Brand:

Yokogawa MLX-A21-14/KU21/ENG/SST Loop Indicator

Description

Yokogawa MLX-A21-14/KU21/ENG/SST loop-powered process indicator overview

The Yokogawa MLX-A21-14/KU21/ENG/SST is a field-mounted, loop-powered digital indicator that shows the value of a 4 to 20 mA signal at the point where operators actually work. It takes its operating power from the current loop itself, so no separate supply is needed, and it can be wired in series with any two-wire transmitter. The Yokogawa MLX-A21-14/KU21/ENG/SST configuration combines an aluminum housing, a vertical 2 inch pipe or wall mount, M20 cable entries and the ATEX explosion-protection package, with factory-set scaling and a stainless steel tag screwed to the housing.

Because the MLX is fully configurable from its front panel, the same hardware serves flow, pressure, level and temperature loops. Engineering units, decimal point and range are set locally, which suits maintenance teams that need to re-range a loop without a communicator. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Part number MLX-A21-14/KU21/ENG/SST decoded

Yokogawa builds the MLX model code from fixed positions, and each position of MLX-A21-14/KU21/ENG/SST has a clear meaning in the general specification.

Code element Meaning
MLX-A Loop-powered indicator, input 4 to 20 mA DC
2 2 inch vertical pipe mounting (or wall mount)
1 Cast aluminum alloy housing
-1 Standard communication code
4 ISO M20 x 1.5 female, two electrical connections and one 316 stainless steel blind plug
/KU21 ATEX approval package: intrinsically safe, flameproof, dust and non-incendive markings
/ENG Factory calibration of the range and scale in engineering units
/SST Stainless steel tag plate screwed to the housing

When ordering a replacement or a matching unit, the range, scale and tag text supplied with the original MLX-A21-14/KU21/ENG/SST should be repeated so that the new indicator arrives configured the same way.

Key features of the MLX-A21-14/KU21/ENG/SST

  • Six 7-segment digits, six 14-segment alphanumeric characters and a 20-segment bar graph on one LCD.
  • Zero and span can be set anywhere between plus and minus 999999, with user-selectable engineering units.
  • Root extraction for square root, 3/2 root and 5/2 root signals, handy for differential pressure flow loops.
  • Built-in loop protection that removes the indicator from the circuit if the MLX itself fails, so the loop stays intact.
  • Self-diagnostics at power-up and during operation, with a 12 second turn-on time and a 1 second display update.
  • Four touch switches and one push button give full configuration without opening the housing.
  • NEMA 4X and IP67 enclosure with a 316 stainless steel name plate and tag.

These traits make the MLX-A21-14/KU21/ENG/SST a low-effort way to add a local readout to a transmitter that otherwise has no display, or to give a second view of the same loop at a different location.

MLX-A21-14/KU21/ENG/SST technical specifications

Parameter Value
Input 4 to 20 mA DC, 2-wire
Voltage drop 3.5 V at 20 mA
Operating current 3.6 mA to 28 mA
Over-range 200 mA without damage
Accuracy Plus or minus 0.05 percent of full scale plus 1 digit
Linearity / hysteresis / repeatability 0.03 percent each
Isolation Input, output and ground isolated to 500 V DC
Ambient temperature -40 to +80 C (-40 to 176 F)
Ambient humidity 0 to 100 %RH at 23 C
Vibration / shock 3 G at 10 to 150 Hz / 50 G
Housing Low-copper cast aluminum, polyurethane baked finish, deep sea moss green
Name plate and tag 316 stainless steel
Degree of protection NEMA 4X, IP67
Mounting Nominal 2 inch (50 mm) pipe or surface, horizontal or vertical
Weight 1.25 kg without bracket; add 0.8 kg for the bracket
EMC EN 61326-1 Class A, Table 2 (industrial locations)

The datasheet lists these as the standard specifications of the MLX family, and they apply to the MLX-A21-14/KU21/ENG/SST unless the ordering code says otherwise.

Hazardous-area approval of the MLX-A21-14/KU21/ENG/SST

The /KU21 code on MLX-A21-14/KU21/ENG/SST carries the ATEX package described in the Yokogawa general specification. The markings are II 1G Ex ia IIC T4 Ga for the intrinsically safe loop connection, II 2G Ex d IIC T4 Gb for the flameproof enclosure, II 2D Ex tb IIIC T135 Db for combustible dust and II 3G Ex nA IIC T4 Gc for non-sparking use. The enclosure protection is IP66 and IP67, the temperature class is T4 and the ambient range is -40 to 80 C.

For intrinsically safe use the entity parameters are Ui 28 V, Ii 115 mA, Pi 0.65 W, with Ci and Li equal to zero. For the non-incendive marking the parameters are Ui 30 V, Ii 150 mA and Pi 0.85 W. Always verify that the installed loop and barrier match these figures and the certificate before commissioning.

Applications in Oman and GCC plants

A loop indicator such as the MLX-A21-14/KU21/ENG/SST is common wherever a transmitter sits high on a pipe rack or inside a hazardous area and the operator still needs a number. In oil and gas facilities it shows wellhead pressure, separator level and metered flow beside the transmitter. In utilities and water treatment it indicates pump discharge pressure, chemical dosing flow and tank level. In manufacturing and petrochemical units it supports local checks during start-up, calibration and shutdown. The M20 cable entry and ATEX marking match the metric conduit practice and Ex requirements common across the Sultanate and the wider GCC.

Selection and compatibility notes for MLX-A21-14/KU21/ENG/SST

Before choosing the MLX-A21-14/KU21/ENG/SST, confirm that the loop can tolerate an additional 3.5 V drop at 20 mA, and that the transmitter and power supply still deliver the minimum terminal voltage. Check that the signal really is 4 to 20 mA; the MLX-A input code is for that signal only. Decide the mounting position early: this version has the vertical 2 inch pipe bracket, and the horizontal pipe variant is a different code. The housing code 1 is cast aluminum, while stainless steel housing availability must be confirmed with the manufacturer. If the process variable is non-linear and based on a root function, set the root extraction in the menu rather than adding a separate converter.

Where the original MLX-A21-14/KU21/ENG/SST is being replaced, match the ATEX package, the cable entry thread and the scaling. A unit with a different approval code is not a like-for-like swap.

Typical companions to the MLX-A21-14/KU21/ENG/SST include Yokogawa pressure and differential pressure transmitters, stainless steel tag plates and mounting brackets. When requesting a quotation, state the housing, mounting, cable entry, approval code, calibrated range, engineering units and tag number so the match is exact.

Installation and commissioning of the MLX-A21-14/KU21/ENG/SST

  • Mount the bracket on a 2 inch pipe or a flat surface and fit the indicator, keeping the display readable from the normal walking route.
  • Wire the indicator in series with the loop using twisted shielded pair, observing polarity on terminals J1 and J2, and leave the shorting bar until the loop is ready.
  • Use certified M20 glands and keep the blind plug fitted in the unused entry to preserve the enclosure rating.
  • Power the loop, wait for the 12 second start-up routine, then set zero, span, decimal point and units from the front panel if the factory scaling needs adjusting.
  • Compare the displayed value against the transmitter or a calibrator at several points of the range and record the result.

Maintenance and troubleshooting

The MLX-A21-14/KU21/ENG/SST has no consumables. Keep the cover threads clean and lightly greased, check the cover seal at each shutdown, and make sure the cable glands remain tight. If the display is blank, measure the loop current: the operating range of the indicator starts at 3.6 mA, and a loop that falls below that value will blank the screen. A reading that disagrees with the transmitter usually points to scaling, root extraction or a loop calibration issue rather than a faulty indicator. Because the built-in loop protection takes a failed MLX out of the circuit, a dark display does not stop the control loop.

Documents and quotation

The Yokogawa datasheet for the MLX-A21-14/KU21/ENG/SST family (General Specifications GS 60A02S01-01E-A) is available on request and on this page. To receive availability and lead time, send an RFQ with the part number MLX-A21-14/KU21/ENG/SST, the quantity and any scaling or tag text. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Datasheets & Documents
  • PDF Datasheet Yokogawa MLX-A21-14/KU21/ENG/SST Loop Indicator Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.

Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.

Yokogawa at a glance

Established 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki
Milestones Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986
Headquarters Tokyo, Japan
Product families Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers

Yokogawa products we list

Family Models Typical use
Pressure and DP transmitters EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable Pressure, level and DP flow measurement in process plants
Temperature transmitters YTA610, YTA710 RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus
Flowmeters ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 Water and conductive liquids, mass flow of hydrocarbons, steam and gas
Analysers TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen
Controllers and recorders UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 Single-loop control, furnace programs and data recording
Control and safety systems CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 Spares and expansions for CENTUM DCS, safety systems and STARDOM
Battery packs S9129FA, S9185FA, S9548FA Memory backup batteries for DCS and controller modules

The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.

Where Yokogawa products are used

In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.

Ordering Yokogawa products: what we need

Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.

Facts checked against Yokogawa's corporate history, October 2026.

FAQ

Questions about the Yokogawa MLX-A21-14/KU21/ENG/SST Loop Indicator

Answers from our engineering team on installation, compatibility and integration.

01What is the Yokogawa MLX-A21-14/KU21/ENG/SST?
It is a Yokogawa MLX loop-powered process indicator in the A21-14 configuration with ATEX approval, factory range and scale, and a stainless tag screwed to an aluminum housing.
02Does the MLX-A21-14/KU21/ENG/SST need an external power supply?
No. The MLX takes its power from the 4 to 20 mA loop, with a voltage drop of 3.5 V at 20 mA, so it is wired in series with the loop.
03What do the codes in MLX-A21-14/KU21/ENG/SST mean?
MLX-A is the 4 to 20 mA indicator, 2 is the vertical 2 inch pipe mount, 1 is the aluminum housing, -1 is standard communication, 4 is the M20 entry with one blind plug, KU21 is ATEX, ENG is factory scaling and SST is the tag plate.
04What accuracy does the MLX-A21-14/KU21/ENG/SST offer?
The datasheet gives plus or minus 0.05 percent of full scale plus one digit, with an operating ambient range of -40 to +80 C and an enclosure rating of NEMA 4X and IP67.
05How do I request the MLX-A21-14/KU21/ENG/SST in Oman?
Send an RFQ with the part number, quantity, calibrated range, units and tag text. Seven Star LLC is an independent supplier and replies with availability for Oman and the GCC.