Brand: Honeywell
Honeywell ToxiRAE Pro Wireless Personal Toxic Gas Monitor
Description
Honeywell ToxiRAE Pro wireless personal monitor for toxic gases and oxygen overview
The Honeywell ToxiRAE Pro is a pocket-size personal monitor for toxic gases and oxygen. The manufacturer describes it as the first wireless personal monitor of its kind: it can detect gases such as carbon monoxide, hydrogen sulfide, oxygen, ammonia, chlorine and formaldehyde, and it can pass live readings and alarm status to safety staff in a remote location when the wireless version is used.
Its intelligent interchangeable sensors store their own calibration data, so a user can monitor one gas one day and another the next by swapping the sensor. The monitor measures 118 x 60 x 30 mm, weighs 220 g and has a graphical LCD with white LED backlight. A Man Down alarm with real-time remote notification is included.
This page summarises the manufacturer documentation for the Honeywell ToxiRAE Pro for buyers in Oman and the GCC. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Key features of the ToxiRAE Pro
The following points come from the manufacturer datasheet for the ToxiRAE Pro.
- More than twenty intelligent, field-replaceable electrochemical sensors, most of them shared with the MultiRAE family.
- Five-way local and remote alarm notification: 95 dB audible alarm, vibration, flashing red LEDs, on-screen message and wireless notification.
- Man Down alarm with pre-alarm and real-time remote wireless notification.
- Continuous datalogging with three months of capacity at one-minute intervals, and a user-set interval from 1 to 3,600 seconds.
- Rechargeable lithium-ion battery with more than 30 hours of normal non-wireless operation and recharge in less than 4 hours.
- Fully automatic bump testing and calibration when used with the AutoRAE 2 system.
- Wireless range of about 200 m to a mesh router or host and about 100 m to a RAELink3 modem, with an optional built-in radio.
- IP-65 dust and water rating and hazardous area certifications including ATEX Ex ia IIC Ga T4 and IECEx Ex ia IIC Ga T4.
ToxiRAE Pro technical specifications
The table lists the main data for the ToxiRAE Pro from the manufacturer datasheet. Specifications are subject to change by the manufacturer, so confirm the configuration with your quotation.
| Parameter | Value |
|---|---|
| Model | ToxiRAE Pro |
| Size | 118 x 60 x 30 mm |
| Weight | 220 g |
| Sampling | Diffusion |
| Display | Graphical LCD with white LED backlight |
| Battery | Rechargeable Li-ion, over 30 hours, recharge under 4 hours |
| Alarm | 95 dB at 30 cm, vibration, red LEDs, wireless |
| Datalogging | Three months at one-minute intervals |
| Operating temperature | -20 to 55 degC |
| Humidity | 0 to 95 percent RH non-condensing |
| Ingress protection | IP-65 |
| Ammonia (NH3) range | 0 to 100 ppm |
| Carbon monoxide (CO) range | 0 to 500 ppm |
| CO extended range range | 0 to 2,000 ppm |
| Chlorine (Cl2) range | 0 to 50 ppm |
| Hydrogen sulfide (H2S) range | 0 to 100 ppm |
| H2S extended range range | 0 to 1,000 ppm |
| Oxygen (O2) range | 0 to 30 percent vol. |
| Sulfur dioxide (SO2) range | 0 to 20 ppm |
| Certifications | CSA Class I Div 1; ATEX II 1G Ex ia IIC Ga T4; IECEx Ex ia IIC Ga T4 |
| Warranty | Two years on O2 sensor; three years on H2S and CO sensors |
Typical applications in Oman and the GCC
Portable and transportable gas detectors protect people and plant wherever toxic, combustible or oxygen-deficient atmospheres can occur. Typical uses for the ToxiRAE Pro in Oman and the GCC include the following.
- Oil and gas: personal H2S and CO protection for upstream, refinery and pipeline workers, including turnaround crews.
- Utilities and power: confined space entry in tanks, culverts and cable tunnels.
- Water and wastewater: H2S and oxygen monitoring in sewers, pumping stations and treatment works.
- Manufacturing: chemical, steel, food and pharmaceutical sites that need single-gas personal monitors.
Selection and compatibility notes for the ToxiRAE Pro
Choose the ToxiRAE Pro when one worker needs personal protection against one toxic gas or oxygen deficiency. The sensor is selected when ordering and can be changed later, which reduces spares. For several gases at once, the MultiRAE family is the multi-gas option, and for a lower-cost CO or H2S only monitor the manufacturer offers the ToxiRAE 3.
Decide whether the wireless version is needed. Wireless units have a working radio and are ready for deployment, but non-wireless units cannot be upgraded later. Remote monitoring may need extra equipment or software licences, and country-specific wireless approvals should be checked with the manufacturer.
Installation and commissioning of the ToxiRAE Pro
Prepare the ToxiRAE Pro for service as described in the manufacturer user guide.
- Fit the sensor specified and charge the battery in the cradle before the first use.
- Perform a calibration, ideally on the AutoRAE 2, and record the result.
- Bump test before each day of use or as required by your safety procedure.
- Clip the monitor in the breathing zone and set alarm limits to your site procedure.
Maintenance and service life
Maintenance is simple: the sensor, filter and lithium-ion battery are replaceable. Calibrate sensors on installation as the manufacturer recommends, bump test regularly and keep the dust filter clean. Replace sensors at the end of their life and follow your site calibration interval.
Related products and ordering notes
Related Honeywell gas detectors available through Seven Star LLC on request include the MultiRAE Lite, ToxiRAE 3 and AutoRAE 2. Please state the gas, range and wireless requirement with your enquiry.
ToxiRAE Pro questions in brief
Typical questions about the ToxiRAE Pro concern sensors, alarms and certification. The answers below summarise the main points from the datasheet.
Documents and quotation
The manufacturer datasheet for the ToxiRAE Pro is available from Seven Star LLC with this listing when it is attached, and it should be read together with the installation manual before any engineering decision. To request a quotation, send an RFQ that states the part number ToxiRAE Pro, the quantity, the delivery location and, where relevant, the options you need. Seven Star LLC replies with availability and lead time; no price is published on this page.
Datasheets & Documents
- Datasheet Honeywell ToxiRAE Pro Wireless Personal Toxic Gas Monitor Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).
Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.
Honeywell company profile
| Origins | 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927 |
|---|---|
| Brands in our range | Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance |
| Gent | Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005 |
| Elster | Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015 |
Milestones
- 1885: The Butz thermostat business starts in Minneapolis.
- 1927: It merges with Mark Honeywell's company.
- 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
- 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.
Honeywell products we list
| Family | Models | Typical use |
|---|---|---|
| Fixed gas detectors | Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID | Flammable, toxic and VOC gas detection in process areas |
| Sensors, flame detection and control | SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel | Replacement sensors, fire detection and gas detection control panels |
| Transmitters and flow | SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis | Process pressure and mass flow measurement |
| Elster gas metering | Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display | Gas meters, volume correction and fiscal flow computing |
| Gent fire alarm systems | Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell | Addressable and conventional fire alarm systems in buildings and plants |
| Chadwick-Helmuth rotor track and balance | 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor | Helicopter rotor track and balance and propeller balancing |
Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.
Where Honeywell products are used
In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.
Ordering Honeywell products: what we need
Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.
Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.
Browse Honeywell products by category: Fire & Gas Detector, Vibration, Flowmeters, Pressure Instrumentation, Temperature Instrumentation.
FAQ
Questions about the Honeywell ToxiRAE Pro Wireless Personal Toxic Gas
Answers from our engineering team on installation, compatibility and integration.
01Which gases can the ToxiRAE Pro detect?
It accepts more than twenty sensors including CO, H2S, oxygen, ammonia, chlorine, formaldehyde, hydrogen cyanide and sulfur dioxide, each with its own range.
02Is the ToxiRAE Pro wireless?
Wireless and non-wireless versions are available. Non-wireless units cannot be upgraded to wireless later, so choose at ordering.
03How long does the ToxiRAE Pro battery last?
The rechargeable lithium-ion battery gives more than 30 hours of normal non-wireless operation and recharges in less than 4 hours.
04Can the ToxiRAE Pro be used in hazardous areas?
Yes. The datasheet lists CSA Class I Division 1, ATEX II 1G Ex ia IIC Ga T4 and IECEx Ex ia IIC Ga T4 certification.
05How can I request a quotation for the ToxiRAE Pro?
Send an RFQ with the part number, quantity and delivery location. Seven Star LLC will reply with availability and lead time; this page shows no price.


















Reviews