Brand:

ABB AF09-30-01-13 3-Pole Contactor 4 kW, 100-250 V Coil

Description

ABB AF09-30-01-13 3-pole contactor with a 100 to 250 V universal coil

The ABB AF09-30-01-13 is a compact 3-pole AF contactor for 4 kW motor loads at 400 V, supplied with a built-in N.C. auxiliary contact and a coil that accepts 100 to 250 V on either 50/60 Hz AC or DC. The ABB order code is 1SBL137001R1301. It is a single-piece pack with a net weight of 0.270 kg, and it uses screw terminals on the main poles, the auxiliary contact and the coil.

Because one coil spans such a wide band, the AF09-30-01-13 is the version that fits most plants without a control transformer: a 230 V AC control circuit, a 110 V AC circuit and a 220 V DC battery-backed circuit are all inside the same coil range. That makes it a sensible stock item for maintenance teams that look after several panels with different control supplies.

Decoding the AF09-30-01-13 type designation

The AF type code is short, and each group tells you something you will need on the order.

Group Meaning in AF09-30-01-13
AF09 Contactor size: 9 A AC-3 at 400 V, 4 kW
30 3 main poles, all normally open
01 No N.O. and one N.C. auxiliary contact built in (the N.C. contact is a mirror contact to IEC 60947-4-1 annex F)
13 Coil code for 100 to 250 V 50/60 Hz and 100 to 250 V DC

The same AF09-30-01 body is sold with coil codes 11 (24 to 60 V AC, 20 to 60 V DC), 12 (48 to 130 V), 13 (100 to 250 V) and 14 (250 to 500 V). A contactor with the Z in the name, such as the AF09Z-30-01-23, is the low-consumption version of the same housing.

AF09-30-01-13 technical specifications

Parameter Specification
Manufacturer / part number ABB / AF09-30-01-13
Order code / EAN 1SBL137001R1301 / 3471523110137
Poles and built-in contacts 3 N.O. main poles; 1 N.C. built-in auxiliary contact
Coil voltage Uc 100 to 250 V 50/60 Hz and 100 to 250 V DC
Coil consumption (AF) Average pull-in 50 VA (AC) or 50 W (DC); holding 2.2 VA / 2 W (AC) or 2 W (DC)
Coil operating limits 0.85 x Uc min to 1.1 x Uc max at 60 °C; 0.85 x Uc min to Uc max at 70 °C
Drop-out voltage 60 % of Uc min or lower
Rated operational voltage Ue (IEC) 690 V max.
Rated frequency limits 25 … 400 Hz
Conventional free-air thermal current Ith (40 °C, 6 mm²) 35 A
AC-1 rated operational current 25 A at 40 °C, 25 A at 60 °C, 22 A at 70 °C (4 mm²)
AC-3 rated operational current 9 A at 220 to 440 V; 9.5 A at 500 V; 7 A at 690 V
AC-3 rated power 2.2 kW at 230 V; 4 kW at 400/415/440 V; 5.5 kW at 500 V and 690 V
AC-8a (no overload relay, 400 V, 40 °C) 12 A / 5.5 kW
Making / breaking capacity AC-3 10 x Ie / 8 x Ie
Short-circuit protection (no overload relay) gG fuse 25 A up to 500 V AC
Short-time withstand current Icw 300 A for 1 s; 150 A for 10 s; 80 A for 30 s; 60 A for 1 min; 35 A for 15 min
Heat dissipation per pole 0.8 W (AC-1); 0.1 W (AC-3)
Switching frequency 600 cycles/h AC-1; 1200 cycles/h AC-3; 300 cycles/h AC-2/AC-4
Mechanical durability 10 million operating cycles
Net weight 0.270 kg

Values above are taken from the ABB technical datasheet for the AF09-30-01 range. Ratings for IEC and UL/CSA operation differ, so use the correct column for your project standard.

How the AF09-30-01-13 coil and contacts work

AF contactors carry an electronic coil interface. When the coil is energised the interface applies a high pull-in current to close the magnet quickly, then drops to a low holding level. On the AF09-30-01-13 the pull-in average is about 50 VA on AC, and the holding value falls to roughly 2.2 VA, so the coil stays cool and the panel loses little heat in continuous duty. The same electronics make the wide coil range possible and include surge protection, so no external suppressor is needed across the coil.

The datasheet gives an operating time of 40 to 95 ms from coil energisation to N.O. contact closing and 38 to 90 ms for the N.C. contact to open. De-energising gives 11 to 95 ms for the N.O. contacts to open and 13 to 98 ms for the N.C. to close. If your sequencing logic depends on contact timing, plan for this spread rather than a single figure.

Where the AF09-30-01-13 fits and which parts go with it

The AF09-30-01-13 sits at the 9 A end of the AF range, below the AF12, AF16 and AF26 sizes. The ABB TF42 thermal overload relays mount directly on the contactor, and the TF42 family for this footprint covers settings from under 1 A up to 35 A, so a TF42 can be chosen to match the nominal current of a 4 kW motor. Front-mounted blocks such as CA4-10 or CA4-01 add auxiliary contacts, CAL4-11 adds a side-mounted pair, and VEM4 builds a mechanical and electrical interlock between two contactors for reversing duty.

Related items on the same range include the AF09-30-10-11 with a 24 to 60 V coil, the AF09Z-30-01-23 low-consumption version with the same 100 to 250 V coil, the AF09-22-00-13 with four main poles, and the larger AF26-30-00-13 for 11 kW.

Selection checklist for the AF09-30-01-13

  • Motor power and current: confirm the nameplate current is at or below 9 A at 400 V (AC-3), and check the duty if the motor starts frequently or inches.
  • Control voltage: confirm the supply falls inside 100 to 250 V, AC or DC, including its tolerance band against the 0.85 to 1.1 operating limits.
  • Auxiliary contacts: this version has one N.C. contact built in; add a CA4 block if you need N.O. feedback to a PLC.
  • Overload protection: select a TF42 range that brackets the motor current, or use a motor protection circuit breaker upstream.
  • Short-circuit protection: a gG fuse of 25 A is the maximum for the contactor itself when no overload relay is fitted; motor protection is excluded from that figure.
  • UL/CSA projects: check the separate UL rating table, where the general use rating is 25 A at 600 V AC.

Installation, commissioning and maintenance of the AF09-30-01-13

Mount the contactor on a 35 mm DIN rail (7.5 mm or 15 mm profile) or with two M4 screws placed diagonally. Contactors may be assembled side by side. The datasheet shows the permitted mounting positions, so check the diagram if the panel layout is unusual.

Main terminals take 1 to 6 mm² solid or stranded conductors, 0.75 to 6 mm² flexible with a non-insulated ferrule, and 0.75 to 4 mm² with an insulated ferrule; the stripping length is 10 mm. Tighten the main terminals to 1.5 Nm and the coil and auxiliary terminals to 1.2 Nm. Terminal screws are delivered open, and the screws of any unused terminal must be tightened before energising.

At commissioning, check the coil voltage at A1-A2 under load, operate the contactor a few times from the control circuit and listen for even magnet closing, and confirm that the N.C. mirror contact opens whenever the main poles close. For maintenance, inspect for discoloured terminals, loose conductors and dust build-up in the housing; the ambient limits are -25 to +60 °C when fitted with an overload relay and -40 to +70 °C without.

Typical applications of the AF09-30-01-13 in Oman and the GCC

In the Gulf region the AF09-30-01-13 is used on small pumps, fans, dosing skids, instrument air compressors and conveyors where the motor is around 4 kW. Typical sites include water desalination and treatment plants, oil and gas auxiliary skids, power station balance-of-plant panels and building services in Muscat. The wide 100 to 250 V coil is useful where one panel builder supplies projects fed from both 230 V AC and 110 V or 220 V DC control sources.

High panel temperatures are common in outdoor kiosks, so plan for the 60 °C derating point: the AC-1 current stays at 25 A up to 60 °C and falls to 22 A at 70 °C. Keeping the enclosure ventilated and the contactor away from heat sources protects both the coil and the contacts.

AF09-30-01-13 and neighbouring AF09 variants

Type Coil range Note
AF09-30-01-11 24 to 60 V AC, 20 to 60 V DC Not suited to direct PLC output control
AF09-30-01-12 48 to 130 V AC and DC Low-voltage AC controls
AF09-30-01-13 100 to 250 V AC and DC Widest use; fits 110 V and 230 V circuits
AF09-30-01-14 250 to 500 V AC and DC 400 V control circuits
AF09Z-30-01-23 100 to 250 V AC and DC, low consumption Pull-in 16 VA instead of 50 VA

Information to send with an RFQ for the AF09-30-01-13

  • Exact type: AF09-30-01-13 (order code 1SBL137001R1301), quantity and required delivery.
  • Control voltage and whether it is AC or DC, with frequency.
  • Motor kW and full-load current, plus supply voltage.
  • Overload relay or motor protection that must be quoted with it.
  • Any auxiliary contact blocks, interlocks or markers needed.
  • Project standard (IEC only, or UL/CSA ratings needed).

Documents and quotation

A technical datasheet for the AF09-30-01-13 is attached on this page, covering the ordering table, ratings, coil data, terminal data and accessory fitting details.

Seven Star LLC supplies ABB low-voltage control gear in Oman and the GCC. Send us the part number AF09-30-01-13, the quantity and your control voltage, and we will confirm availability and a quotation.

Other Models in the Abb Af09 3pole Contactor Range

Seven Star LLC supplies models from the Abb Af09 3pole Contactor range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
ABB AF09-30-01-13 3-Pole Contactor 4 kW, 100-250 V CoilContactors & Overload RelaysYou are viewing this model
ABB AF09Z-30-01-23 Low-Consumption Contactor 4 kW, 100-250 VContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet ABB AF09-30-01-13 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB AF09-30-01-13 3-Pole Contactor 4 kW, 100-250 V

Answers from our engineering team on installation, compatibility and integration.

01What coil voltage does the AF09-30-01-13 accept?
The coil covers 100 to 250 V at 50/60 Hz AC and also 100 to 250 V DC. The operating limits are 0.85 times the minimum voltage up to 1.1 times the maximum at ambient temperatures up to 60 degrees C.
02What load can the AF09-30-01-13 switch in AC-3?
It is rated 9 A at 400 V in category AC-3, which corresponds to 4 kW at 400 V. At 500 V the current rating is 9.5 A (5.5 kW) and at 690 V it is 7 A (5.5 kW).
03Does the AF09-30-01-13 have a built-in auxiliary contact?
Yes. The 01 in the type code means one N.C. auxiliary contact is built in. It is a mirror contact in line with annex F of IEC 60947-4-1, so it can be used for safety-related feedback.
04Which overload relay can be mounted on the AF09-30-01-13?
The ABB TF42 thermal overload relays mount directly on the AF09 to AF38 contactors. Pick the TF42 setting range so the motor nameplate current sits inside it, for a 4 kW motor usually a range around 7 to 10 A.
05Do I need a surge suppressor on the AF09-30-01-13 coil?
No. The datasheet states that AF contactors have built-in surge protection and do not require additional surge suppressors across the coil.