What the Honeywell PVL4022AS is built for

Honeywell PVL4022AS is a Spyder Lon VAV controller with a velocity pressure sensor and a direct-coupled Series 60 floating damper actuator already wired to it. It is aimed at single-duct terminal boxes: it reads box airflow through the pickup, positions the damper and, with its two Triac outputs, can bring on reheat stages or a baseboard valve.

Details below come from the Honeywell Spyder Lon product data (form 63-2685) and the matching installation guide. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

PVL4022AS specification table

Parameter Value
Model PVL4022AS, VAV, Spyder Lon
Points 4 UI, 0 DI, 2 AO, 2 DO
Supply 20 to 30 Vac, 50/60 Hz
Controller plus actuator load 9 VA maximum
Ambient (VAV rating) 32 to 122 F (0 to 50 C), 5 to 95 percent RH non-condensing
Network LONWORKS FTT-10A, 78 kbps, LONMARK compliant
Actuator torque 44 lb-in (5 Nm), Series 60 floating
Actuator stroke 95 degrees plus or minus 3, CW or CCW opening dampers
Run time 90 seconds for 90 degrees at 60 Hz
Damper shaft 3/8 to 1/2 in (10 to 13 mm) square or round, minimum length 1-9/16 in (40 mm)
Actuator ambient minus 4 to 140 F (minus 20 to 60 C)
Velocity pressure sensor 0 to 1.5 in. H2O (0 to 374 Pa), microbridge
Mounting Direct on damper shaft; controller panel mounted per Fig. 4 (not DIN rail)

Power, wiring and network rules that affect this model

PVL4022AS must be fed from an energy-limited Class II 24 Vac source. The datasheet states that to conform to Class II restrictions in the United States the transformer should not exceed 100 VA, and that one transformer can power several controllers provided the same side of the secondary goes to the same power terminal on each one and the earth ground terminal is bonded on every unit. Terminals 1 and 2 take power, terminal 3 is earth, and the bus goes to terminals 7 and 8. Do not tie the universal input, analog output or digital common terminals to earth.

For the LONWORKS segment, Honeywell names Level IV 22 AWG (0.34 sq mm) unshielded twisted pair, with U.S. parts AK3798 for non-plenum and AK3797 or AK3799 for plenum spaces. The theoretical limit is 60 controllers per segment and 120 with a repeater, and a singly terminated bus needs one 209541B termination module while a doubly terminated bus needs two. Keep at least 3 in (76 mm) between Triac wiring and the bus cable.

How PVL4022AS differs from other Spyder Lon variants

Against PVL0000AS, which has the same actuator and flow sensor but no I/O at all, PVL4022AS adds four universal inputs and two analog and two Triac outputs. Against PVL4024NS the inputs and analog outputs match, but the NS has four Triacs and no actuator, and it can mount on DIN rail. Against PVL6436AS the PVL4022AS gives up two UI, four DI, one AO and four DO. Unlike PUL unitary models, the VAV family operates in 32 to 122 F rather than minus 40 to 150 F.

Installing on a VAV box damper

Mount the actuator first. Fit it flush to the box or use a spacer, set the mechanical end-limit screws (they ship at 95 degrees; each hash mark on the bracket is about 6.5 degrees per side), and press the Declutch button to turn the shaft adapter to the open position before tightening the two centering clamp bolts to 8 to 10 Nm (70.8 to 88.5 lb-in). It ships set to open clockwise; for counter-clockwise dampers set Reverse to Open in the program. For PVL4022AS, leave the damper open during power-down to avoid over-pressurizing duct on fan start.

Piping the air flow pickup

Use 1/4 in outside diameter, 0.040 in wall plenum-rated 1219 FR (94V-2) tubing with a fresh cut at each end. High (upstream) pressure goes to the port marked plus, low pressure to minus. Keep tube length under three feet (0.914 m); longer runs degrade the reading. In dusty places add an in-line 5 micron disposable filter on the plus line.

Applications

Because the box already carries a damper actuator and a flow pickup, this is a single-part replacement for a failed VAV controller: the old controller and actuator are unbolted together and the new assembly goes onto the same shaft. The four universal inputs normally take a zone sensor or TR23 wall module, a discharge-air temperature and an optional CO2 or occupancy signal. Variable-volume terminals in hotels, hospitals, airport terminals and offices across Oman and the GCC; replacement of failed boxes in existing LONWORKS buildings; retrofit where the original controller is obsolete and a programmable model is wanted. Pair with the TR23 wall module for zone setpoint. When ordering a spare PVL4022AS, confirm the box shaft diameter first, because the actuator cannot be used on shafts shorter than 40 mm.

Maintenance

The Honeywell guidance for PVL4022AS also says that pull straight away from a tube connector when removing tubing, or cut the edge of the tube, because pulling at an angle damages the restrictor port. Check actuator travel and clamp torque once a year, and confirm that the pickup tubes are unkinked, cut cleanly at the ends and not longer than three feet. Use the declutch button to open the damper by hand on a controller that is powered down. All terminal blocks lift off with wiring intact, so a failed assembly is swapped by loosening the actuator clamp, removing the two pickup tubes and sliding the unit off the shaft.

Documents and quotation

The Spyder Lon product data serves as the datasheet for PVL4022AS. Send us the part number PVL4022AS, quantity, destination and whether an -ILC licensed version is needed so we can answer your RFQ.

Other Models in the Spyder Lon VAV Range

Seven Star LLC supplies models from the Spyder Lon VAV range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Honeywell PVL4022AS Spyder Lon VAV Controller with ActuatorControllers & Data AcquisitionYou are viewing this model
Honeywell PVL6436AS Spyder Lon VAV Controller 6 UI 4 DI 6 DOControllers & Data AcquisitionView details
Datasheets & Documents
  • PDF Datasheet Honeywell PVL4022AS Spyder Lon VAV Controller with Actuator Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).

Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.

Honeywell company profile

Origins 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927
Brands in our range Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance
Gent Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005
Elster Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015

Milestones

  • 1885: The Butz thermostat business starts in Minneapolis.
  • 1927: It merges with Mark Honeywell's company.
  • 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
  • 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.

Honeywell products we list

Family Models Typical use
Fixed gas detectors Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID Flammable, toxic and VOC gas detection in process areas
Sensors, flame detection and control SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel Replacement sensors, fire detection and gas detection control panels
Transmitters and flow SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis Process pressure and mass flow measurement
Elster gas metering Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display Gas meters, volume correction and fiscal flow computing
Gent fire alarm systems Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell Addressable and conventional fire alarm systems in buildings and plants
Chadwick-Helmuth rotor track and balance 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor Helicopter rotor track and balance and propeller balancing

Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.

Where Honeywell products are used

In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.

Ordering Honeywell products: what we need

Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.

Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.

FAQ

Questions about the Honeywell PVL4022AS Spyder Lon VAV Controller with

Answers from our engineering team on installation, compatibility and integration.

01Does the Honeywell PVL4022AS include an actuator?
Yes. The A suffix models include a Series 60 floating actuator, 44 lb-in (5 Nm), hard-wired to the controller.
02What damper shaft sizes fit the PVL4022AS actuator?
Shafts from 3/8 to 1/2 in (10 to 13 mm), square or round, with at least 1-9/16 in (40 mm) of length.
03How many I/O points does PVL4022AS have?
Four universal inputs, two analog outputs and two Triac digital outputs; it has no digital inputs.
04What is the flow sensor range of PVL4022AS?
The onboard microbridge velocity pressure sensor covers 0 to 1.5 in. H2O (0 to 374 Pa).
05Can PVL4022AS be mounted on a DIN rail?
No. The datasheet lists DIN rail mounting only for PUL and PVL N-suffix models, so the actuator model is panel mounted with the controller.