- Automation & ControlView all 2,610 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- HMI Displays
- Pneumatic Cylinders
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: ABB
ABB AF40-30-00-13 3-Pole Contactor 18.5 kW, 100-250 V
Description
ABB AF40-30-00-13 3-pole contactor for 18.5 kW motors
The ABB AF40-30-00-13 is a AF40 block contactor with three normally open main poles, screw terminals and an electronic coil interface that accepts 100 to 250 V on 50/60 Hz AC or on DC. According to the ABB product data it is rated for motors up to 18.5 kW at 400 V in category AC-3 and carries 70 A in AC-1 at 690 V and 40 °C. The order code is 1SBL347001R1300.
Because the coil spans such a wide band, the AF40-30-00-13 fits most control circuits without a dedicated control transformer: a 230 V AC supply, a 110 V AC supply and a 220 V DC battery-backed supply all fall inside the 100 to 250 V window. The contactor has built-in surge suppression, so no separate suppressor has to be added across the coil.
The AF40 is the entry size of the large-frame block. It suits a 18.5 kW pump or a medium fan drive that has outgrown the AF38, and it keeps the 55 mm width, so a row of these contactors fits tightly inside a compact starter panel.
Reading the AF40-30-00-13 type designation
The AF type code is compact, and every group of characters tells you something you must write correctly on the order.
| Code group | Meaning |
|---|---|
| AF40 | Contactor size; 40 A in AC-3 and 18.5 kW at 400 V |
| 30 | Three N.O. main poles |
| 00 | No auxiliary contacts built in; add CA4 or CAL4 blocks as needed |
| 13 | Coil code: 100 to 250 V 50/60 Hz and 100 to 250 V DC |
The same AF40 body is offered with coil codes 11 (24 to 60 V AC, 20 to 60 V DC), 12 (48 to 130 V), 13 (100 to 250 V) and 14 (250 to 500 V). The ABB catalogue notes that a 24 V PLC output should drive the coil through an RA4 interface relay. Always write the complete code including the suffix, because the coil version cannot be changed after delivery.
AF40-30-00-13 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | ABB / AF40-30-00-13 |
| Order code / EAN | 1SBL347001R1300 / 3471523132030 |
| Product type | 3-pole block contactor, screw terminals, AC/DC electronic coil |
| Rated control voltage Uc | 100 to 250 V 50/60 Hz and 100 to 250 V DC |
| Rated operational voltage, main circuit | Main Circuit 690 V |
| AC-3 rated operational current | (415 V) 60 °C 40 A |
| AC-3 rated operational power | (400 V) 18.5 kW |
| AC-1 rated operational current | (690 V) 40 °C 70 A |
| Conventional free-air thermal current Ith | acc. to IEC 60947-4-1, Open Contactors theta = 40 °C 105 A |
| Short-time withstand current Icw | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A |
| Maximum breaking capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A |
| Rated insulation / impulse voltage | acc. to IEC 60947-4-1 690 V / 6 kV |
| Coil consumption | Average Holding Value 50 / 60 Hz 4 V·A |
| Operate time, coil de-energised to N.C. contact closing | Between Coil De-energization and NC Contact Closing 19 to 105 ms |
| Power loss per pole | at Rated Operating Conditions AC-1 per Pole 3 W |
| Maximum mechanical switching frequency | 3600 cycles per hour |
| Main circuit connecting capacity | Flexible with Ferrule 1/2x 4 to 35 mm² |
| Control circuit connecting capacity | Flexible with Ferrule 1/2x 0.75 to 2.5 mm² |
| Dimensions W x D x H | 55 mm x 111 mm x 125.5 mm |
| Net weight | 0.95 kg |
| UL / CSA general use rating | 60 A at 600 V AC |
| Ambient air temperature | Close to Contactor Fitted with Thermal O/L Relay -40 to 70 °C |
Values in the table come from the ABB product page and catalogue for the AF40-30-00-13. Ratings differ between IEC and UL/CSA, so use the column that matches your project standard and the ambient conditions of your panel.
How the AF40-30-00-13 electronic coil interface works
Inside the AF40-30-00-13 an electronic interface supplies a high pull-in current to close the magnet quickly and then reduces the current to a low holding level. The holding consumption listed for the contactor is 4 V·A (average holding value at 50/60 Hz), which is small enough to ease the load on small control transformers and distributed relay outputs and keeps the coil cool in hot panels.
The operate times published on the product page (see the table above) show a defined window for closing and opening. Opening and closing are therefore well defined, and the coil is designed to ride through short voltage dips. Control circuits that carry large voltage swings, for example generator-fed or weak-grid supplies, are a natural application for this coil design.
The main poles are arranged in a block design with the contacts on the front, so add-on auxiliary blocks clip on the top or the side without touching the power circuit.
Where the AF40-30-00-13 fits and which parts go with it
The AF40-30-00-13 belongs to the AF40 to AF96 group of the ABB AF range. According to the ABB catalogue, the TF65 thermal overload relay (TF65 range 22 to 67 A) is the matching thermal relay for this size, and electronic EF65 or EF96 relays are the alternative where class 10E, 20E or 30E protection is wanted. A manual motor starter or a molded-case breaker normally supplies the short-circuit protection ahead of the contactor.
Accessories listed for this group include front-mounted CA4-10 (one N.O.) and CA4-01 (one N.C.) auxiliary blocks, side-mounted CAL4-11 blocks, TEF4 electronic timers and the VM4 mechanical interlock units. Reversing pairs use the BER65-4 or BER96-4 connection sets, which keeps wiring short and tidy.
Related parts in the same group include the AF40-30-00-13, AF52-30-00-13, AF65-30-00-13, AF80-30-00-13 and AF96-30-00-13, all with the same 100 to 250 V coil code. The contactor this page covers is the AF40-30-00-13.
Selection checklist for the AF40-30-00-13
- Motor rating: confirm that the nameplate current is below the AC-3 current of the contactor (40 A) at your supply voltage, and check whether the duty includes frequent starts, inching or plugging.
- Control voltage: the 13 coil covers 100 to 250 V AC and DC; confirm tolerance of the actual supply against the operating limits shown in the datasheet.
- Overload protection: choose a TF65 thermal relay whose setting range (22 to 67 A) brackets the motor current, or an EF electronic relay for higher trip classes.
- Auxiliary contacts: this version has none fitted; plan CA4 or CAL4 blocks for status feedback to the PLC.
- Short-circuit protection: coordinate the contactor with fuses or a breaker according to the type of coordination required by the project.
- Panel space: allow for a width of 55 mm and a depth of 111 mm, plus clearance for the overload relay below.
Installation, commissioning and maintenance of the AF40-30-00-13
Mount the AF40-30-00-13 on a 35 mm DIN rail of the 15 mm profile, or with two M4 or M6 screws placed diagonally. Main terminals accept flexible conductors with ferrules of 4 to 35 mm²; tighten them to the torque stated on the contactor and in the datasheet. Control terminals take flexible conductors with ferrules of 0.75 to 2.5 mm² with a tightening torque of 1.2 N·m.
At commissioning, measure the coil voltage at the terminals while the load is switched, operate the contactor several times from the control circuit and listen for clean, even closing. Check the overload relay setting against the motor nameplate and record the values in the commissioning sheet.
During maintenance, look for discoloured terminals, loose conductors and dust on the magnet face. In dusty or humid Gulf environments, keep panel filters clean and make sure condensation cannot form on the contactor when the panel is de-energised for long periods. Replace the contactor as a complete unit if contact erosion or welded poles are suspected.
Typical applications of the AF40-30-00-13 in Oman and the GCC
In a typical Gulf plant this is the contactor behind a cooling-water circulation pump, a ventilation fan in a pump house, or a screw compressor starter. For star-delta duty three contactors of the same family are normally combined, and the AF40 is often chosen for the line and delta contactors when the main current is around 40 A.
Panels in coastal plants face salt-laden air, and desert sites add dust and high enclosure temperatures. The ambient air temperature range given on the ABB product page, together with sound panel ventilation, is the key design input, and humidity control with anti-condensation heaters is good practice for panels that sit idle between shutdowns.
AF40-30-00-13 and the neighbouring AF40 to AF96 contactors
| Type | AC-3 power (400 V) | AC-3 current | AC-1 current (690 V, 40 °C) | Frame width |
|---|---|---|---|---|
| AF40-30-00-13 | 18.5 kW at 400 V | 40 A | 70 A | 55 mm |
| AF52-30-00-13 | 22 kW at 400 V | 53 A | 100 A | 55 mm |
| AF65-30-00-13 | 30 kW at 400 V | 65 A | 105 A | 55 mm |
| AF80-30-00-13 | 37 kW at 400 V | 80 A | 125 A | 70 mm |
| AF96-30-00-13 | 55 kW at 415 V | 96 A at 415 V | 130 A | 70 mm |
All five carry the same 100 to 250 V coil code. The AF40-30-00-13 is highlighted here because it matches 18.5 kW motor duty; if the motor is slightly larger, move up one size rather than relying on short-time overloads.
Information to send with an RFQ for the AF40-30-00-13
- Exact type AF40-30-00-13 (order code 1SBL347001R1300), quantity and required delivery time.
- Motor power, full-load current, supply voltage and start method (direct on line, star-delta, reversing).
- Control voltage and whether it is AC or DC, including frequency.
- Overload relay and auxiliary contact blocks required with the contactor.
- Panel ambient temperature, altitude and any marine or hazardous-area requirements.
- Project documentation needed, for example datasheets or certificates for the order code.
Documents and quotation
The official ABB short form catalog for motor protection and control (1SBC100195C0202, September 2015 edition, English) is attached on this page as a PDF and lists the ABB AF40-30-00-13 by its order code. It covers the AF range rated operational currents and motor powers for AC-3 and AC-1 duty, the 100-250 V 50/60 Hz and DC wide-range electronic coil, the auxiliary contact blocks, the surge suppressors, the matching thermal and electronic overload relays and the dimension drawings. Check the 18.5 kW motor rating at 400 V, the coil voltage and the auxiliary contacts you need before ordering, then send us the quantity and the delivery location for a quotation.
Seven Star LLC supplies ABB low-voltage control gear in Oman and the GCC. Share your motor data or panel schedule and we will match the contactor, overload relay and accessories for the complete starter.
Other Models in the Abb Af40 96 3pole Contactor Range
Seven Star LLC supplies models from the Abb Af40 96 3pole Contactor range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| ABB AF40-30-00-13 3-Pole Contactor 18.5 kW, 100-250 V | Contactors & Overload Relays | You are viewing this model |
| ABB AF52-30-00-13 3-Pole Contactor 22 kW, 100-250 V | Contactors & Overload Relays | View details |
| ABB AF65-30-00-13 3-Pole Contactor 30 kW, 100-250 V | Contactors & Overload Relays | View details |
| ABB AF80-30-00-13 3-Pole Contactor 37 kW, 100-250 V | Contactors & Overload Relays | View details |
| ABB AF96-30-00-13 3-Pole Contactor 55 kW, 100-250 V | Contactors & Overload Relays | View details |
Datasheets & Documents
- Datasheet ABB Motor Protection and Control Short Form Catalog 1SBC100195C0202 (PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB AF40-30-00-13 3-Pole Contactor 18.5 kW, 100-250
Answers from our engineering team on installation, compatibility and integration.
01What coil voltage does the AF40-30-00-13 accept?
The 13 coil code covers 100 to 250 V at 50/60 Hz AC and also 100 to 250 V DC. The electronic coil interface lowers holding consumption and tolerates large control voltage variations.
02What motor power can the AF40-30-00-13 switch?
The ABB data lists 18.5 kW at 400 V in AC-3 for this contactor, with an AC-3 rated operational current of 40 A. Check the motor nameplate current and the starting duty before you confirm the size.
03Does the AF40-30-00-13 include auxiliary contacts?
No. The 00 in the type code means no auxiliary contacts are built in. Front-mounted CA4 blocks and side-mounted CAL4 blocks are added when status feedback or interlocking is required.
04Which overload relay is used with the AF40-30-00-13?
The ABB catalogue lists the TF65 thermal overload relay (22 to 67 A) for this size, and the EF65 or EF96 electronic relays as the alternative. Select the setting range around the motor nameplate current.
05Do I need a surge suppressor across the AF40-30-00-13 coil?
No. ABB states that the AF contactors have built-in surge suppression, so an external suppressor is not required across the coil in normal installations.