Honeywell PVL6436AS Spyder Lon VAV Controller 6 UI 4 DI 6 DO

Description

PVL6436AS: the high-capacity Spyder Lon VAV controller with actuator

Honeywell PVL6436AS is the model shown in the photograph on the first page of the Spyder Lon product data. It combines a programmable LONMARK controller with 6 universal inputs, 4 digital inputs, 3 analog outputs and 6 Triac outputs, a microbridge velocity pressure sensor and a hard-wired 44 lb-in Series 60 floating actuator.

Because of that point count it is chosen for VAV boxes that carry more than a damper: fan-powered boxes with a fan relay, multi-stage electric reheat, a hot-water valve with feedback and several alarm or status contacts. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Capacity compared with the smaller VAV models

Model UI DI AO DO Sensor Actuator
PVL0000AS 0 0 0 0 Yes Yes
PVL4022AS 4 0 2 2 Yes Yes
PVL6436AS 6 4 3 6 Yes Yes
PVL6438NS 6 4 3 8 Yes No

The PVL6436AS row is the one with the highest I/O count among models that include the actuator. Choose PVL6438NS instead only when the damper is driven by a different actuator and you need 8 Triac outputs.

PVL6436AS electrical and mechanical data

Parameter Value
Model PVL6436AS
Points 6 UI, 4 DI, 3 AO, 6 DO
Supply 20 to 30 Vac, 50/60 Hz; 100 VA limit with all loads
Controller plus actuator 9 VA maximum
External sensor supply 20 Vdc plus or minus 10 percent, 75 mA maximum
Ambient 32 to 122 F (0 to 50 C), 5 to 95 percent RH
Actuator torque 44 lb-in (5 Nm), Series 60 floating
Actuator stroke 95 degrees plus or minus 3, CW or CCW opening dampers
Run time 90 seconds for 90 degrees at 60 Hz
Damper shaft 3/8 to 1/2 in (10 to 13 mm) square or round, minimum length 1-9/16 in (40 mm)
Actuator ambient minus 4 to 140 F (minus 20 to 60 C)
Velocity pressure sensor 0 to 1.5 in. H2O (0 to 374 Pa), microbridge
Panel mounting Fig. 5 layout, controller and actuator together

How PVL6436AS differs from other Spyder Lon variants

Its two nearest relatives are PVL4022AS and PVL6438NS. Relative to PVL4022AS it adds two universal inputs, four digital inputs, one analog output and four Triac outputs. Relative to PVL6438NS it has the same 6 UI, 4 DI, 3 AO but 6 DO instead of 8, and it carries the actuator, which the NS lacks. Its larger body means it is panel mounted using the Fig. 5 hole pattern and cannot be snapped onto a DIN rail.

Field installation sequence

The sequence below is condensed from the manual and is worth printing for the installer. 1. Measure the damper: shaft 10 to 13 mm, shaft length at least 40 mm, direction of opening and angle (45, 60 or 90 degrees). 2. Set the end limits. 3. Declutch and place the adapter. 4. Tighten clamp bolts. 5. Connect the pickup tubes plus and minus. 6. Fix the controller to the panel using four screws. 7. Wire power, bus and I/O. 8. Download and check out. Follow the CW or CCW cases in the manual; special care is required when the damper opens counter-clockwise because the controller must be set to Reverse to Open.

Sizing the supply

Do not undersize the transformer. Honeywell warns that a controller must see at least 20 Vac at its terminals, that line loss above two volts is not acceptable in a design, and that a 40 VA transformer feeding a 37 VA load over 200 ft of 18 AWG wire would deliver only 18.9 V, which is too low. Heavier 14 AWG wire cuts that loss to about 1.58 V. Honeywell gives a worked example in which a PVL controller with actuator (9 VA), an R8242A contactor (21 VA inrush) and an M6410A steam valve (0.7 VA) totals 30.7 VA, so a single 100 VA AT92A transformer could feed three such sets. For PVL6436AS the same method applies: add the 9 VA to the load of every device the controller powers and keep the line-loss at or under two volts.

Typical sites

The mix of inputs suits boxes where one controller must close several small loops. Examples are a parallel fan-powered box with a fan status contact, a discharge sensor on a universal input, two reheat stages on Triacs and a modulating valve on an analog output, or a laboratory supply box that also watches a sash switch. Large commercial towers, airport concourses, hospitals and data halls in the Gulf, where each VAV box needs fan status, discharge-air temperature, a reheat valve and an occupancy sensor input at the same time.

Care and replacement

Replace the complete controller and actuator assembly by removing power, disconnecting both pickup tubes, pulling the terminal blocks with wiring attached, loosening the actuator clamp bolts and pulling the assembly straight off the shaft. Reverse the order to fit the new PVL6436AS, reseat each terminal block on its alignment pins pressing straight down, restore power and run the Checkout procedure.

Keep the end-limit screw torque at 3.0 to 3.5 Nm (26.5 to 31 lb-in) and the centering clamp at 8 to 10 Nm; the manual specifies a Phillips number 2 screwdriver for the end limits and an 8 mm wrench for the clamp. After startup, leave the damper in a known state and note the direction setting in the job file so later technicians do not reverse it by accident. A wrongly set direction makes the box close when the program asks it to open, and the airflow reading then tracks the wrong way during commissioning.

Documents and quotation

Use the Spyder Lon product data, form 63-2685, as the datasheet for PVL6436AS. For an RFQ send the part number PVL6436AS, quantity and delivery location in Oman or the GCC.

Ordering Checklist for the Honeywell PVL6436AS

Before you ask for a quotation for the Honeywell PVL6436AS, check the full order code on the nameplate of the unit you are replacing, the supply voltage, and the process or signal ranges your system expects. If this is an upgrade rather than a like-for-like swap, tell us the existing make and model so that mounting, wiring and connection details can be checked against the controllers & data acquisition already installed. For multi-unit orders, list the quantity per site and the delivery location in Oman or the wider GCC, so packing, paperwork and lead time can be confirmed in a single quotation.

Other Models in the Spyder Lon VAV Range

Seven Star LLC supplies models from the Spyder Lon VAV range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Honeywell PVL4022AS Spyder Lon VAV Controller with ActuatorControllers & Data AcquisitionView details
Honeywell PVL6436AS Spyder Lon VAV Controller 6 UI 4 DI 6 DOControllers & Data AcquisitionYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Honeywell PVL6436AS Spyder Lon VAV Controller 6 UI 4 DI 6 DO Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).

Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.

Honeywell company profile

Origins 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927
Brands in our range Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance
Gent Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005
Elster Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015

Milestones

  • 1885: The Butz thermostat business starts in Minneapolis.
  • 1927: It merges with Mark Honeywell's company.
  • 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
  • 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.

Honeywell products we list

Family Models Typical use
Fixed gas detectors Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID Flammable, toxic and VOC gas detection in process areas
Sensors, flame detection and control SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel Replacement sensors, fire detection and gas detection control panels
Transmitters and flow SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis Process pressure and mass flow measurement
Elster gas metering Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display Gas meters, volume correction and fiscal flow computing
Gent fire alarm systems Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell Addressable and conventional fire alarm systems in buildings and plants
Chadwick-Helmuth rotor track and balance 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor Helicopter rotor track and balance and propeller balancing

Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.

Where Honeywell products are used

In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.

Ordering Honeywell products: what we need

Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.

Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.

FAQ

Questions about the Honeywell PVL6436AS Spyder Lon VAV Controller 6 UI

Answers from our engineering team on installation, compatibility and integration.

01What I/O does the Honeywell PVL6436AS provide?
Six universal inputs, four digital inputs, three analog outputs and six Triac digital outputs, plus a flow sensor and actuator.
02What torque does the PVL6436AS actuator deliver?
The Series 60 floating actuator is rated at 44 lb-in (5 Nm), with a 90 second run time for 90 degrees at 60 Hz.
03Why is PVL6436AS drawn in the datasheet photo?
The first page photo of the Spyder Lon product data is of the model PVL6436AS, which includes the actuator.
04What is the maximum draw of PVL6436AS?
The controller and actuator together draw 9 VA maximum; the total with all connected loads is limited to 100 VA.
05How do I set PVL6436AS for a counter-clockwise damper?
The actuator ships set to open clockwise, so the program must be changed to Reverse to Open for dampers that open counter-clockwise.