JUMO mTRON T 705020 4-Channel Analog Input Module
Description
Four isolated universal inputs on a 22.5 mm DIN-rail module
The JUMO mTRON T analog input module 4-channel (type 705020) adds four universal analog inputs to the modular mTRON T measuring, control and automation system. Each input is electrically isolated from the others and accepts thermocouples, RTD temperature probes, resistance transmitters, resistance or potentiometer signals and standard current or voltage signals. A dynamic A/D converter resolves up to 16 bit, and one extra digital input for DC 0/24 V covers a status contact. The digitised values are then available in the system for control, alarming and logging. Three LEDs show supply, module status and the digital input state. The module insert pulls out of the case at the front for service while the case and its bus board stay on the DIN rail, and a replaced insert configures itself automatically.
Technical specifications
| Parameter | Specification |
|---|---|
| Type | 705020 analog input module, 4 channels, plus 1 digital input |
| Analog inputs | 4, universal and isolated from each other; dynamic A/D resolution up to 16 bit |
| Thermocouples | L, J, U, T, K, E, N, S, R, B, C, D, W3Re-W26Re, Chromel-Copel, Chromel-Alumel, PLII, linear 0 to 75 mV; accuracy 0.1 to 0.15 % of range |
| Thermocouple ranges | K -200 to +1372 °C; J -200 to +1200 °C; S and R -50 to 1768 °C; B 0 to 1820 °C; D 0 to 2495 °C |
| Cold junction | Internal Pt100, accuracy ±1 K; ambient influence 300 ppm/K |
| RTD probes | Pt100 -200 to +850 °C (0.05 % in 3/4-wire, 0.15 % in 2-wire); Pt500; Pt1000; Ni100 -60 to +250 °C; Pt100 JIS -200 to +650 °C |
| Voltage inputs | DC 0(2) to 10 V (Ri > 500 kΩ) and DC 0 to 1 V (Ri > 100 kΩ); accuracy 0.05 % |
| Current inputs | DC 0(4) to 20 mA, voltage drop up to 2 V; accuracy 0.05 % |
| Resistance | Transmitter 100 Ω to 4 kΩ (±4 Ω); potentiometer below 400 Ω (±0.4 Ω) or 400 Ω to 4 kΩ (±4 Ω) |
| Circuit monitoring | Out-of-range, probe or cable break and short circuit detected, depending on sensor type |
| Digital input | 1 x DC 0/24 V, logic 0 = -3 to +5 V, logic 1 = +15 to +30 V |
| Functions | Offset and fine adjustment; linearisation by up to 45 value pairs or 4th-order polynomial; two limit alarms per input |
| Supply | DC 24 V +25/-20 %, 130 mA at DC 19.2 V, 3 W, fed through the base unit or a router module |
| Connection | 18 front terminals with removable Push-In strips, 0.14 to 1.5 mm² |
| Case | Plastic DIN-rail case, 22.5 x 103.6 x 101.5 mm, approx. 140 g, IP 20 |
| Ambient | -20 to +55 °C operating, -40 to +70 °C storage, up to 90 % humidity, up to 2000 m |
| Approvals | cULus (E201387); DNV GL (TAA000016N) with an approved power supply; AMS2750/CQI-9 extra code 879 |
| Stock version | 705020/36/000,000 (part 00566250) |
Measuring circuit monitoring and limit alarms
Each of the four inputs has two independent alarms, a minimum and a maximum, with their own limit values. Alarm type, event text, collective alarm, alarm suppression and alarm delay are configurable. Linearisations for more than 20 common probes are stored in the module, and a customer curve can be entered as up to 45 value pairs or a polynomial. The measuring circuit monitoring reports an out-of-range value for every sensor type. RTD probes, 4 to 20 mA and 2 to 10 V signals and potentiometers also report probe or cable break and short circuit, whereas thermocouples report range and break only. On any fault the digitised value moves to a defined state, which lets the system drop into a safe condition.
Ordering and typical uses
The order code is 705020/ supply / DNV / extra. Supply code 36 means DC 24 V, the DNV GL option is 062 and the AMS2750 or CQI-9 certificate option is extra code 879. The stock version 705020/36/000,000 is part number 00566250. Because the supply is fed through the system bus, the module needs a base unit or a router module beside it, for example the mTRON T central processing unit. For DNV GL installations use an approved power supply such as type 705090. During severe EMC interference the accuracy of the analog inputs may be reduced to ±1 %, so keep sensor cables screened and separate from power wiring.
The module suits plants where several temperatures or process signals must be logged or controlled from one mTRON T station: furnaces and ovens, heat-treatment lines, boilers, extruders, climate rooms and water treatment skids. Because the inputs are isolated, mixed sensor types and grounded thermocouples can share a module without ground loops. Pair it with the multichannel controller module 705010 when loops are needed, or use it alone to feed measured values to a PLC. The setup program or the multifunction panel 840 configures all inputs. Browse the PLC and I/O cards category for related modules.
An enquiry should list the number and type of sensors, the thermocouple or RTD types, the ranges and the wiring (2-wire, 3-wire or 4-wire), plus any standard signals or potentiometers. Tell us the base unit already installed, because the supply is taken from the system bus, and whether DNV GL or AMS2750 certification is required. With a stock version available as 705020/36/000, delivery is simple when no approval is needed.
Documents and quotation
The hosted document is JUMO data sheet 705020 (10 pages, English). Confirm sensor types, supply and approvals before ordering. Seven Star LLC is an independent supplier in Muscat; send the sensor list for a quotation.
See also: JUMO mTRON T 705010 Multichannel Controller Module.
Datasheets & Documents
- Datasheet JUMO 705020 data sheet 705020 (EN) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
JUMO is the German maker of temperature sensors, process controllers, pressure transmitters and liquid analysis instruments. Moritz Kurt Juchheim founded it in Fulda in 1948 as M. K. Juchheim KG, making glass thermometers with six employees. The name JUMO comes from the founder's name. It is still a family company headquartered in Fulda, and the parent company has been called JUMO GmbH & Co. KG since 2003.
Seven Star LLC is an independent supplier in Muscat. We list JUMO RTD and thermocouple probes, thermowells, transmitters, controllers, recorders and water analysis instruments, and supply them to process plants, OEMs, HVAC contractors and water utilities in Oman and the GCC by type number.
JUMO company profile
| Established | 1948, Fulda, Germany, by Moritz Kurt Juchheim |
|---|---|
| First products | Glass and contact thermometers; platinum glass sensors from 1966 |
| Ownership | Family-owned; renamed JUMO GmbH & Co. KG in 2003 |
| Product families | RTD and thermocouple probes, thermowells, temperature and pressure transmitters, controllers and thermostats, safety temperature limiters, paperless recorders, liquid analysis and flow and level instruments |
Milestones
- 1948: Moritz Kurt Juchheim founds M. K. Juchheim KG in Fulda, making glass thermometers with six employees.
- 1966: Platinum glass temperature sensors are added.
- 2003: The parent company is renamed JUMO GmbH & Co. KG.
JUMO products we list
| Family | Models | Typical use |
|---|---|---|
| RTD and thermocouple probes | 902020, 902030, 902050, 902120, 902006 2xPt100, PROCESStemp, mineral-insulated RTD, 901020 thermocouple, 901210, 902810 hygienic, 902550 surface, 902520 HVAC, MarineTemp | Temperature measurement in pipes, vessels, machines, HVAC and food plants |
| Thermowells and inserts | 909710 thermowells, 909740 measuring inserts | Protecting sensors and replacing them without opening the process |
| Temperature transmitters | dTRANS T01, T03, T04, T05, T06 SIL, T07 HART, T09, T1000 IO-Link, DELOS T switch | Converting sensor signals to 4-20 mA, HART or IO-Link |
| Pressure and level | dTRANS p20, p30, p31 hygienic, p33 Ex, p02 DELTA, MIDAS S05, MIDAS DP10, DELOS S02, MAERA S25, NESOS R20 | Pressure in process, hydraulic and OEM systems; tank and well level |
| Controllers, limiters and recorders | DICON touch, IMAGO 500, dTRON 316, iTRON, cTRON, diraTRON 104, eTRON T, safetyM STB/STW, safetyM TB/TW, LOGOSCREEN 601, mTRON T | Furnace, oven and process control, over-temperature protection and recording |
| Liquid analysis and flow | AQUIS touch S, AQUIS touch P, AQUIS 500 pH, AQUIS 500 CR, dTRANS pH 02, pH electrode, digiLine DO, ecoLine NTU, flowTRANS MAG H20, flowTRANS US W01 | pH, conductivity, oxygen and turbidity in water treatment; liquid flow |
Choosing a temperature sensor starts with the range and accuracy. A Pt100 RTD is accurate and stable from about -200 to 600 °C and is the usual choice in process plants. A thermocouple (type K or J, for example) covers much higher temperatures and responds faster but is less accurate. The wiring also matters: a 3-wire or 4-wire Pt100 connection cancels the resistance of the cable, while a 2-wire connection adds an error that grows with cable length. That is why a head-mounted transmitter is often fitted close to the sensor.
Where JUMO products are used
In Oman and the GCC, JUMO sensors and controllers are used in oil and gas and chemical plants, food and beverage production, plastics and metal heat treatment, HVAC and district cooling, water and wastewater treatment, swimming pools and marine applications.
Ordering JUMO products: what we need
Send the JUMO type number and the full order code from the label (for example 902020/10-...). For probes, add the sensor type (Pt100, Pt1000, type K or J), the number of wires, the insertion length and diameter, and the process connection. For controllers, add the input, outputs and supply voltage.
Facts checked against JUMO's company history, October 2026.
Browse JUMO products by category: Temperature Instrumentation, Pressure Instrumentation, Liquid Analysis Sensors, Controllers & Data Acquisition, Level Transmitter.
Related products
Frequently Asked Questions
Four universal analog inputs, each isolated, plus one digital input for DC 0/24 V.
Thermocouples, RTD probes, resistance transmitters, potentiometers, and current and voltage standard signals.
Yes, range, probe or cable break and short circuit are detected, depending on the sensor type.
Yes, use up to 45 value pairs or a polynomial up to the fourth order.
DC 24 V, fed through the base unit or router module over the system bus.