Honeywell STG88L SmartLine STG800 Gauge Pressure Transmitter
Description
Overview of Honeywell STG88L
Honeywell STG88L is a 6,000 psi (413.68 bar) gauge pressure transmitter in the STG800 SmartLine range. It is one of only two L models above 3,000 psi in the family and one of the few high-pressure transmitters that retains 200:1 maximum turndown and a 0.030 percent standard accuracy.
Its minimum span is 30 psi (2.06 bar), its MAWP equals its range at 6,000 psi (420 bar), and the overpressure limit given in the datasheet is 9,000 psi (620 bar). That combination suits hydraulic, injection and test applications at pressures where plain 3,000 psi devices cannot be used.
Key features of STG88L
- Range minus 14.7 to 6,000 psi (minus 1.01 to 413.68 bar).
- Accuracy 0.030 percent standard, 0.025 percent optional with 12:1 reference turndown.
- Knee C of 500 psi (34.47 bar).
- Total performance 0.081 percent of span at 1,200 psi.
- Overpressure limit 9,000 psi (620 bar).
STG88L in numbers
| Parameter | Value |
|---|---|
| Model | STG88L (STG800 SmartLine gauge pressure, L-suffix) |
| Upper / lower range limit | 6000 psi (413.68 bar) / -14.7 psi (-1.01 bar) |
| Minimum span | 30 psi (2.06 bar) |
| Maximum turndown | 200:1 |
| Accuracy (standard / optional) | 0.030 / 0.025 percent of span |
| Stability (percent of URL per year, 15 years) | Up to 0.010 for the STG800 family |
| Reference turndown (standard / high accuracy) | 10:1 / 12:1 |
| Accuracy knee C | 500 psi (34.47 bar) |
| Temperature coefficients (D / E / F) | 0.0325 / 0.025 / 0.01 |
| Total performance example | 0.081 percent of span at 1200 psi |
| MAWP | 6000 psi (420 bar) |
| Overpressure limit | 9000 psi (620 bar) |
| Output / protocols | 4 to 20 mA, Honeywell DE, HART 7 or FOUNDATION Fieldbus |
| Supply voltage | HART: 10.8 to 42.4 VDC (load 0 to 1,440 ohms); DE: 15 to 49.3 VDC; FOUNDATION Fieldbus: 9.0 to 32.0 VDC |
| Response time | As fast as 80 ms |
| Rated ambient / meter body temperature | -40 to 85 degC / -40 to 110 degC (operative limit 125 degC) |
| Process connections (STG80L inline) | 1/2-inch NPT female, 1/2-inch NPT male, 9/16-18 high-pressure cone and thread female, G1/2-B male, DIN 19213 (except STG89L) |
| Wetted parts (STG80L) | 316L stainless steel or Hastelloy C-276 diaphragm and process head |
| Fill fluid | Silicone 200, CTFE, NEOBEE M-20 or Silicone 704 |
| Housing | Polyester powder-coated low-copper aluminium, Type 4X / IP66 / IP67; stainless housing optional |
| Net weight (STG80L) | 3.6 lb (1.6 kg) with aluminium housing |
| Additional features | Plugged impulse line detection option; NAMUR NE-107 diagnostics (HART, FF); display languages EN, DE, FR, IT, ES, RU, UK, TR, CN, JP |
How STG88L differs from STG87L, STG89L and the other STG800 variants
Next to the STG87L (3,000 psi) the STG88L doubles the range and the minimum span (30 psi versus 15 psi) but keeps the same 0.030 percent accuracy and 200:1 turndown. Next to the STG89L (10,000 psi) it offers a better accuracy statement, 0.030 percent versus 0.055 percent, because the STG89L has a larger fixed accuracy term A of 0.015.
A noteworthy difference concerns connections: the STG88L supports the DIN 19213 connection among its options, whereas the datasheet excludes it for the STG89L.
| Model | URL | Min span | Std accuracy | Overpressure |
|---|---|---|---|---|
| STG87L | 3000 psi | 15 psi | 0.030% | 4500 psi |
| STG88L | 6000 psi | 30 psi | 0.030% | 9000 psi |
| STG89L | 10000 psi | 100 psi | 0.055% | 15000 psi |
Oman and GCC applications for STG88L
Applications in Oman include chemical injection pumps, high-pressure hydraulic power units for valve actuation, test benches, and the discharge of high-pressure plunger pumps in water jet and descaling systems. Offshore skids and workshop test stands in the GCC also use similar devices.
For reciprocating pumps raise the damping value to smooth pulsation.
A practical point for buyers comparing quotes: the STG88L sits at the top of the range where the datasheet still allows the same 0.030 percent standard accuracy as the 500 psi model, so replacing a 10,000 psi transmitter with the STG88L is worthwhile wherever your real maximum is under 6,000 psi, since the minimum span halves from 100 psi to 30 psi and the 12:1 reference turndown of the high-accuracy option is retained.
Selecting STG88L correctly
Choose the STG88L if working pressure is between about 3,000 and 6,000 psi. Verify that the mating fitting is rated for the pressure, particularly the 9/16-18 cone and thread; check wetted material compatibility (316L stainless steel or Hastelloy C-276) and decide between silicone and CTFE fill.
The transmitter is available in HART, DE, FOUNDATION Fieldbus and analog variants.
Commissioning the STG88L
Install with high-pressure rated tubing and fittings, de-pressurise slowly, and always mount the transmitter with the diaphragm end protected from mechanical shock.
After wiring check the minimum supply voltage and set range and units.
Maintenance and diagnostics
Check the process connection for leaks at start-up and after each pressure cycle series. Verify zero and span periodically against a dead-weight tester.
Ordering Checklist for the Honeywell STG88L
Before you ask for a quotation for the Honeywell STG88L, check the full order code on the nameplate of the unit you are replacing, the supply voltage, and the process or signal ranges your system expects. If this is an upgrade rather than a like-for-like swap, tell us the existing make and model so that mounting, wiring and connection details can be checked against the pressure transmitters already installed. For multi-unit orders, list the quantity per site and the delivery location in Oman or the wider GCC, so packing, paperwork and lead time can be confirmed in a single quotation.
Installation and Commissioning Planning
Planning ahead shortens downtime when a Honeywell STG88L goes into service. Confirm the available mounting space, cable entry or process connection, and the tools and spare seals needed on the day. Keep the existing configuration or calibration data so the new unit can be set up to match, and check that loop drawings and the asset register are updated after the swap. If the installation has to fit a short shutdown window, tell us the date when you request a quotation so that delivery of the Honeywell equipment can be planned around it.
Frequently asked questions about STG88L
What is the range of the Honeywell STG88L? It spans minus 14.7 psi to 6,000 psi (minus 1.01 to 413.68 bar), with a minimum span of 30 psi (2.06 bar).
What is the overpressure limit of the STG88L? The STG800 datasheet gives an overpressure limit of 9,000 psi (620 bar) for the STG88L.
What accuracy does the STG88L have? Standard accuracy is 0.030 percent of span, with 0.025 percent available as the high-accuracy option.
Is the STG88L available with fieldbus? Yes, the family offers 4 to 20 mA, DE, HART 7 and FOUNDATION Fieldbus.
What is the total performance of the STG88L? 0.081 percent of span at 1,200 psi with 5:1 turndown and a 28 degC shift.
Documents and quotation
The STG800 specification 34-ST-03-83 documents the STG88L and is available on request.
To request a quotation for Honeywell STG88L, send part number, quantity, range, output and connection details to Seven Star LLC.
Other Models in the STG800L Range
Seven Star LLC supplies models from the STG800L range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Honeywell STG83L SmartLine STG800 Gauge Pressure Transmitter | Pressure Transmitters | View details |
| Honeywell STG84L SmartLine STG800 Gauge Pressure Transmitter | Pressure Transmitters | View details |
| Honeywell STG88L SmartLine STG800 Gauge Pressure Transmitter | Pressure Transmitters | You are viewing this model |
Datasheets & Documents
- Datasheet Honeywell STG88L SmartLine STG800 Gauge Pressure Transmitter Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).
Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.
Honeywell company profile
| Origins | 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927 |
|---|---|
| Brands in our range | Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance |
| Gent | Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005 |
| Elster | Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015 |
Milestones
- 1885: The Butz thermostat business starts in Minneapolis.
- 1927: It merges with Mark Honeywell's company.
- 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
- 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.
Honeywell products we list
| Family | Models | Typical use |
|---|---|---|
| Fixed gas detectors | Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID | Flammable, toxic and VOC gas detection in process areas |
| Sensors, flame detection and control | SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel | Replacement sensors, fire detection and gas detection control panels |
| Transmitters and flow | SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis | Process pressure and mass flow measurement |
| Elster gas metering | Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display | Gas meters, volume correction and fiscal flow computing |
| Gent fire alarm systems | Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell | Addressable and conventional fire alarm systems in buildings and plants |
| Chadwick-Helmuth rotor track and balance | 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor | Helicopter rotor track and balance and propeller balancing |
Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.
Where Honeywell products are used
In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.
Ordering Honeywell products: what we need
Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.
Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.
Browse Honeywell products by category: Fire & Gas Detector, Vibration, Flowmeters, Pressure Instrumentation, Temperature Instrumentation.
FAQ
Questions about the Honeywell STG88L SmartLine STG800 Gauge Pressure
Answers from our engineering team on installation, compatibility and integration.
01What is the range of the Honeywell STG88L?
It spans minus 14.7 psi to 6,000 psi (minus 1.01 to 413.68 bar), with a minimum span of 30 psi (2.06 bar).
02What is the overpressure limit of the STG88L?
The STG800 datasheet gives an overpressure limit of 9,000 psi (620 bar) for the STG88L.
03What accuracy does the STG88L have?
Standard accuracy is 0.030 percent of span, with 0.025 percent available as the high-accuracy option.
04Is the STG88L available with fieldbus?
Yes, the family offers 4 to 20 mA, DE, HART 7 and FOUNDATION Fieldbus.
05What is the total performance of the STG88L?
0.081 percent of span at 1,200 psi with 5:1 turndown and a 28 degC shift.