- Automation & ControlView all 2,965 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Isolator & Barrier
- Controllers & Data Acquisition
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Honeywell
Honeywell PUL1012S Spyder Lon Unitary Programmable Controller
Description
Honeywell PUL1012S Spyder Lon unitary controller: what it is
Honeywell PUL1012S is the smallest member of the Spyder Lon unitary line: a programmable, LONMARK-compliant HVAC controller with one universal input, no digital inputs, one analog output and two Triac digital outputs. It is the board you pick when a packaged unit, a single fan coil or a small exhaust fan only needs a handful of points, and when the rest of the building already talks over a 78 kbps FTT-10A LONWORKS bus.
The unit is listed in the Honeywell Spyder Lon product data (form 63-2685) together with seven siblings. Inside the plastic base plate and snap-on cover sit two microcontrollers: a host controller that runs the downloaded HVAC application and a second one that handles LONWORKS communications. Because the two jobs are separated, a network fault does not stop the control loop, and a control download does not disturb the Neuron communication image.
Seven Star LLC supplies PUL1012S for replacement and retrofit work. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. The notes below are built only from the manufacturer literature for PUL1012S and are meant to help a controls engineer or buyer check fit before sending an RFQ.
Input and output budget, point by point
The control point count is the most important thing to verify, so it is listed first. Table 1 of the datasheet gives the following allocation for this model.
- Universal input (UI): 1, and that single input is user selectable as a fast digital pulse meter (counter or meter, 15 Hz maximum, 20 ms minimum pulse width, 5 ms maximum chatter).
- Digital inputs (DI): 0.
- Analog outputs (AO): 1, individually configurable as 4 to 20 mA current or 0 to 10 Vdc voltage.
- Digital Triac outputs (DO): 2.
- Velocity pressure sensor: not fitted. Series 60 floating actuator: not fitted.
With one UI, the typical use is a single room, discharge-air or return-air temperature (20K ohm NTC, range minus 40 to 199 F, or minus 40 to 93 C) while the Triac pair switches a fan contactor and a stage, and the analog output drives a modulating valve or a variable-speed device. If you need two or more sensors, or a dry-contact status input such as a filter switch, step up to a larger Spyder unitary board.
PUL1012S technical specification table
| Parameter | Value |
|---|---|
| Model | PUL1012S, Spyder Lon unitary |
| Universal inputs / digital inputs | 1 / 0 |
| Analog outputs / Triac digital outputs | 1 / 2 |
| Controller-only load | 5 VA maximum |
| Rated supply | 20 to 30 Vac, 50/60 Hz, Class 2 energy-limited source |
| Maximum power draw incl. loads | 100 VA |
| Network | LONWORKS FTT-10A, 78 kbps, LONMARK compliant, communication terminals 7 and 8 |
| Sensor power output | 20 Vdc plus or minus 10 percent at 75 mA maximum |
| Triac digital output rating | 20 to 30 Vac, 25 mA to 500 mA continuous, 800 mA for 60 ms |
| Analog output | Configurable 4 to 20 mA (550 ohm maximum load) or 0 to 10 Vdc (10 mA maximum) |
| Operating and storage temperature | minus 40 to 150 F (minus 40 to 65.5 C) |
| Humidity | 5 to 95 percent, non-condensing |
| Real time clock backup | 24 hours at 32 to 100 F, 22 hours at 100 to 122 F; accuracy plus or minus 1 minute per month at 77 F |
| Mounting | Panel (four 3/16 in / 4.5 mm holes) or DIN rail, any orientation |
| Enclosure depth | 2-1/4 in (57 mm) |
Two ratings deserve attention. First, the unitary Spyder Lon family is rated for minus 40 to 150 F, a wider band than the VAV family at 32 to 122 F, so PUL1012S is acceptable for unconditioned plant rooms and rooftop cabinets. Second, the controller-only load is just 5 VA; the 100 VA figure is the cap for the controller plus everything it powers from the same transformer.
How PUL1012S differs from other Spyder Lon variants
Within the Lon unitary group, PUL1012S sits at the bottom. Compared with PUL4024S the input count falls from 4 UI to 1, and the analog outputs from 2 to 1 while Triacs drop from 4 to 2. Compared with PUL6438S it also loses the four digital inputs, three analog outputs and the other six Triacs. Against the VAV models (PVL series) it has no air-flow pickup ports and no onboard damper actuator, so it never needs tubing to a flow pickup.
Mounting also differs. Unitary models, including this one, can be fixed on a DIN rail to standard EN50022 (35 mm by 7.5 mm) by hooking the top tabs and pressing the two bottom flex connectors in, whereas the actuator-equipped VAV models are panel mounted only.
Typical applications in Oman and the GCC
In Gulf climates the load is dominated by cooling, so a small-point controller usually ends up on a split unit, a packaged rooftop unit or a make-up air handler. Typical uses for this board include a plant-room extract fan that must start on a high-temperature signal, a small chilled-water fan coil with a floating or 0 to 10 Vdc valve, or a pump skid where a single process temperature input is enough. In oil and gas camps, utility buildings and water treatment plants the same logic is applied to control rooms and MCC rooms.
Installation and commissioning notes
Terminal 3 is the earth ground; power goes to terminals 1 and 2 from a Class 2 transformer. Honeywell recommends 14 AWG for power and earth runs and no less than 18 AWG, and it limits line loss to two volts so the unit still sees at least 20 Vac when mains falls 15 percent. Keep Triac wiring at least 3 in (76 mm) from LONWORKS cable, use Level IV 22 AWG twisted pair on the bus, and terminate according to the singly or doubly terminated topology in the manual. A segment is theoretically limited to 60 devices, or 120 with a repeater.
Programming needs the Spyder programmable feature licensed in WEBpro workbench on a WEBS AX JACE. The datasheet also notes that eight Spyder Lon models exist as individually licensed controllers with an -ILC suffix, such as PUL6438S-ILC; check which licence you hold before ordering.
Service and maintenance
There are no serviceable parts. Maintenance is limited to checking terminal tightness, confirming the status LED (normal operation, download, alarm, manual mode, error), and verifying the supply voltage under load. The real time clock keeps time for 24 hours at 32 to 100 F after power loss. When replacing a failed unit, the manual lets you pull the terminal blocks off with the wiring still attached and seat them on the new controller, then run the Checkout procedure.
Related items and ordering notes
Sensors the datasheet recommends with Spyder inputs are the C7031G outdoor sensor and C7041F duct sensor, which give better resolution than PT1000, and the TR23 wall module for setpoint. When sending an RFQ for PUL1012S, state whether you need the -ILC version, the quantity, and whether a transformer or wall module should be quoted with it.
Frequently asked questions in brief
Buyers most often ask whether PUL1012S can read a dry contact (only through the single UI), whether it carries an actuator (no), what the supply is (20 to 30 Vac), and how it talks to the building (LONWORKS FTT-10A). The five questions below answer these directly.
Documents and quotation
The Honeywell product data for the Spyder Lon family, form 63-2685, is available as the datasheet for PUL1012S. For a quotation, send us the part number PUL1012S, the quantity, the destination in Oman or the GCC and any programming-licence requirement, and we will reply to your RFQ.
Datasheets & Documents
- Datasheet Honeywell PUL1012S Spyder Lon Unitary Programmable Controller Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).
Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.
Honeywell company profile
| Origins | 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927 |
|---|---|
| Brands in our range | Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance |
| Gent | Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005 |
| Elster | Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015 |
Milestones
- 1885: The Butz thermostat business starts in Minneapolis.
- 1927: It merges with Mark Honeywell's company.
- 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
- 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.
Honeywell products we list
| Family | Models | Typical use |
|---|---|---|
| Fixed gas detectors | Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID | Flammable, toxic and VOC gas detection in process areas |
| Sensors, flame detection and control | SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel | Replacement sensors, fire detection and gas detection control panels |
| Transmitters and flow | SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis | Process pressure and mass flow measurement |
| Elster gas metering | Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display | Gas meters, volume correction and fiscal flow computing |
| Gent fire alarm systems | Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell | Addressable and conventional fire alarm systems in buildings and plants |
| Chadwick-Helmuth rotor track and balance | 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor | Helicopter rotor track and balance and propeller balancing |
Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.
Where Honeywell products are used
In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.
Ordering Honeywell products: what we need
Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.
Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.
Browse Honeywell products by category: Fire & Gas Detector, Vibration, Flowmeters, Pressure Instrumentation, Temperature Instrumentation.
FAQ
Questions about the Honeywell PUL1012S Spyder Lon Unitary Programmable
Answers from our engineering team on installation, compatibility and integration.
01How many inputs and outputs does the Honeywell PUL1012S have?
It has 1 universal input, no digital inputs, 1 analog output and 2 Triac digital outputs, according to Table 1 of the Spyder Lon product data.
02Can the single input of PUL1012S count pulses?
Yes. The one universal input is user selectable as a fast digital pulse meter with a 15 Hz maximum frequency and 20 ms minimum pulse width.
03What temperature range does PUL1012S tolerate?
Unitary Spyder Lon controllers are rated for minus 40 to 150 F (minus 40 to 65.5 C) operating and storage, with 5 to 95 percent non-condensing humidity.
04Does PUL1012S need a Honeywell workbench licence?
The Spyder programmable feature must be licensed in WEBpro workbench on a WEBS AX JACE, unless you buy the individually licensed -ILC version of the model.
05Is PUL1012S suited to VAV boxes?
No. VAV boxes use the PVL series, which has a velocity pressure sensor and often an actuator; this unitary model has neither.


















Reviews
There are no reviews yet.