Brand:

Hochiki CHQ-DIM2/DIN(SCI) Dual Input Module, DIN Rail

Description

Overview

Door contacts, sprinkler flow switches, valve tamper switches and plant status relays all speak the same language: a volt free contact that is either open or closed. The Hochiki CHQ-DIM2/DIN(SCI) is the DIN rail interface that carries two such contacts back to an ESP analogue addressable fire alarm panel using only a single loop address. Seven Star LLC is an independent supplier serving Oman and the GCC. It is loop powered, so no separate supply cable runs to the module, and it includes an integral short-circuit isolator that protects the rest of the loop if the module wiring fails.

Two independent inputs on one address

Each of the two inputs can be configured to watch either normally open or normally closed contacts, which means a door held shut by a magnet and a flow switch that closes on water movement can sit on the same module. The datasheet gives the input line resistance thresholds: an ON state below 50 ohms and an OFF state above 100 kilohms. The module draws a typical 280 microamps in quiescent state and about 22 mA plus or minus 20 percent while polling, rising by 4.3 mA when both inputs are active.

Technical data for Hochiki CHQ-DIM2/DIN(SCI)

Item Datasheet value
Ordering codes CHQ-DIM2(SCI) enclosed module; CHQ-DIM2/DIN(SCI) DIN rail module
Operating voltage 17 to 41 V DC
Quiescent current 280 microamps typical
Polling current 22 mA plus or minus 20 percent; 4.3 mA with both inputs active
Current in short circuit 8 mA
Maximum short-circuit current 1 A
Input thresholds ON below 50 ohms, OFF above 100 kilohms
Operating temperature minus 10 to plus 50 degrees C
Storage temperature minus 30 to plus 60 degrees C
Humidity up to 95 percent RH non-condensing at 40 degrees C
DIN module weight 113 g
DIN module dimensions length 119 mm, width 108 mm, depth 24 mm
Material Green ABS for the DIN module
Approvals LPCB

How the Hochiki CHQ-DIM2/DIN(SCI) differs from the enclosed CHQ-DIM2(SCI)

The two codes share the same electronics and the same ESP behaviour. The difference is in the mounting. The enclosed CHQ-DIM2(SCI) comes in a white ABS housing with a semi-opaque black lid that measures 157 by 127 by 35 mm and weighs 327 g, and when used with the CHQ-BACKBOX it reaches 79 mm in depth, weighs 235 g more and raises the ingress protection to IP65. The DIN version weighs only 113 g and measures 119 by 108 by 24 mm, so several can be packed into a cabinet on a standard rail. It has no lid of its own, so it must live inside a panel, marshalling cabinet or enclosure that gives the protection needed for the environment.

Applications in Oman and GCC facilities

Marshalling cabinets in plant buildings, pump stations, utility rooms and tank farm control houses often need many monitored contacts gathered into the fire system. Fire pump controllers, deluge valve position switches, sprinkler flow indicators, extraction fan status contacts and emergency door release contacts are typical sources. Mounting the DIN module inside the cabinet next to the equipment keeps field wiring short and puts the module in a controlled, dust-free place, which suits hot, dusty sites.

Selection and wiring guidance

Keep the contact wiring short and use the cable type required by the project, remembering that the thresholds of 50 ohms and 100 kilohms include the line resistance. Choose normally open or normally closed monitoring according to how the field device fails, and document the choice per input in the loop schedule. Confirm that the control panel supports the module type and supply the address with the usual programming procedure. The integral isolator means that a short on the loop side is cut off at the module, but the input wiring itself is not isolated, so protect it as the design requires.

Why a loop-powered input module saves cable

Before addressable systems, every monitored contact needed its own cable home to the panel or to a zone card. With a loop-powered module, the same two-core loop that feeds the detectors also feeds the module, and the status of both inputs returns as digital messages. The result is fewer cable runs, a shorter installation programme and a clear event log with an address for each contact rather than a zone number for many. In a plant building with a dozen valve switches and door contacts, six of these DIN modules in one cabinet replace a bundle of home-run cables. Because each module carries its own isolator, a damaged cable in the cabinet cannot drag the whole loop down, which is valuable in industrial areas where maintenance crews work around the wiring.

Keep a margin in the loop current budget, since each module adds its polling draw, and keep the total number of addresses inside the limits given for your panel.

Installation and commissioning

Clip the module on the rail, wire the loop in and out terminals first and then the inputs, set the address, and apply the loop. Test each input by operating the contact and watching the panel event, and test the open and short circuit behaviour that your design requires. Label both input numbers inside the cabinet and in the as-built drawings.

Maintenance

At each service, operate every monitored contact in turn, check terminal tightness and look for dust, moisture or heat marks inside the cabinet. Record any change in polling current if your panel exposes it.

Ordering notes for Hochiki CHQ-DIM2/DIN(SCI)

Quote the DIN code exactly, because the enclosed module and the DIN module are separate order codes. If a protective back box is wanted for the enclosed version, quote the CHQ-BACKBOX separately.

Related items you may also need: Hochiki CDX FIREbeam Conex Conventional Beam Smoke Detector | Hochiki ESP FIREbeam Xtra Addressable Beam Smoke Detector | Hochiki ACD-EN Intelligent Multi Sensor | All Hochiki products.

Documents and quotation

The manufacturer datasheet that covers the Hochiki CHQ-DIM2/DIN(SCI) and the enclosed version is attached to this page. Send your RFQ with the part number, quantity and delivery location in Oman or the GCC.

Datasheets & Documents
  • PDF Datasheet Hochiki CHQ-DIM2/DIN(SCI) Dual Input Module, DIN Rail Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Hochiki is a Japanese fire detection company, established in Tokyo in 1918 as Japan's first fire alarm manufacturer, with leading insurance companies among its founders. It makes smoke and heat detectors, beam detectors, addressable fire alarm systems and emergency lighting. Hochiki America has operated in the US since 1972.

Seven Star LLC is an independent supplier in Muscat. We list Hochiki detectors for fire alarm contractors in Oman and the GCC.

Hochiki company profile

Founded 1918, Tokyo, Japan
Founders Members of Japan's insurance industry
US operations Since 1972
Systems Conventional and addressable fire detection
Product families ESP intelligent detectors and multi-sensors, FIREbeam beam detectors, CDX conventional detectors, control panels

Milestones

  • 1918: Hochiki is founded in Tokyo.
  • 1972: Hochiki America begins US operations.

Hochiki product series

The ACD-EN is an intelligent multi sensor detector for Hochiki addressable systems.

Beam smoke detectors include the CDX FIREbeam Conex and CDX FIREbeam Xtra conventional detectors and the ESP FIREbeam Xtra addressable detector.

Multi sensor detectors combine smoke and heat sensing to detect different fire types and reduce false alarms. Beam detectors send an infrared beam across an open space and alarm when smoke reduces the signal, covering large areas with fewer devices.

Detectors must match the panel protocol and be installed and tested to the local fire code.

Where Hochiki detectors are used

Offices, hotels, schools and hospitals, and large open spaces such as warehouses, atriums and halls where beam detectors cover long distances.

Hochiki products we list

Family Examples
Fire & Gas Detectors ACD-EN Intelligent Multi Sensor, CDX FIREbeam Conex Conventional Beam Smo…, ESP FIREbeam Xtra Addressable Beam Smoke…

Ordering Hochiki detectors: what we need

Send the part number, protocol (conventional or ESP addressable), the beam range and the panel in use.

Facts checked against IFSEC Global centenary coverage and Hochiki company profiles, October 2026.

FAQ

Questions about the Hochiki CHQ-DIM2/DIN(SCI) Dual Input Module, DIN

Answers from our engineering team on installation, compatibility and integration.

01How many inputs does the Hochiki CHQ-DIM2/DIN(SCI) have?
It has two independent inputs for volt free contacts, each configurable for normally open or normally closed monitoring, on a single loop address.
02Does the Hochiki CHQ-DIM2/DIN(SCI) include a short-circuit isolator?
Yes. The datasheet states that both the enclosed and DIN versions feature an integral short-circuit isolator, with 8 mA in short circuit.
03What are the size and weight of the Hochiki CHQ-DIM2/DIN(SCI)?
The DIN module weighs 113 g and measures 119 mm long, 108 mm wide and 24 mm deep, in green ABS.
04What input thresholds does the Hochiki CHQ-DIM2/DIN(SCI) use?
The input line resistance ON threshold is below 50 ohms and the OFF threshold is above 100 kilohms.
05How does the DIN version differ from the CHQ-DIM2(SCI)?
The electronics are the same, but the DIN version is a lighter rail-mounted module of 113 g without lid, while the enclosed one is 327 g in a lidded housing.