Lovato DMED300T2 Three-Phase 80 A Direct Energy Meter

Description

Direct-connection three-phase energy metering on DIN rail

The DMED300T2 is a three-phase energy meter with neutral from the Lovato Electric DME range. It connects directly to the circuit up to 80 A, so no current transformers are needed, and it measures imported and exported active and reactive energy. It occupies four DIN-rail modules and suits sub-metering of feeders, tenant loads, pumps and machine lines. Typical applications include feeder sub-metering, tenant cost allocation and energy reporting in distribution boards, where a compact meter with pulse outputs is easier to integrate than a full network analyzer.

The meter shows multiple measurements on its LCD and offers two programmable static pulse outputs for remote counting by a PLC or energy management system. It is non-expandable and has no built-in communication port, which keeps installation simple: wire the three phases and neutral, set the pulse rate if needed and read energy on the display. The values below come from the Lovato data sheet.

Technical specifications

Parameter Specification
Type Three-phase plus neutral energy meter, order code DMED300T2
Connection Direct, 80 A maximum (Imax), 15 A reference (Iref), 0.75 A minimum (Imin)
Rated voltage 380 to 415 V AC line to line, 220 to 240 V AC line to neutral
Operating voltage range 323 to 456 V AC L-L, 187 to 264 V AC L-N
Frequency 50 to 60 Hz
Start current / transition current 60 mA / 1.5 A
Accuracy Active energy class 1 (IEC/EN 62053-21), reactive energy class 2 (IEC/EN 62053-23)
Measurement Imported and exported active and reactive energy
LED pulse 1000 pulses per kWh, 30 ms
Static outputs 2, programmable at 1, 10, 100 or 1000 pulses per kWh; 10 to 30 V DC external supply, 50 mA maximum
Power consumption 20 VA maximum, 1.35 W dissipation
Terminals Fixed, 2.5 to 25 mm2 (14 to 4 AWG), 2 Nm maximum tightening torque
Housing Polyamide, DIN rail, 4 modules
Operating / storage temperature -25 to +55 degC / -25 to +70 degC
Insulation Ui 250 V, impulse withstand 6 kV
Communication / expansion / MID No built-in port / not expandable / not MID certified
Standards IEC/EN 61010-1, IEC/EN 61010-2-030, IEC/EN 50470-1; EAC, RCM

Pulse outputs and typical use

Each static output can be programmed to 1, 10, 100 or 1000 pulses per kWh, with a 100 ms pulse for the lower rates and 60 ms for 1000 pulses. This lets a PLC counter input or a pulse-based energy gateway collect consumption without a serial link. Because the meter is not MID certified, it is intended for internal sub-metering and cost allocation rather than legal billing.

Choosing the right DME meter

The DME family also includes CT-connected and communicating models, so please check the order code with us if you need Modbus, current transformer inputs or harmonic analysis, which the DMED300T2 does not provide. Lovato lists the DMXP04 panel-mounting accessory for four-module devices. For other power monitoring on the site, see the Janitza UMG 508, or browse automation accessories.

Documents and quotation

The DMED300T2 instruction manual (Lovato document I332, 2022 edition, covering DMED300T2 and DMED300T2UL) is attached to this page and covers wiring and operation. Please send the full order code, quantity and delivery location through the quotation form, and Seven Star LLC will revert with availability.

Datasheets & Documents
  • PDF Instruction manual Lovato DMED300T2 instruction manual (EN, I332, 2022) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is an Italian manufacturer of low voltage electrical devices for industrial applications, founded in 1922 in Bergamo and still family owned. Seven Star LLC, an independent supplier in Muscat, quotes Lovato Electric contactors, motor protection circuit breakers, generator controllers and power factor controllers for control panels, motor starters and stand-by power systems.

Motor control, protection and energy management

The Lovato Electric catalogue covers contactors and motor protection circuit breakers, thermal overload relays, soft starters, pushbuttons and signalling, switch disconnectors, time and monitoring relays, energy meters, power factor controllers and engine and generator controllers. Each catalogue page links its instruction sheet, leaflet and declarations of conformity.

Ordering Lovato Electric products

Send the full order code, coil or supply voltage, quantity and any approval needed for the project. With the order code, the matching version can be checked against its documentation before a quotation is issued.

Frequently Asked Questions

What current can the DMED300T2 measure directly?
Up to 80 A maximum on a direct connection, so no current transformers are required.
Does it measure reactive energy?
Yes, imported and exported active and reactive energy, with class 1 and class 2 accuracy respectively.
Does it have a communication port?
No. It offers two programmable static pulse outputs instead.
Is it MID certified?
No. Lovato lists it as not MID certified.
How wide is it?
Four DIN-rail modules.