Brand:

Honeywell T7350H1017 Modulating Programmable Thermostat

Description

T7350H1017 at a glance

Honeywell T7350H1017 is the modulating, networked member of the T7350 line. Where its sibling relay model switches stages, this thermostat has two modulating outputs plus two relay stages, and it also exposes the same LONWORKS connection, humidity input, occupancy input and outdoor and discharge-air capability. It targets single-zone equipment with a modulating valve, damper or SCR, for example chilled water or hot water coils.

Facts are from Honeywell form 63-2605. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Output structure

The manufacturer table lists the modulating models as applications with 2 modulating stages and 2 relay stages. The modulating output is 4 to 20 mA into a terminating resistance of up to 510 ohm; the table notes 2 to 10 Vdc is possible by adding a 500 ohm resistor. The auxiliary relay on the H1017 is a Normally Open type. Throttling range adjusts automatically with heat and cool stages and can be set by hand using TStatSpec or a PDA.

T7350H1017 data sheet values

Parameter Value
Model T7350H1017
Application Modulating single zone
Stages 2 modulating plus 2 relay
Modulating output 4 to 20 mA, 510 ohm maximum terminating resistance
Auxiliary relay Normally Open
Network LONWORKS FTT with LonMark Space Comfort Controller profile
Supply 24 Vac, 50/60 Hz (20 to 30 Vac), 5 VA maximum without load
Relay outputs at 30 Vac 1.5 A running, 7.5 A inrush, N.O. SPST
Inputs Space 20K ohm; humidity 0 to 10 Vdc; outdoor 3000 ohm PTC; discharge air 20K ohm; occupancy dry contact 30 Vdc at 1 mA
Operating ambient 30 to 110 F (minus 1 to 43 C); shipping minus 30 to 150 F
Setpoint range Heating 40 to 90 F (4 to 32 C); cooling 45 to 99 F (7 to 37 C); deadband 2 F (1 C)
Display accuracy / clock accuracy Plus or minus 1 F (1 C) / plus or minus 1 minute per month at 77 F
Humidity rating 5 to 90 percent RH, non-condensing
Finish / batteries Trident White / none required
Power-loss memory Programmed times and temperatures retained; clock and day kept at least 48 hours after 5 minutes of powered operation

How T7350H1017 differs from other T7350 models

Compared with T7350H1009 the T7350H1017 swaps the relay-only stage structure for modulating outputs. Compared with T7350M, the non-networked modulating unit, T7350H1017 adds the LONWORKS capability. Compared with T7350D, it adds both network access and modulating drives. Choose it when one device must modulate a valve and also report values to a building supervisor.

Typical uses

Hot-water or chilled-water fan coils with a modulating valve, rooftop units with a modulating economizer, and VAV-free single zone air handlers in hotels, schools and government buildings. In Gulf projects, a T7350H1017 can replace an older analog thermostat and add scheduling plus remote override without a separate controller. The same thermostat can read a 0 to 10 Vdc humidity sensor and a dry-contact motion sensor, so a single T7350H1017 can restrict modulation on a humid day or fall back to a standby setpoint when the room is empty, which saves cooling energy in meeting rooms and prayer halls that are used only part of the day.

Programming and set-up

The datasheet devotes an Installer Setup section and a Programming section to configuring the unit, and advanced items are reached through TStatSpec on Windows XP or Windows 7, or via a Palm OS PDA with RS-232 serial link. Network tools such as LonSpec and CARE can configure every PDA-available feature on the networked models.

Wiring notes

The modulating networked subbase (Table 7 of the datasheet) is conventional-only; heat pump columns are blank. Its terminals are RC and RH for the transformers (factory jumper for one transformer), X common, W1 as the stage 1 heating relay, Y1 as the stage 1 cooling relay, G for the fan, MX as modulating common, MH as the 4 to 20 mA heating signal and MC as the 4 to 20 mA cooling signal. AS carries the discharge-air sensor, OS the outdoor sensor, HS, HC and HP the 0 to 10 Vdc humidity sensor, M the motion sensor, T3 to T7 a TR20 series remote sensor and ebus the LonWorks bus. The auxiliary relay is a floating contact, normally open and common, not tied to transformer hot or common. Wire size is 18 gauge at most and no smaller than 22 gauge; shielded cable such as Belden type 8762 is advised for sensor runs with the shield grounded only at the equipment case. Outdoor sensor wiring requires 18 gauge wire, the supply must stay within 20 to 30 Vac, and every relay output is rated 1.5 A running and 7.5 A inrush at 30 Vac. Keep wiring runs short and away from line voltage distribution to avoid erratic operation. When used with TR23 wall modules, use the relative plus or minus offset knob only, since Celsius and Fahrenheit knobs do not work properly with the T7350.

Service

A four or nine sensor averaging network of TR21 sensors may be connected when one sensor is not representative of the space; Honeywell shows two TR21-A 10K ohm sensors as a smaller alternative. Mount sensors about 5 ft (1.5 m) above the floor and avoid drafts, duct air, direct sun, concealed pipes and outside walls. Because the unit retains programmed times for the life of the product and no battery is used, field service is limited to wiring checks, sensor verification and re-download of the schedule. For T7350H1017, make a note of the throttling range and output scaling after commissioning, and store a copy of the application database, because the datasheet notes that configuration can be downloaded and stored. Replacement then becomes a matter of fitting the new subbase wiring, plugging in the thermostat and loading the saved file.

Documents and quotation

Use the Honeywell T7350 product data (form 63-2605) as the datasheet for T7350H1017. For an RFQ, send the part number T7350H1017, quantity and delivery location in Oman or the GCC.

Other Models in the T7350 Range

Seven Star LLC supplies models from the T7350 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Honeywell T7350H1009 Commercial Programmable Thermostat LONWORKSControllers & Data AcquisitionView details
Honeywell T7350H1017 Modulating Programmable ThermostatControllers & Data AcquisitionYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Honeywell T7350H1017 Modulating Programmable Thermostat Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).

Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.

Honeywell company profile

Origins 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927
Brands in our range Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance
Gent Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005
Elster Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015

Milestones

  • 1885: The Butz thermostat business starts in Minneapolis.
  • 1927: It merges with Mark Honeywell's company.
  • 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
  • 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.

Honeywell products we list

Family Models Typical use
Fixed gas detectors Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID Flammable, toxic and VOC gas detection in process areas
Sensors, flame detection and control SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel Replacement sensors, fire detection and gas detection control panels
Transmitters and flow SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis Process pressure and mass flow measurement
Elster gas metering Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display Gas meters, volume correction and fiscal flow computing
Gent fire alarm systems Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell Addressable and conventional fire alarm systems in buildings and plants
Chadwick-Helmuth rotor track and balance 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor Helicopter rotor track and balance and propeller balancing

Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.

Where Honeywell products are used

In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.

Ordering Honeywell products: what we need

Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.

Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.

FAQ

Questions about the Honeywell T7350H1017 Modulating Programmable

Answers from our engineering team on installation, compatibility and integration.

01What does the Honeywell T7350H1017 output?
It provides two modulating stages (4 to 20 mA) and two relay stages.
02Can T7350H1017 give a 2 to 10 Vdc output?
The datasheet states that 2 to 10 Vdc can be obtained by using a 500 ohm resistor on the 4 to 20 mA output.
03Is T7350H1017 networked?
Yes, it is an H model with a LONWORKS connection and LonMark Space Comfort Controller rooftop profile.
04What auxiliary relay type does T7350H1017 have?
The datasheet table shows a Normally Open auxiliary relay.
05What is the maximum terminating resistance for the T7350H1017 output?
The 4 to 20 mA modulating output allows up to 510 ohm of terminating resistance.