ABB MS132-2.5 Manual Motor Starter 1.6-2.5 A
Description
ABB MS132-2.5 manual motor starter, 1.6 to 2.5 A setting range
The ABB MS132-2.5 is a three-pole manual motor starter, also called a motor protection circuit breaker, with a rated operational current of 2.5 A and an adjustable thermal release from 1.6 to 2.5 A. It switches a motor on and off by hand and protects it against short circuit, overload and phase failure without a separate fuse. The order code is 1SAM350000R1007.
ABB gives the MS132-2.5 a rated service short-circuit breaking capacity of 100 kA at 400 V AC and trip class 10. At 400 V it is rated for motors up to 0.75 kW. Further features listed by ABB are the built-in disconnect function, temperature compensation, a trip-free mechanism, a rotary handle with clear position indication and a handle that can be locked against unintended changes.
The ABB MS132-2.5 covers motors from 1.6 to 2.5 A, which means fractional-kilowatt pump motors, small blowers, laboratory equipment and instrument cabinets with three-phase auxiliaries.
Reading the MS132-2.5 type designation
The type name of the MS132 family is built from the family prefix and the upper limit of the setting range.
| Code group | Meaning |
|---|---|
| MS132 | Manual motor starter family, 45 mm wide |
| 2.5 | Upper end of the setting range in amperes; this device is set between 1.6 and 2.5 A |
| Ie | Rated operational current 2.5 A |
Because the family has many neighbouring ratings, it is worth checking the nameplate current of the motor against the 1.6 to 2.5 A window on this type, rather than only comparing kilowatts.
MS132-2.5 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | ABB / MS132-2.5 |
| Order code / EAN | 1SAM350000R1007 / 4013614400070 |
| Type | Manual motor starter (motor protection circuit breaker), 3-pole, rotary handle |
| Setting range (thermal release) | 1.6 to 2.5 A |
| Rated operational current Ie | 2.5 A |
| AC-3 rated power at 400 V | 0.75 kW |
| Instantaneous trip setting Ii | 31.3 A |
| Trip class | 10 |
| Rated service short-circuit breaking capacity Ics, 400 V AC | 100 kA |
| Ics as listed on the product page | (230 V AC) 100 kA |
| Rated ultimate short-circuit breaking capacity Icu | (230 V AC) 100 kA |
| Rated operational voltage | Main Circuit 690 V AC |
| Rated insulation / impulse voltage | 690 V / Main Circuit 6 kV |
| Operating frequency | 0 to 400 Hz |
| Power loss per pole | at Rated Operating Conditions AC-3 per Pole 1.8 W |
| Electrical / mechanical durability | 50000 cycle / Nr. Operations 100000 cycle |
| Degree of protection | Housing IP20 |
| Ambient air temperature | Around the Enclosure 0 to +40 °C |
| Maximum altitude without derating | 2000 m |
| Main circuit connecting capacity | Flexible with Ferrule 1/2x 0.75 to 2.5 mm² |
| Tightening torque | Main Circuit 0.8 to 1.2 N·m |
| Mounting | TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 |
| Dimensions W x H x D | 45 mm x 90 mm x 86.75 mm |
| Net weight | 0.265 kg |
| UL / CSA full-load amps (200 V, 3-phase) | (200 V AC) Three Phase 2.5 A |
Values come from the ABB product page and catalogue for the MS132-2.5. Short-circuit breaking capacity depends on the rating and the voltage, so check the figure that matches your supply voltage and prospective fault level.
How the MS132-2.5 protects the motor
The MS132-2.5 combines a thermal release for overload with a magnetic release for short circuit. The thermal element follows the motor current within the 1.6 to 2.5 A range and trips in line with trip class 10, and the instantaneous magnetic trip is fixed at 31.3 A on this rating. Temperature compensation keeps the thermal trip stable when the surrounding air changes, within the ambient limits given by ABB (0 to +40 °C around the enclosure).
A phase-failure sensitivity in the thermal release protects the motor when one supply phase is lost, which is a common cause of winding damage in remote pump stations. The rotary handle gives clear position indication (listed by ABB as ON / OFF / TRIP), so an operator can see at a glance what state the starter is in.
It is often fitted in motor control centres where dozens of small feeders each need their own protective device, and where 45 mm width per starter keeps the panel compact.
Where the MS132-2.5 fits and which parts go with it
The MS132-2.5 is normally the first device in a direct-on-line motor feeder. It sits ahead of a contactor of the AF family, such as the AF09 to AF38 sizes for small and medium motors, and it can be combined with that contactor through ABB mounting accessories listed for the range (for example BEA16-4 and BEA38-4 in the ABB catalogue).
ABB lists auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, three-phase busbars, power in-feed blocks and terminal spacers as accessories for the MS132 family; use these to build group feeders without extra cabling.
Other types in the same family include the MS132-1.6, MS132-4.0, MS132-6.3, MS132-10, MS132-12, MS132-16, MS132-20, MS132-25, MS132-32. This page covers the MS132-2.5.
Selection checklist for the MS132-2.5
- Motor nameplate current: confirm it lies inside the 1.6 to 2.5 A setting range with margin at both ends of the dial.
- Motor power: ABB lists 0.75 kW at 400 V in AC-3; check the actual motor rating and the supply voltage.
- Fault level: the rated service short-circuit breaking capacity is 100 kA at 400 V AC, so verify the prospective short-circuit current at the starter.
- Starting duty: trip class 10 suits normal starts; heavy-start loads need a check against the time-current curve.
- Accessories: decide on auxiliary contacts, trip signalling, undervoltage or shunt releases and busbars before ordering.
- Panel space: the device is 45 mm wide and 90 mm high; allow clearance for the handle and the wiring.
Installation, commissioning and maintenance of the MS132-2.5
Mount the MS132-2.5 on a 35 mm DIN rail of the 15 mm profile in any of the mounting positions permitted in the ABB documentation. Main terminals take flexible conductors with ferrules of 0.75 to 2.5 mm²; use the tightening torque of 0.8 to 1.2 N·m and a Pozidriv 2 screwdriver. The minimum horizontal mounting distance listed by ABB is 0 mm on a conductive board at up to 400 V, so check the datasheet when planning side-by-side rows.
At commissioning, set the dial to the motor nameplate current within the 1.6 to 2.5 A range, close the handle and start the motor under supervision. Operate the handle through its positions to confirm that it indicates correctly, and check that a downstream contactor drops out where an auxiliary contact is wired to it.
In maintenance rounds, check the terminal tightness, look for discolouration, and record any trip with the cause. If a trip follows a short circuit, inspect the motor and cable before closing the starter again, and compare the fault level with the breaking capacity before relying on it for another fault.
Typical applications of the MS132-2.5 in Oman and the GCC
The MS132-2.5 covers motors from 1.6 to 2.5 A, which means fractional-kilowatt pump motors, small blowers, laboratory equipment and instrument cabinets with three-phase auxiliaries.
Motor protection devices on Gulf sites work in warm panels, so keep the enclosure ambient inside the range printed on the device, and keep the dial setting consistent with the nameplate current at the actual supply voltage. In coastal plants a clean, dry panel and sealed cable entries are as important as the starter rating.
MS132-2.5 and the neighbouring MS132 ratings
| Type | Setting range | AC-3 power | Instantaneous trip Ii | Ics |
|---|---|---|---|---|
| MS132-1.6 | 1.0 to 1.6 A | 0.55 kW at 400 V | 20 A | 100 kA at 400 V |
| MS132-2.5 | 1.6 to 2.5 A | 0.75 kW at 400 V | 31.3 A | 100 kA at 400 V |
| MS132-4.0 | 2.5 to 4.0 A | 1.5 kW at 400 V | 50 A | 100 kA at 400 V |
| MS132-6.3 | 4.0 to 6.3 A | 2.2 kW at 400 V | 78.8 A | 100 kA at 400 V |
| MS132-10 | 6.3 to 10 A | 4 kW at 400 V | 150 A | 100 kA at 400 V |
| MS132-12 | 8.0 to 12 A | 5.5 kW at 400 V | 180 A | 100 kA at 400 V |
| MS132-16 | 10 to 16 A | 7.5 kW at 400 V | 240 A | 100 kA at 400 V |
| MS132-20 | 16 to 20 A | 7.5 kW at 400 V | 300 A | 100 kA at 400 V |
| MS132-25 | 20 to 25 A | 11 kW at 400 V | 375 A | 50 kA at 400 V |
| MS132-32 | 25 to 32 A | 15 kW at 400 V | 480 A | 30 kA at 400 V |
The MS132-2.5 is highlighted in the family because its 1.6 to 2.5 A window matches 0.75 kW motors at 400 V. Where the motor current is close to the boundary between two ranges, choose the range where the nameplate current sits near the middle of the dial.
Information to send with an RFQ for the MS132-2.5
- Exact type MS132-2.5 (order code 1SAM350000R1007), quantity and required delivery time.
- Motor nameplate data: power, full-load current, voltage, frequency and start method.
- Prospective short-circuit current at the starter location.
- Accessories required: auxiliary or signalling contacts, releases, busbars, in-feed blocks.
- Panel ambient temperature and altitude.
- Documents needed with the order, for example datasheets or certificates.
Documents and quotation
The official ABB data sheet for the MS132 series (document 2CDC131021D0202, English) is attached on this page as a PDF and applies to the ABB MS132-2.5. It lists every MS132 setting range with its order code and rated AC-3 motor power, together with the trip class 10 overload data, short-circuit breaking capacity, approvals, accessories and dimension drawings. Check the rating and the characteristic against your circuit before ordering, then send us the quantity and the delivery location for a quotation.
Seven Star LLC supplies ABB low-voltage control gear in Oman and the GCC. Share your motor schedule and we will match the starter, the contactor and the accessories for the full feeder.
Other Models in the Abb Ms132 Manual Motor Starter Range
Seven Star LLC supplies models from the Abb Ms132 Manual Motor Starter range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| ABB MS132-1.6 Manual Motor Starter 1.0-1.6 A | Contactors & Overload Relays | View details |
| ABB MS132-2.5 Manual Motor Starter 1.6-2.5 A | Contactors & Overload Relays | You are viewing this model |
| ABB MS132-4.0 Manual Motor Starter 2.5-4.0 A | Contactors & Overload Relays | View details |
| ABB MS132-6.3 Manual Motor Starter 4.0-6.3 A | Contactors & Overload Relays | View details |
| ABB MS132-12 Manual Motor Starter 8.0-12 A | Contactors & Overload Relays | View details |
| ABB MS132-20 Manual Motor Starter 16-20 A | Contactors & Overload Relays | View details |
Datasheets & Documents
- Datasheet ABB MS132 Manual Motor Starter Data Sheet (PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB MS132-2.5 Manual Motor Starter 1.6-2.5 A
Answers from our engineering team on installation, compatibility and integration.
01What current range does the MS132-2.5 cover?
The thermal release of the MS132-2.5 is adjustable from 1.6 to 2.5 A, and the rated operational current is 2.5 A. Set the dial to the motor nameplate current within that window.
02What motor power can the MS132-2.5 protect?
ABB lists 0.75 kW at 400 V in category AC-3 for this type. Confirm the real motor nameplate current and voltage, since the thermal range is what actually sets the protection.
03What is the short-circuit breaking capacity of the MS132-2.5?
ABB lists a rated service short-circuit breaking capacity of 100 kA at 400 V AC for this type, with trip class 10. Always compare it with the prospective fault level at the installation.
04Can I mount a contactor directly on the MS132-2.5?
Yes, ABB lists mounting accessories for combining the starter with AF contactors, so the pair forms a compact direct-on-line starter. Check the contactor size against the motor rating before you order.
05Does the MS132-2.5 protect against phase failure?
Yes. ABB describes the manual motor starter as protecting against short circuit, overload and phase failure without needing a separate fuse. Always verify the correct dial setting at commissioning.