Brand:

ABB AF26Z-30-00-23 3-Pole Contactor 11 kW, Low-Consumption

Description

ABB AF26Z-30-00-23 11 kW low-consumption contactor for 100 to 250 V control

The ABB AF26Z-30-00-23 is a 3-pole AF26 contactor rated 26 A in AC-3, or 11 kW at 400 V, in the low-consumption (Z) version. The coil takes 100 to 250 V at 50/60 Hz AC or DC. The ABB order code is 1SBL236001R2300, the EAN is 3471523114135 and the net weight is 0.350 kg. No auxiliary contact is built in, so any feedback contact is added as a front or side block.

With its 11 kW rating, the AF26Z-30-00-23 is typically chosen for mid-size pumps, fans, compressors and conveyor drives. The Z coil keeps the control-side burden low, which matters in panels that carry many contactors from one supply.

Decoding AF26Z-30-00-23

Group Meaning in AF26Z-30-00-23
AF26 Size with 26 A AC-3 rating, 11 kW at 400 V
Z Low-consumption coil interface
30 Three N.O. main poles
00 No auxiliary contact built in
23 Coil 100 to 250 V 50/60 Hz and 100 to 250 V DC

The other Z coil codes for this body are 20 (12 to 20 V DC), 21 (24 to 60 V), and 22 (48 to 130 V). The Z-series code numbers start at 2, whereas standard AF coil codes start at 1.

AF26Z-30-00-23 technical data

Parameter Specification
Manufacturer / part number ABB / AF26Z-30-00-23
Order code / EAN 1SBL236001R2300 / 3471523114135
Poles and built-in contacts 3 N.O. main poles; no built-in auxiliary contact
Coil voltage Uc 100 to 250 V 50/60 Hz and 100 to 250 V DC
Coil consumption (AF..Z) Pull-in average 16 VA (AC) or 12 to 16 W (DC); holding 1.7 VA / 1.5 W (AC) or 1.7 W (DC)
Coil operating limits 0.85 x Uc min to 1.1 x Uc max at 60 °C
Operating time N.O. closing 40 to 95 ms; N.O. opening 11 to 95 ms
Rated operational voltage Ue (IEC) 690 V max.
Rated frequency limits 25 … 400 Hz
Conventional free-air thermal current Ith (40 °C, 10 mm²) 50 A
AC-1 rated operational current 45 A at 40 °C; 40 A at 60 °C; 32 A at 70 °C
AC-3 rated operational current 26 A at 220 to 440 V; 23 A at 500 V; 17 A at 690 V
AC-3 rated power 6.5 kW at 230 V; 11 kW at 400/415 V; 15 kW at 440, 500 and 690 V
AC-8a (no overload relay, 400 V, 40 °C) 30 A / 15 kW
Making / breaking capacity AC-3 10 x Ie / 8 x Ie
Short-circuit protection (no overload relay) gG fuse 50 A up to 500 V AC
Short-time withstand current Icw 700 A for 1 s; 350 A for 10 s; 225 A for 30 s; 150 A for 1 min; 50 A for 15 min
Maximum breaking capacity (cos phi 0.45) 500 A at 440 V; 200 A at 690 V
Heat dissipation per pole 1.8 W (AC-1); 0.6 W (AC-3)
Switching frequency 600 cycles/h AC-1; 1200 cycles/h AC-3; 150 cycles/h AC-2/AC-4
Mechanical durability 10 million operating cycles
UL/CSA (UL 508) NEMA size 1; general use 45 A at 600 V AC; 3-phase 7.5 hp at 200-240 V, 15 hp at 440-480 V, 20 hp at 550-600 V
Net weight 0.350 kg

All ratings come from the ABB technical datasheet for the AF26 range with screw terminals.

Operating principle of the AF26Z-30-00-23

A magnet system driven by an electronic interface closes the three main poles. At pull-in the AF26Z-30-00-23 draws about 16 VA from an AC supply, a small fraction of the 50 VA a standard AF26 coil takes, and holds at about 1.7 VA. The built-in surge protection removes the need for an RC or varistor module on the coil. The drop-out voltage is 60 % of the minimum coil voltage or lower, so the contactor releases cleanly when the control supply is removed.

The datasheet quotes a 22 ms average dip withstand for the Z version at 24 to 250 V, which is useful on supplies that sag briefly during motor starting.

Compatible parts for the AF26Z-30-00-23

A TF42 thermal overload relay mounts directly on the AF26Z-30-00-23; for an 11 kW motor at 400 V the nameplate current is around 22 A, which falls in the TF42-24 range of 20 to 24 A, and for slightly smaller motors the TF42-20 and TF42-16 ranges apply. CA4 and CC4 one-pole blocks, the CAL4-11 side block, the CA4-22E and CA4-31E four-pole blocks add contacts, and VEM4 builds a reversing interlock. BEA26-4 links join the contactor to a manual motor starter and BER38-4 provides connection sets for reversing contactors.

Other contactors on the site and in the range include the AF26-30-00-13 with a standard 100 to 250 V coil, the AF09Z-30-01-23 for 4 kW, and the larger AF38 size.

Selecting the AF26Z-30-00-23

  • Motor current: 26 A at 400 V AC-3 maximum; at 500 V it is 23 A and at 690 V it is 17 A.
  • Control supply: 100 to 250 V AC or DC within tolerance.
  • Contacts: none built in; specify CA4 or CAL4 blocks for status feedback.
  • Overload relay: choose the TF42 range that matches the motor nameplate current.
  • Fuse protection of the contactor alone is a gG 50 A fuse up to 500 V AC.
  • Check ambient temperature: AC-1 current is 45 A at 40 °C, 40 A at 60 °C and 32 A at 70 °C.

Installing and servicing the AF26Z-30-00-23

Fix the contactor on a 35 mm rail or with two M4 screws placed diagonally, and keep the contactors side by side if space is limited. Main terminals accept 2.5 to 10 mm² solid or stranded (one or two conductors) and 1.5 to 10 mm² flexible with a ferrule; the stripping length is 14 mm and the screws are M4, tightened to 2.5 Nm. Coil and auxiliary terminals are M3.5 and take 0.75 to 2.5 mm² at 1.2 Nm.

At commissioning, verify the coil voltage at A1-A2, check that all three poles close together, and confirm that unused terminal screws are tight. Over the life of the contactor, look for terminal discolouration, loose conductors and contact wear. The datasheet gives a mechanical life of 10 million operating cycles, though electrical life depends on the load category and switching frequency.

AF26Z-30-00-23 in oil and gas, water and power duty in Oman

The AF26Z-30-00-23 fits motor feeders on pump stations, cooling water fans, compressor skids, desalination dosing and booster sets, and power station auxiliaries across Oman and the GCC. With a 11 kW rating and a coil that accepts both 110 V and 230 V circuits, one stock part covers many existing panels.

In hot enclosures, rely on the derating figures: the AC-1 rating drops from 45 A to 32 A at 70 °C, so panel ventilation and spacing should be reviewed for outdoor kiosks.

AF26 coil variants beside the AF26Z-30-00-23

Type Coil range Note
AF26Z-30-00-20 12 to 20 V DC Observe A1+ and A2- polarity
AF26Z-30-00-21 24 to 60 V AC, 20 to 60 V DC Can be driven by a 24 V DC PLC output of 500 mA
AF26Z-30-00-22 48 to 130 V AC and DC Low-voltage control
AF26Z-30-00-23 100 to 250 V AC and DC Mains-voltage control, low consumption
AF26-30-00-14 250 to 500 V AC and DC Standard coil, 400 V control

RFQ checklist for AF26Z-30-00-23

  • Type AF26Z-30-00-23 (1SBL236001R2300) and quantity.
  • Control voltage and frequency.
  • Motor power, current and supply voltage.
  • Overload relay and accessories required.
  • Required delivery and project standard.

Documents and quotation

A technical datasheet for the AF26Z-30-00-23 is attached on this page with ordering, ratings, coil, terminal and accessory data.

Seven Star LLC supplies ABB low-voltage control gear in Oman and the GCC. Send us the part number AF26Z-30-00-23 and your quantity, and we will confirm availability and a quotation.

Other Models in the Abb Af26 3pole Contactor Range

Seven Star LLC supplies models from the Abb Af26 3pole Contactor range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
ABB AF26Z-30-00-23 3-Pole Contactor 11 kW, Low-ConsumptionContactors & Overload RelaysYou are viewing this model
ABB AF26-30-00-14 3-Pole Contactor 11 kW, 250-500 V CoilContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet ABB AF26Z-30-00-23 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB AF26Z-30-00-23 3-Pole Contactor 11 kW,

Answers from our engineering team on installation, compatibility and integration.

01What is the AC-3 rating of the AF26Z-30-00-23?
The rating is 26 A at 400 V, equal to 11 kW at 400 or 415 V. At 440 V the power is 15 kW, at 500 V the current is 23 A and at 690 V it is 17 A.
02Does the AF26Z-30-00-23 include an auxiliary contact?
No. The 00 in the type code means no auxiliary contact is built in. Add a front-mounted CA4 block or a side-mounted CAL4-11 block when status contacts are needed.
03What coil does the AF26Z-30-00-23 use?
It has a 100 to 250 V coil for 50/60 Hz AC and DC. As a Z version it draws about 16 VA at pull-in and about 1.7 VA when held, which is less than the standard AF26 coil.
04Which TF42 overload relay suits an 11 kW motor on the AF26Z-30-00-23?
An 11 kW, 400 V motor draws about 22 A, which sits in the TF42-24 range of 20 to 24 A. Always select the range from the actual motor nameplate current.
05What fuse protects the AF26Z-30-00-23 without an overload relay?
The datasheet gives a gG fuse of 50 A for voltages up to 500 V AC. This protects the contactor only; motor protection is excluded and must be provided separately.