Lovato DMG610 Flush-Mount LCD Multimeter

Description

A three-phase-plus-neutral multimeter with RS485 output

The DMG610 is a flush-mount LCD multimeter, expandable with EXP modules from the Lovato Electric DMG range for three-phase + neutral systems. It measures with true RMS inputs, connects to current transformers with 1 A or 5 A secondaries, and shows readings on a backlit LCD.

The auxiliary supply covers 100-440 VAC and 120-250 VDC. Voltage inputs are rated 600 VAC line-to-line and 300 VAC line-to-neutral. Active energy accuracy is Class 1 (IEC/EN 62053-21).

Technical specifications

Parameter Specification
Order code DMG610
Product designation Flush-mount LCD multimeters. expandable
Product type designation DMG610
Type Three-phase + neutral
Auxiliary rated supply voltage AC 100-440 VAC
Auxiliary rated supply voltage DC 120-250 VDC
AC (min) 90 VAC
AC (max) 484 VAC
DC (min) 93.5 VDC
DC (max) 300 VDC
Operational frequency (min) 45 Hz
Operational frequency (max) 66 Hz
Power consumption (max) 9.5 VA
Power dissipation Max 3.5 W
phase-phase 600 VAC
phase-neutral 300 VAC
phase-phase (Operating voltage range) 50-720 VAC
phase-neutral (Operating voltage range) 30-360 VAC
Voltage inputs operational frequency (min) 45 Hz
Voltage inputs operational frequency (max) 66 Hz
Voltage inputs measurement method True RMS
Connection method Single. two. three-phase with or without neutral. balanced three-phase system
Rated current (Ie) 1A/5A
Measurement range 0.025-6A
Overload capacity +20% Ie by external CT with 5A secondary
Overload peak 50A for 1s
VLN voltage ±0.5%
VLL voltage ±0.5%
Current ±0.5%
Frequency ±0.05%
Active power ±0.5%
Active energy Class 1 (IEC/EN 62053-21)
Reactive energy Class 2 (IEC/EN 62053-23)
Baud rate Programmable 1200-115200 bps
Rated insulation voltage Ui IEC/EN 600 V
Rated impulse withstand voltage Uimp 9.5 kV
Operating frequency withstand voltage 5.2 kV
Harmonic analysis 15th order
Type of communication port RS485
Housing type Polyamide
Terminals type Removable
Operating temperature (min) -20 °C
Operating temperature (max) +60 °C
Storage temperature (min) -30 °C
Storage temperature (max) +80 °C
Maximum Pollution degree 2
Protection degree IP54 on front – IP20 terminals

What to confirm before ordering

Pick between flush-mount (panel door) and modular (DIN rail) formats first, then check the supply range, the communication port and whether expansion modules are needed.

Check the current transformer ratio and set it in the meter during commissioning.

Where it fits

Typical installations are motor control centres, generator panels and incomer cubicles, where operators need current, voltage, power and energy on the front of the panel and the same values on a Modbus network.

Housing: Polyamide.

For panel design and commissioning, the practical figures to keep at hand are: rated current (Ie) 1A/5A; measurement range 0.025-6A; overload capacity +20% Ie by external CT with 5A secondary; overload peak 50A for 1s; VLN voltage ±0.5%; VLL voltage ±0.5%; current ±0.5%; frequency ±0.05%; active power ±0.5%; reactive energy Class 2 (IEC/EN 62053-23); baud rate Programmable 1200-115200 bps; housing type Polyamide; terminals type Removable; protection degree IP54 on front – IP20 terminals. These come straight from the datasheet and are repeated here so that the key installation limits are visible without opening the PDF.

Documents and quotation

A copy of the manufacturer’s datasheet for DMG610, exported from the Lovato Electric catalogue in English, is attached to this page; every figure in the table comes from it. Make sure of the system voltage, the current transformer ratio and the communication interface you need before placing an order, since the published values can change. Browse automation accessories for alternatives. To order DMG610, submit the quotation form with your quantity and site; Seven Star LLC, an independent supplier in Muscat, handles the reply. The datasheet adds the accuracy classes, input ranges and terminal data needed to commission the instrument correctly.

Datasheets & Documents
  • PDF Datasheet Lovato Electric DMG610 datasheet (EN, catalogue export) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.

Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.

Lovato Electric at a glance

Established 1922, Bergamo, Italy
Headquarters Gorle (Bergamo), Italy
Ownership Private, family-run for four generations
Product families Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs

Lovato products we list

Family Models Typical use
Contactors BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing Switching motors, heaters, lighting and capacitor banks
Motor protection and starters SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay Short-circuit and overload protection and direct starting of motors
Soft starters ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 Reducing starting current and mechanical shock on pumps, fans and compressors
Variable speed drives VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 Speed control of pumps, fans and conveyors to save energy
Power management and control DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC Power factor correction, mains/generator changeover and energy monitoring

Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.

Where Lovato products are used

In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.

Ordering Lovato products: what we need

Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.

Facts checked against Lovato Electric company profile brochures, October 2026.

FAQ

Questions about the Lovato DMG610 Flush-Mount LCD Multimeter

Answers from our engineering team on installation, compatibility and integration.

01What does the DMG610 measure?
Three-phase voltages, currents, power, energy and related values, as listed in the datasheet.
02What supply does it need?
100-440 VAC or 120-250 VDC.
03What is its energy accuracy?
Active energy Class 1 (IEC/EN 62053-21).
04Which communication port?
RS485.
05Is it expandable?
Flush-mount LCD multimeters. expandable.