The Honeywell OmniPoint is a gas transmitter designed to operate in hazardous locations and to support multiple sensors for the detection of toxic, oxygen and flammable gas hazards. Instead of installing a separate transmitter for every gas, one OmniPoint unit can serve up to three sensors simultaneously, each with its own fully configurable 4-20 mA channel. Honeywell combines this with HART 7 communication, optional Modbus RTU and Bluetooth 5.0 modules, a 3 inch full-colour TFT display and a wide operating temperature range of –55 to 75 °C, making it a modern platform for process plants and oil and gas facilities.

Seven Star LLC supplies the Honeywell OmniPoint to oil and gas operators, refineries, petrochemical plants and EPC contractors in the Sultanate of Oman and the GCC. Multi-gas points are common in Oman: H2S plus LEL around sour gas wells and gathering stations, oxygen plus toxic gas in analyser houses, and ammonia or chlorine in utilities. With engineering support in Muscat, our team helps choose the sensor cartridges, enclosure material and communication modules for each detection point and checks the current certification status for the project.

Measurement Principle

The Honeywell OmniPoint works with two families of sensor modules. XPIS sensor modules use electrochemical cells for ammonia, carbon monoxide, chlorine, hydrogen sulphide, oxygen and sulphur dioxide; in general terms these cells generate a current proportional to the concentration of the target gas. XP sensor modules use catalytic bead sensors for flammable gases or infrared sensors for methane and propane, measuring in %LEL. Both XPIS and XP sensor modules can be wired up to 300 m from the transmitter with two-wire cable, and the transmitter can also accept an Optima point infrared detector.

For each sensor the Honeywell OmniPoint applies configurable alarm levels and drives its outputs. The default current output scheme uses 1.0 mA for fault, 2.0 mA for warm-up and inhibit, 3.0 mA for warning, 4.0 to 20.0 mA for normal measurement and 21.0 mA for maximum over range, with ±1% full-scale signal accuracy. The transmitter automatically detects whether it should operate in current sink or current source mode, and an isolated mode is also supported. This allows the same unit to connect to many types of safety PLC or fire and gas panel.

Engineering Design of the Honeywell OmniPoint

The Honeywell OmniPoint enclosure is five-coat marine-finish painted aluminium alloy or 316 stainless steel. With the display module the transmitter weighs about 2.78 kg in aluminium or 5.70 kg in stainless steel; an XPIS sensor module with cartridge adds 0.80 kg and an XP module 0.69 kg. Four conduit or cable entries (M25 or 3/4 inch NPT) are provided for wiring and sensors, plus one M22 top entry for the optional Bluetooth antenna. The unit can be mounted on flat walls or, with the optional kit, on pipes from 2 to 6 inches in diameter. Ingress protection is IP66/IP67 to IEC/EN 60529 and NEMA 4X.

The user interface of the Honeywell OmniPoint is a 3 inch circular high-resolution colour display with four capacitive touch keys and an LED ring: green for normal operation, red for alarm, yellow for fault or warning and blue for wireless communication. The display shows five-digit readings with units and an alarm snapshot with gas trend. Three fully configurable alarm relays and one normally energised fault relay are rated up to 240 V AC, 5 A. Input voltage is 12 to 32 V DC for catalytic, IR and XPIS sensors and 18 to 32 V DC with Optima, with transmitter consumption of 4.5 W normal and 8.5 W maximum.

Key Features

Key features of the Honeywell OmniPoint from the Honeywell technical specifications are summarised below.

  • One transmitter supports up to three sensors at the same time for toxic, oxygen and flammable gases.
  • Three fully configurable 4-20 mA channels operate in sink, source or isolated modes.
  • HART 7 communication on the first channel supports point-to-point or multi-drop operation with up to 8 devices.
  • An optional isolated Modbus RTU module connects the unit to RS-485 networks with addresses 1 to 247.
  • An optional Bluetooth 5.0 module enables remote zero and span calibration and configuration from a smartphone.
  • The 3 inch full-colour display and LED status ring make detector status visible at a glance.
  • Operating temperature extends from –55 to 75 °C, with IP66/IP67 and NEMA 4X protection.
  • Honeywell lists a 5-year warranty for the transmitter unit and up to 3 years for many sensor cartridges.

Industrial Applications

The Honeywell OmniPoint suits applications where several gas hazards exist at the same location: wellpads and gathering stations with H2S and methane, gas compression and processing plants, refinery process units, tank farms and loading facilities, chemical plants that handle ammonia or chlorine, and water treatment works. Using one transmitter for multiple sensors reduces the number of field devices, cable runs and panel inputs, which helps on brownfield upgrades in Oman where cable trays and junction boxes are already crowded.

Seven Star LLC supplies the Honeywell OmniPoint with other Honeywell detection products such as the Honeywell XNX Excel gas detector, the Honeywell Searchline Excel Plus open path detector and the Honeywell Sensepoint XRL fixed gas detector. Our engineering team in Muscat supports projects across Oman and the GCC with detector selection and replacement planning.

Technical Specifications

The table lists Honeywell OmniPoint data from the Honeywell technical specifications sheet (US-EN 0125). The sheet shows ATEX, IECEx and performance approvals as pending at that date, so please confirm current certification before ordering for a classified area.

Parameter Specification
Model Honeywell OmniPoint gas transmitter
Sensors supported Up to 3 simultaneously: XPIS (electrochemical), XP (catalytic or IR), Optima
XPIS gases NH3, CO, Cl2, H2S, O2, SO2
XP gases Flammables (catalytic), methane and propane (IR), 0 to 100% LEL
Sensor wiring distance Two-wire, up to 300 m (984 ft)
Input voltage 12 to 32 V DC (catalytic, IR, XPIS); 18 to 32 V DC (Optima); 24 V DC nominal
Power consumption Transmitter 4.5 W normal, 8.5 W max; maximum 17 W with Optima plus 2 XP sensors
Current outputs 3 x 4-20 mA, sink/source/isolated, ±1% full scale
Communication HART 7 (channel 1); optional Modbus RTU (RS-485); optional Bluetooth 5.0 (up to 20 m)
Relays 3 x SPDT alarm, 1 x SPDT fault; max 240 V AC, 5 A
Display 3 in full-colour TFT, four capacitive touch keys, LED status ring
Enclosure Marine-painted aluminium alloy or 316 stainless steel; IP66/IP67, NEMA 4X
Cable entries 4 x M25 or 3/4 in NPT; 1 x M22 for Bluetooth antenna
Operating temperature / humidity –55 to 75 °C; 0 to 99% RH non-condensing
Hazardous area approvals UL/cUL Class I Div. 1 Groups A-D, Class II Div. 1 Groups F and G; ATEX and IECEx listed as pending on the sheet

How to Order

To order the Honeywell OmniPoint, send Seven Star LLC the gases and ranges for each detection point, enclosure material, cable entry type and the communication options you need. Our team in Muscat will confirm the configuration and current approvals, share the technical datasheet for download and prepare a formal quotation. Seven Star LLC supplies Honeywell gas detection equipment across Oman and the GCC with engineering support.

Datasheets & Documents
  • PDF Datasheet Honeywell OmniPoint Technical Specifications Sheet (US-EN 0125) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).

Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.

Honeywell company profile

Origins 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927
Brands in our range Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance
Gent Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005
Elster Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015

Milestones

  • 1885: The Butz thermostat business starts in Minneapolis.
  • 1927: It merges with Mark Honeywell's company.
  • 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
  • 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.

Honeywell products we list

Family Models Typical use
Fixed gas detectors Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID Flammable, toxic and VOC gas detection in process areas
Sensors, flame detection and control SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel Replacement sensors, fire detection and gas detection control panels
Transmitters and flow SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis Process pressure and mass flow measurement
Elster gas metering Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display Gas meters, volume correction and fiscal flow computing
Gent fire alarm systems Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell Addressable and conventional fire alarm systems in buildings and plants
Chadwick-Helmuth rotor track and balance 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor Helicopter rotor track and balance and propeller balancing

Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.

Where Honeywell products are used

In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.

Ordering Honeywell products: what we need

Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.

Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.

FAQ

Questions about the Honeywell OmniPoint Multi-Sensor Fixed Gas Detector

Answers from our engineering team on installation, compatibility and integration.

01How many sensors can one Honeywell OmniPoint transmitter handle?
The Honeywell technical specifications state that OmniPoint supports up to three sensors simultaneously, each with its own configurable 4-20 mA output channel, covering toxic, oxygen and flammable gases.
02Which communication options are available?
HART 7 is provided on the first 4-20 mA channel, with point-to-point or multi-drop modes. Optional modules add isolated Modbus RTU over RS-485 and Bluetooth 5.0 for smartphone configuration and remote zero and span calibration.
03Is OmniPoint suitable for hot climates like Oman?
The specified operating temperature range is minus 55 to plus 75 degC with IP66/IP67 and NEMA 4X protection. Individual sensor cartridges have their own temperature limits, which should be checked for each gas.
04What hazardous area approvals does it have?
The 2025 specification sheet lists UL/cUL Class I Division 1 and Class II Division 1 approvals, with ATEX and IECEx shown as pending at that date. Please ask us to confirm the current certificates before ordering for an ATEX or IECEx zone.
05Does Seven Star LLC supply Honeywell fixed gas detectors in Oman?