mode, what the default configuration is, and whether the display is included. The answers are in the FAQ above and in the datasheet; if something is not stated there we leave it out rather than guess.

Documents and quotation

The official JUMO datasheet for the T07 series (data sheet 707080) covers 707086/8-06 and is available on request together with the quotation. Send us the RFQ with the full part number 707086/8-06, the quantity, and any special range or linearisation you need so we can confirm availability and lead time.

Other Models in the DTRANS T07 Range

Seven Star LLC supplies models from the DTRANS T07 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
JUMO 707088/8-06 dTRANS T07 Ex SIL Rail TransmitterTemperature TransmittersView details
JUMO 707086/8-06 dTRANS T07 Ex SIL Head TransmitterTemperature TransmittersYou are viewing this model
JUMO 707082/8-06 dTRANS T07 DIN Rail Temperature TransmitterTemperature TransmittersView details
Datasheets & Documents
  • PDF Datasheet JUMO 707086/8-06 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.

Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.

JUMO company profile

Established 1948, Fulda, Germany, by Moritz Kurt Juchheim
First products Glass and contact thermometers; platinum glass sensors from 1966
Ownership Family-owned; renamed JUMO GmbH & Co. KG in 2003
Product families RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments

Milestones

  • 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
  • 1966: Platinum glass temperature sensors are added.
  • 2003: The parent company is renamed JUMO GmbH & Co. KG.

JUMO products we list

Family Models Typical use
RTD and thermocouple probes 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp Temperature measurement in pipes, vessels, machines, HVAC and food plants
Thermowells and inserts 909710 thermowells, 909740 measuring inserts Protecting sensors and replacing them without opening the process
Temperature transmitters dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch Converting sensor signals to 4-20 mA, HART or IO-Link
Pressure and level dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 Pressure in process, hydraulic and OEM systems; tank and well level
Controllers, limiters and recorders DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T Furnace, oven and process control, over-temperature protection and recording
Liquid analysis and flow AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 pH, conductivity, oxygen and turbidity in water treatment; liquid flow

Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.

Where JUMO products are used

In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.

Ordering JUMO products: what we need

Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.

Facts checked against JUMO's company history, October 2026.

FAQ

Questions about the JUMO 707086/8-06 dTRANS T07 Ex SIL Head Transmitter

Answers from our engineering team on installation, compatibility and integration.

01What does the suffix /8-06 mean on 707086/8-06?
The 8 selects the default settings of 0 to 100 C, Pt100 three-wire and 4 to 20 mA; 06 selects screw terminals.
02Is 707086/8-06 approved for zone 0?
Yes, the ATEX/IECEx marking includes II 1G Ex ia IIC T6 to T4 Ga, with zone 0 ambient limits of -40 to +46 C (T6) and up to +60 C (T5, T4) without display.
03What supply range applies to 707086/8-06 in SIL operation?
DC 11 to 32 V, versus DC 11 to 42 V in standard operation; SIL ambient is -40 to +70 C.
04Can 707086/8-06 take two sensors?
Yes, it has two universal inputs for RTD, thermocouple, resistance or mV signals, with backup, drift, average and differential functions.
05Does 707086/8-06 include a display?
No, the plug-on BD7 display (part 00672701) is an optional accessory with its own ATEX/IECEx approval.