- Automation & ControlView all 2,607 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- HMI Displays
- Pneumatic Cylinders
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Endress+Hauser (E & H)
Endress+Hauser CM44P Liquiline Multichannel Transmitter
Description
Endress+Hauser CM44P Liquiline photometer and Memosens transmitter
The Endress+Hauser CM44P is a Liquiline four-wire multichannel transmitter that connects up to two process photometers together with up to four Memosens digital sensors. The combination lets a skid builder or process engineer assemble a complete measuring point for chromatography, fermentation, phase separation and filtration, where UV absorbance and a handful of standard parameters such as pH, conductivity and dissolved oxygen are measured side by side. The CM44P belongs to the Liquiline platform, so operation, system integration and spare parts are shared with the CM442, CM444 and CM448 devices. Seven Star LLC supplies the CM44P in Oman and the GCC as an independent supplier in Muscat.
CM44P technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Endress+Hauser / Liquiline CM44P |
| Inputs | 1 or 2 process photometers; 0 to 4 Memosens digital inputs |
| Photometer ranges | 0 to 2.5 AU (max. 50 OD); 0 to 3 AU; 0 to 4 AU; 0 to 200 FTU depending on sensor |
| Current outputs | 2 to 8 x 0/4 to 20 mA |
| Relays | Alarm relay 0.5 A; up to 4 relays 2.0 A |
| Fieldbus | HART, PROFIBUS, Modbus, EtherNet/IP, PROFINET; web server |
| Supply | 100 to 230 V AC or 24 V DC |
| Ingress protection | IP20 cabinet; IP66 external display; IP66/67 field device |
| Housing material | PC-FR; EPDM seals |
| Memory | SD card for update and setup copy |
What the CM44P can connect
Photometer inputs accept the manufacturer’s OUSAF11, OUSAF12, OUSAF21, OUSAF22, OUSAF44 and OUSAF46 sensors, as well as the OUSTF10 and OUSBT66. Typical ranges are 0 to 2.5 AU (up to 50 OD depending on path length) for most OUSAF types, 0 to 3 AU for OUSAF11, 0 to 200 FTU for OUSTF10 and 0 to 4 AU for OUSBT66. Memosens inputs, up to four, accept pH, ORP, conductivity (conductive and inductive), dissolved oxygen, turbidity and other digital sensors in any combination, together with the Flowfit and OUA260 flow assemblies shown in the document.
CM44P hardware, outputs and communication
The device offers two to eight 0/4 to 20 mA current outputs, an alarm relay and up to four additional relays (alarm relay 0.5 A, other relays 2.0 A), digital inputs and outputs, and an SD card for software updates and for copy-and-paste of the setup. Fieldbuses include HART, PROFIBUS, Modbus, EtherNet/IP and PROFINET, and an integrated web server allows browser operation. Data can be transferred through Ethernet, a CDI interface or an SD card and stored in a tamper-proof database. Supply is 100 to 230 V AC (50/60 Hz) or 24 V DC depending on version. Ingress protection is IP20 for the cabinet device, IP66 for an external display and IP66/67 for the field device. Housing and DIN rail parts use PC-FR with EPDM seals.
Heartbeat Technology and the Liquiline platform
Heartbeat Technology in the transmitter helps balance availability against inspection effort by verifying the measuring chain and logging diagnostics. The platform has a modular concept: slots and ports are assigned in order, so channel 1 is slot 1 port 1, and extension modules can add inputs, outputs, controllers and math functions later without replacing the base unit.
Selecting the CM44P
List the sensors and the photometer model first, then the fieldbus and outputs, then the housing: cabinet device, DIN rail or field device with display. Decide the supply voltage and whether relays are needed for cleaning or limit values. Order the sensors and flow assemblies from the same measuring-point list so that cables and assemblies match.
Installing and commissioning the CM44P
Mount the transmitter in the cabinet or on the wall, keep sensor and photometer cables apart from power wiring, and connect the Memosens cables to the numbered ports. At first start the device guides through language, date and the sensor assignment, and the photometer is configured with its path length and calibration. Back up the setup to the SD card and record the module and port assignment for service.
CM44P uses in Oman and the GCC
The CM44P is a specialist device: the main users are pharmaceutical, biotech and food plants and research or pilot facilities using chromatography and filtration, plus packaged skids built for export to the region. In general oil, gas and water plants, the CM442 or CM444 family covers the common pH and conductivity tasks without a photometer.
CM44P within the Liquiline family
| Model | Role |
|---|---|
| CM44P | Photometers plus Memosens sensors |
| CM442 / CM442R | 2-channel Memosens |
| CM444R / CM448R | DIN rail 4 or 8 channel |
Information to send with a CM44P RFQ
- Photometer type and path length
- Memosens sensors and parameters
- Fieldbus and outputs
- Supply voltage and housing
- Cleaning or control functions needed
- Quantity and delivery location
Spares and handling notes for the CM44P
Keep spare Memosens cables and a spare photometer sensor cable at the plant, because chromatography and filtration skids often cannot stop for long. Document the photometer path length, calibration values and the module and port assignment in the commissioning file. Clean photometer windows only with the agent and method approved for the assembly, and protect the optical connectors from dust and liquid.
Site conditions in Oman for the CM44P
Field instruments in Oman are exposed to strong sun, high ambient temperature, wind-blown dust and, on coastal plants, salt in the air. When you specify the CM44P, check the ambient and process temperature limits, the enclosure rating and the wetted and housing materials against the actual installation point, and consider sunshades for transmitters mounted in direct sunlight. Cable entries should be sealed with suitable glands so that dust and moisture cannot enter the housing.
Calibration and verification planning matters as much as selection. Record the range, configuration and tag data of each CM44P at commissioning, define a check interval that suits the criticality of the loop, and keep the certificates with the plant documentation so that audits and shutdown work can proceed without delay.
Documents and quotation
A copy of the manufacturer technical information for the CM44P is attached on this page so you can check ranges, connections and ordering codes against your specification.
Send the full order code or the process data (fluid, temperature, pressure, line size or tank data, output and approvals) and Seven Star LLC will prepare a quotation and confirm lead time. We are an independent supplier in Muscat and do not represent the manufacturer.
Other Models in the Eh Liquiline Range
Seven Star LLC supplies models from the Eh Liquiline range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Endress+Hauser CM44P Liquiline Multichannel Transmitter | Liquid Analytical Systems | You are viewing this model |
| Endress+Hauser CM444R Liquiline DIN-Rail Transmitter | Liquid Analytical Systems | View details |
Datasheets & Documents
- Datasheet Endress+Hauser CM44P Technical Information Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Endress+Hauser makes process measurement instruments for flow, level, pressure, temperature and liquid analysis. Georg H. Endress and Ludwig Hauser started the business in Lörrach, Germany, on 1 February 1953, first selling level meters, and the Endress+Hauser name has been used since 1957. The group is headquartered in Reinach, Switzerland, and has been wholly owned by the Endress family since 1975.
Seven Star LLC is an independent supplier listing Endress+Hauser flowmeters, level and pressure transmitters, temperature assemblies and liquid analysis products for buyers in Oman and the GCC. Instruments are matched from the full order code on the nameplate.
Endress+Hauser company profile
| Origin | Founded in Lörrach, Germany, on 1 February 1953 by the Swiss engineer Georg H. Endress and Ludwig Hauser |
|---|---|
| Headquarters | Endress+Hauser AG, Reinach (Basel-Landschaft), Switzerland |
| Ownership | Family owned; the Endress family has been the sole shareholder since 1975, and a family charter commits the company to stay family owned |
| Size | About 16,500 employees and sales of about EUR 3.7 billion (2023, as reported by the company) |
| Product families | Proline flowmeters, Micropilot and Levelflex radar, Liquiphant switches, Cerabar and Deltabar pressure, iTEMP and iTHERM temperature, Liquiline and Memosens liquid analysis |
Milestones
- 1953: Georg H. Endress and Ludwig Hauser start the business in Lörrach on 1 February, first selling level meters.
- 1957: The Endress+Hauser name comes into use.
- 1975: The Endress family becomes sole shareholder.
- 2023: About 16,500 employees and sales of about EUR 3.7 billion, as reported by the company.
Endress+Hauser product lines
| Line | Measuring principle | Typical use |
|---|---|---|
| Promass F 300, Promass 80F, 83F/84F | Coriolis mass flow | Direct mass flow and density of liquids and gases, hydrocarbon transfer and chemical dosing |
| Promag P 300, P 500, H 300, W 400, W 10, 50P | Electromagnetic flow | Water, wastewater, slurries and other conductive liquids |
| Prowirl F 200, 72F | Vortex flow | Steam, gas and low-viscosity liquids |
| Prosonic Flow 92F, t-mass 65F | Ultrasonic and thermal mass flow | Water lines; compressed air and industrial gases |
| Micropilot FMR62, FMR67, FMR60, FMR10B, FMR20, FMR50, FMR52 | Free-space radar level, 80 GHz and 26 GHz | Tanks, process vessels, silos and open water channels |
| Levelflex FMP51, FMP50, FMP54, FMP55 | Guided wave radar level | Level and interface in vessels, separators and bypass chambers |
| Liquiphant FTL51, Prosonic S FMU90 | Vibronic point level; ultrasonic level | High and low level alarms, pump protection, open channel flow |
| Cerabar PMC71B, PMP51B, PMP71, Deltabar PMD78B, PMD75 | Pressure and differential pressure | Process pressure, hydrostatic level and DP flow |
| iTEMP TMT82, TMT162, iTHERM TM101, TR66, TR10 | Temperature transmitters and thermometers | RTD and thermocouple points with thermowells |
| Liquiline CM444, CM442, Memosens CPS11E, Stamolys reagents | Liquid analysis | pH, ORP, conductivity, dissolved oxygen and nutrient analysis in water treatment and process |
Where Endress+Hauser instruments are used
In Oman and the GCC, Endress+Hauser instruments are common in oil and gas production and processing, refineries and petrochemicals, desalination and water networks, wastewater treatment, power plants and food and beverage plants. Coriolis meters measure hydrocarbon and chemical flows, electromagnetic meters cover water and wastewater, radar transmitters handle tank and silo level, and Liquiline analysers monitor water quality. Proline 300 and 500 flowmeters include Heartbeat Technology for in-situ verification, which reduces the need to remove a meter for checks.
Ordering Endress+Hauser instruments: what we need
The order code on the nameplate (for example PMP71-1QA1S11RDADU) defines every option: measuring range, process connection, materials, output, approvals and display. Send it with the serial number; Endress+Hauser can retrieve the original configuration from the serial number. For a new instrument add the medium, operating and design pressure and temperature, range, line size or tank geometry, process connection, wetted materials, output or protocol (4-20 mA HART, PROFIBUS, FOUNDATION Fieldbus, Modbus) and the hazardous-area approval required. Older models such as Promass 80/83 or Micropilot M are replaced by current Proline or 80 GHz Micropilot devices.
Facts checked against Endress+Hauser company history and product information, October 2026.
Browse Endress+Hauser products by category: Flowmeters, Level Transmitter, Pressure Instrumentation, Temperature, Liquid Analysis Sensors, Liquid Analytical Systems.
FAQ
Questions about the Endress+Hauser CM44P Liquiline Multichannel
Answers from our engineering team on installation, compatibility and integration.
01What is the CM44P?
A Liquiline four-wire multichannel transmitter that connects one or two process photometers and up to four Memosens digital sensors.
02Which photometers are supported?
OUSAF11, OUSAF12, OUSAF21, OUSAF22, OUSAF44, OUSAF46, OUSTF10 and OUSBT66.
03Which fieldbuses are available?
HART, PROFIBUS, Modbus, EtherNet/IP and PROFINET, plus an integrated web server.
04What supply voltages exist?
100 to 230 V AC or 24 V DC, depending on the version.
05Can the setup be copied?
Yes. An SD card carries software updates and copies the setup to a replacement device.


















Reviews