Brand: Lovato Electric
Lovato DMED330 Three-Phase Energy Meter for CT Connection
Description
Billing-grade active energy metering on a four-module DIN-rail housing
The DMED330 is a three-phase energy meter from the Lovato Electric DMED range, listed as three-phase with and without neutral. It is connected through current transformers with a 5 A secondary (maximum current 5 A) and rated for 380-415 VAC line-to-line and 220-240 VAC line-to-neutral, with an operating range printed in the table.
Accuracy for active energy is Class 0.5s (IEC/EN 62053-22) and for reactive energy Class 2; a calibration LED pulses at 1000 pulse/kWh. The housing is 4 DIN-rail modules wide.
Technical specifications
| Parameter | Specification |
|---|---|
| Order code | DMED330 |
| Product designation | Three-phase energy meters |
| Product type designation | DMED330 |
| Type | Three-phase with and without neutral |
| DIN rail module number | 4 |
| Operational frequency (min) | 50 Hz |
| Operational frequency (max) | 60 Hz |
| Power consumption (max) | 3.5 VA |
| Power dissipation Max | 2.7 W |
| phase-phase | 380-415 VAC |
| phase-neutral | 220-240 VAC |
| phase-phase (Operating voltage range) | 323-456 VAC |
| phase-neutral (Operating voltage range) | 187-264 VAC |
| IEC maximum (Imax) | 5 A |
| IEC minimum (Imin) | 0.05 A |
| IEC rated (Iref-lb) | 5 A |
| IEC start (Ist) | 0.005 mA |
| Transition (Itr) | 0.25 A |
| Active energy | Class 0.5s (IEC/EN 62053-22) |
| Reactive energy | Class 2 (IEC/EN 62053-23) |
| LED Pulse rate | 1000 pulse/kWh |
| LED Pulse duration | 30 ms |
| Rated insulation voltage Ui IEC/EN | 250 V |
| Rated impulse withstand voltage Uimp | 6 kV |
| Operating frequency withstand voltage | 4 kV |
| Housing type | Polyamide |
| Operating temperature (min) | -25 °C |
| Operating temperature (max) | +55 °C |
| Storage temperature (min) | -25 °C |
| Storage temperature (max) | +70 °C |
| Maximum Pollution degree | 2 |
Selecting the meter
Because the meter is CT-connected, choose current transformers whose primary matches the circuit being measured, with a 5 A secondary and an accuracy class suited to the metering purpose. Direct-connection meters in the same family (DMED300 and others) cover up to 80 A without CTs.
Check whether MID certification is needed for sub-billing; the MID versions carry different order codes, so do not assume this code is a MID version unless the datasheet states it.
Applications and installation
Typical use is sub-metering of motors, chillers, HVAC plant and feeders in a distribution board, with the calibration LED (1000 pulses per kWh, 30 ms pulse duration) or a serial interface feeding a building or energy management system.
Current ratings printed in the datasheet: maximum current 5 A, minimum 0.05 A, transition current 0.25 A, starting current 0.005 mA, reference current 5 A. Operating voltage ranges are 323 to 456 VAC line-to-line and 187 to 264 VAC line-to-neutral, so the meter tolerates normal supply variation. Power consumption is 3.5 VA with a dissipation of 2.7 W, and the housing is polyamide with fixed terminals.
For a clear installation, record the current transformer ratio on the front or in the commissioning sheet, because the meter itself shows secondary-side values and the multiplier must be applied in the reading or in the supervisory software.
Documents and quotation
The Lovato Electric datasheet for DMED330 (English, exported from the manufacturer’s online catalogue) is attached and is the source of the figures above. Please confirm the system voltage, the current transformer ratio and the communication interface you need before you order, and note that the manufacturer may revise datasheet values. Browse automation accessories for alternatives. To order DMED330, submit the quotation form with your quantity and site; Seven Star LLC, an independent supplier in Muscat, handles the reply. The datasheet adds the accuracy classes, input ranges and terminal data needed to commission the instrument correctly.
Datasheets & Documents
- Datasheet Lovato Electric DMED330 datasheet (EN, catalogue export) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.
Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.
Lovato Electric at a glance
| Established | 1922, Bergamo, Italy |
|---|---|
| Headquarters | Gorle (Bergamo), Italy |
| Ownership | Private, family-run for four generations |
| Product families | Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs |
Lovato products we list
| Family | Models | Typical use |
|---|---|---|
| Contactors | BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing | Switching motors, heaters, lighting and capacitor banks |
| Motor protection and starters | SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay | Short-circuit and overload protection and direct starting of motors |
| Soft starters | ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 | Reducing starting current and mechanical shock on pumps, fans and compressors |
| Variable speed drives | VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 | Speed control of pumps, fans and conveyors to save energy |
| Power management and control | DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC | Power factor correction, mains/generator changeover and energy monitoring |
Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.
Where Lovato products are used
In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.
Ordering Lovato products: what we need
Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.
Facts checked against Lovato Electric company profile brochures, October 2026.
Browse Lovato Electric products by category: Motor Soft Starters, Automation Accessories, Controllers & Data Acquisition, PLC & I/O Cards, Circuit Breakers, Diesel Generator Spare Parts.
FAQ
Questions about the Lovato DMED330 Three-Phase Energy Meter for CT
Answers from our engineering team on installation, compatibility and integration.
01How is the DMED330 connected?
Through current transformers with a 5 A secondary, on three-phase systems with or without neutral.
02What is its active energy class?
Class 0.5s (IEC/EN 62053-22).
03How wide is it?
4 DIN-rail modules.
04What voltage does it measure?
380-415 VAC phase-to-phase, 220-240 VAC phase-to-neutral.
05Is it expandable?
The datasheet title lists it as non-expandable.


















Reviews