Brand:

Honeywell SLXL-ESMGXX Searchline Excel Edge Long Range M25

Description

Honeywell SLXL-ESMGXX is the Searchline Excel Edge long-range open path flammable gas detector in stainless steel with M25 cable entries and global approvals. It is a transmitter and receiver pair that creates an invisible infrared beam of 60 to 330 metres, so that a hydrocarbon cloud crossing the beam is detected anywhere along its length. The datasheet describes it as built for perimeter and fence-line monitoring in harsh conditions, with a long range that exceeds typical open path products.

How to read the SLXL-ESMGXX part number

Field Code Meaning
Field Code Meaning
Family SLXL Searchline Excel long range
Version E Long-range perimeter monitoring open path flammable gas detector (Edge)
Material S Stainless steel
Entries M M25
Approvals G Global: ATEX, IECEx, UL, Marine, INMETRO, CCCF
Reserved XX Reserved field; the datasheet lists X as kit, D demo, R receiver, T transmitter

The listed description reads: Searchline Excel Edge, Long Range, stainless steel with M25 entries, including a small stainless steel mount and bracket and a plastic sunshade.

SLXL-ESMGXX datasheet specification

Parameter Value
Gas Hydrocarbons: methane, ethane, propane, butane, pentane, hexane, ethylene, propylene
Range 0 to 5 LEL.m
Recommended alarms Low 1 LEL.m, high 3 LEL.m; minimum 0.5 LEL.m
Path length 60 m to 330 m (196 ft to 1082 ft)
Response T90 less than 3 seconds
Analog output 4 to 20 mA; 1 mA fault; 2 mA inhibit; 3 mA warning; 21 mA over range
Operating temperature -55 to +75 degrees C
Supply 24 VDC nominal (18 to 32 VDC)
Power, transmitter 3.8 W above +30 degrees C; 5.6 W from +30 to -30 degrees C; 11.8 W below -30 degrees C
Power, receiver 3.0 W / 4.8 W / 7.4 W over the same bands
Outputs 4 to 20 mA with HART, fault relay, alarm 1 and alarm 2 relays, Modbus, Bluetooth
Relay rating 32 V, 2 A resistive
Humidity 0 to 99 percent RH, non-condensing
Repeatability +/-0.4 LEL.m
Warm-up Under 5 minutes operational, under 1 hour fully stabilised
Weight Receiver 6.1 kg, transmitter 6.0 kg
Dimensions 103 mm diameter x 325 x 180 mm
Ingress protection IP66/67, Type 4X
Safety SIL 2 certified by TUV SUD to EN 61508
Ex marking IECEx Ex db ia IIC T4 Gb; Ex db eb ia IIC T4 Gb; Ex tb IIIC 100 degrees C Db

Why the Edge differs from other open path detectors

Compared with the Searchline Excel of earlier generations, which covers path lengths of 5 to 200 metres in three ranges, the Edge covers 60 to 330 metres in a single configuration, and it runs from -55 to +75 degrees C instead of -40 to +65. It adds a high-visibility LED halo ring for status, automatic event logging, Bluetooth communication for non-intrusive set-up with an intrinsically safe phone, and an alignment scope. The Honeywell datasheet claims that it sees through thick fog better than other open path detectors, whether NDIR or laser based, and continues to monitor in low visibility after others have stopped.

How SLXL-ESMGXX differs from SLXL-ESNGXX

The only change is the cable entry thread: SLXL-ESMGXX uses M25, SLXL-ESNGXX uses three-quarter inch NPT. Everything else, including range, approvals and the accessory bundle of mount, bracket and sunshade, is shared. Choose M25 for sites built to IEC and ATEX cable gland practice, which includes most Gulf oil and gas installations.

Applications of SLXL-ESMGXX

Fence-line monitoring of refineries, tank farms, LNG and LPG storage, gas receiving terminals, compressor stations, pipeline pump stations and offshore deck edges. Because the beam integrates gas along its path, a transmitter and receiver 300 metres apart can replace a row of point detectors and is less likely to miss a drifting cloud. Salt mist and sulphuric atmosphere resistance is quoted at 15 to 60 minutes exposure.

The SLXL-ESMGXX is aimed at a different job from an ordinary point detector. A point detector tells you the gas concentration at one spot, while an open path detector reports the gas along a line in LEL.m, the product of concentration and path length. A reading of 1 LEL.m can therefore mean a 100 percent LEL cloud one metre thick or a 10 percent LEL cloud ten metres thick, and the Honeywell recommended alarms of 1 LEL.m low and 3 LEL.m high, with a minimum of 0.5 LEL.m, are set in those units. Operators who are used to point detector percentages need a short briefing before commissioning the SLXL-ESMGXX.

The datasheet also lists performance and approval standards that matter for procurement: ATEX, IECEx, cULus, FM, INMETRO and CCCF hazardous-area marks, SIL 2, and ANSI, FM, IEC and EN 60079-29-4 performance approval, with DNV approval for methane and propane and FM performance approval for several gases. Core approvals include IEC, EN, UL and CSA 61010 electrical safety and EN 50270 electromagnetic compatibility, with the Radio Equipment Directive covering the Bluetooth link.

Installation and alignment

Mount the transmitter and receiver on the supplied Universal Mount, with a bracket weighing 3.1 kg in stainless steel, facing each other along the beam. The Searchline Excel Edge uses an alignment scope, listed as 2017B0299, and the Honeywell Fixed Platform App on an intrinsically safe Android device. Dimensions are 103 mm diameter by 325 by 180 mm per unit. Spares include the universal mounting bracket plate 2331B1100, standard plastic sunshade 2017B0112 and terminal block set 2331B1150.

Commissioning and maintenance

Allow the unit under 5 minutes to become operational and under 1 hour to stabilise fully. Functional test filters 2017B0218 and an extender 2017D0226 allow a gas check without a gas release, and a gassing test cell 2017B0185 is available. A large adjustable mounting bracket 2331B1020 and stainless steel sunshade 2017B0113 are other accessories. The internal TLH-2450 battery cell has a 10-year life and is replaced only by the manufacturer’s service.

When ordering the SLXL-ESMGXX, state the planned path length between 60 and 330 metres, because very short paths are outside the range, and ask whether a transmitter and receiver are wanted as a pair. The reserved field letters in the code, X for kit, D for demo, R for receiver and T for transmitter, appear in the datasheet’s code key; the listed description of the SLXL-ESMGXX includes the mount, bracket and sunshade, and we confirm the exact scope of supply on each quotation.

Documents and quotation

Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. The datasheet can accompany the quotation. Send an RFQ for SLXL-ESMGXX, the quantity, the path length and the delivery location.

Datasheets & Documents
  • PDF Datasheet Searchline Excel Edge Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).

Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.

Honeywell company profile

Origins 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927
Brands in our range Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance
Gent Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005
Elster Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015

Milestones

  • 1885: The Butz thermostat business starts in Minneapolis.
  • 1927: It merges with Mark Honeywell's company.
  • 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
  • 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.

Honeywell products we list

Family Models Typical use
Fixed gas detectors Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID Flammable, toxic and VOC gas detection in process areas
Sensors, flame detection and control SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel Replacement sensors, fire detection and gas detection control panels
Transmitters and flow SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis Process pressure and mass flow measurement
Elster gas metering Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display Gas meters, volume correction and fiscal flow computing
Gent fire alarm systems Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell Addressable and conventional fire alarm systems in buildings and plants
Chadwick-Helmuth rotor track and balance 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor Helicopter rotor track and balance and propeller balancing

Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.

Where Honeywell products are used

In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.

Ordering Honeywell products: what we need

Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.

Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.

FAQ

Questions about the Honeywell SLXL-ESMGXX Searchline Excel Edge Long

Answers from our engineering team on installation, compatibility and integration.

01What does Honeywell SLXL-ESMGXX detect?
It is a long-range open path infrared detector for hydrocarbon gases such as methane, ethane, propane, butane, pentane, hexane, ethylene and propylene over 0 to 5 LEL.m.
02What path length does SLXL-ESMGXX cover?
The datasheet gives a path length of 60 m to 330 m (196 ft to 1082 ft) with response T90 under 3 seconds.
03What does the M in SLXL-ESMGXX mean?
M indicates M25 cable entries, as opposed to N for three-quarter inch NPT in SLXL-ESNGXX. S is stainless steel and G is global approvals.
04What outputs does SLXL-ESMGXX provide?
4 to 20 mA with HART, fault relay, alarm 1 and alarm 2 relays, Modbus and Bluetooth, with relays rated 32 V and 2 A resistive.
05What temperature range can SLXL-ESMGXX operate in?
Honeywell specifies -55 to +75 degrees C, with IP66/67 and resistance to salt mist and sulphuric atmosphere.