Brand:

ABB AF09Z-30-01-23 Low-Consumption Contactor 4 kW, 100-250 V

Description

ABB AF09Z-30-01-23 low-consumption 3-pole contactor for PLC-driven panels

The ABB AF09Z-30-01-23 is the low-consumption (Z) version of the AF09 contactor, with three N.O. main poles, one built-in N.C. auxiliary contact and a coil for 100 to 250 V on 50/60 Hz AC or DC. Its order code is 1SBL136001R2301 and its net weight is 0.310 kg. The main-circuit ratings match those of the standard AF09-30-01-13: 9 A in AC-3 at 400 V, which is a 4 kW motor.

What changes with the Z is the magnet system. The AF09Z-30-01-23 draws far less at pull-in and when held closed, which lowers the burden on a transformer, a UPS-fed control circuit or a distributed relay output, and cuts heat inside a crowded enclosure.

Reading the AF09Z-30-01-23 code

Group Meaning in AF09Z-30-01-23
AF09 Contactor size, 9 A AC-3 at 400 V, 4 kW
Z Low-consumption coil interface
30 Three N.O. main poles
01 One built-in N.C. auxiliary contact (mirror contact)
23 Coil code: 100 to 250 V 50/60 Hz and 100 to 250 V DC

Z-type coil codes start with 2 (20, 21, 22 and 23). They are not interchangeable with standard AF codes starting with 1, so write the full code on any purchase order.

AF09Z-30-01-23 technical specifications

Parameter Specification
Manufacturer / part number ABB / AF09Z-30-01-23
Order code / EAN 1SBL136001R2301 / 3471523113336
Poles and built-in contacts 3 N.O. main poles; 1 N.C. built-in auxiliary contact
Coil voltage Uc 100 to 250 V 50/60 Hz and 100 to 250 V DC
Coil consumption (AF..Z) Pull-in average 16 VA (AC) or 12 to 16 W (DC); holding 1.7 VA / 1.5 W (AC) or 1.7 W (DC)
Coil operating limits 0.85 x Uc min to 1.1 x Uc max at 60 °C; at 70 °C the AF..Z DC coil keeps 1.1 x Uc max
Dip withstand (IEC 61000-4-11, level 0 %) 22 ms average for Uc = 24 to 250 V 50/60 Hz, -20 to +60 °C
Rated operational voltage Ue (IEC) 690 V max.
Rated frequency limits 25 … 400 Hz
Conventional free-air thermal current Ith (40 °C, 6 mm²) 35 A
AC-1 rated operational current 25 A at 40 °C, 25 A at 60 °C, 22 A at 70 °C (4 mm²)
AC-3 rated operational current 9 A at 220 to 440 V; 9.5 A at 500 V; 7 A at 690 V
AC-3 rated power 2.2 kW at 230 V; 4 kW at 400/415/440 V; 5.5 kW at 500 V and 690 V
AC-8a (no overload relay, 400 V, 40 °C) 12 A / 5.5 kW
Making / breaking capacity AC-3 10 x Ie / 8 x Ie
Short-circuit protection (no overload relay) gG fuse 25 A up to 500 V AC
Short-time withstand current Icw 300 A for 1 s; 150 A for 10 s; 80 A for 30 s; 60 A for 1 min; 35 A for 15 min
Heat dissipation per pole 0.8 W (AC-1); 0.1 W (AC-3)
Switching frequency 600 cycles/h AC-1; 1200 cycles/h AC-3; 300 cycles/h AC-2/AC-4
Mechanical durability 10 million operating cycles
Net weight 0.310 kg

Z-version coil data are quoted by ABB in the same datasheet as the standard coils; the voltage sag immunity to SEMI F47-0706 is stated as conditions of use on request.

What makes the Z coil different

A standard AF coil pulls in at about 50 VA. The AF09Z-30-01-23 pulls in at about 16 VA on AC, and holds at about 1.7 VA, which is also lower than the 2.2 VA of the standard type. In practice this lets a small control transformer carry more contactors, and it reduces the voltage drop on long control cables during simultaneous starting.

Z contactors are also specified to ride through short voltage dips: the datasheet quotes an average of 22 ms at zero residual voltage for the 24 to 250 V range. That helps avoid nuisance drop-outs on weak supplies, though it is not a substitute for a proper ride-through design where a process must not stop.

Fitting the AF09Z-30-01-23 into a system

Use the AF09Z-30-01-23 where the control supply is 100 to 250 V and the load is around 4 kW. The ABB TF42 overload relay mounts directly, CA4 and CAL4 auxiliary blocks extend the contact set, and BEA26-4 connecting links are available for building a direct-on-line starter with a manual motor starter. Note from the datasheet that the CAT4 coil-terminal block and the VEM4 interlock set cannot be fitted on Z contactors with the 12 to 20 V DC coil; that restriction does not apply to the 100 to 250 V coil of the AF09Z-30-01-23.

Sibling parts include the standard AF09-30-01-13 with the same voltage band, the AF26Z-30-00-23 for 11 kW, and the AF09Z-30-01-21 for 24 to 60 V control that can be driven by a 24 V DC PLC output.

Selection checklist for the AF09Z-30-01-23

  • Decide between the Z and standard coil: choose Z when control power, heat or transformer size is a limit.
  • Check the control supply sits within 100 to 250 V, AC or DC, including tolerance.
  • Confirm the load: 9 A AC-3 at 400 V (4 kW), or 9.5 A at 500 V, 7 A at 690 V.
  • One N.C. contact is already built in; add CA4 blocks for N.O. contacts.
  • Select the overload relay range from the motor nameplate.
  • State the standard needed, since UL/CSA ratings (25 A general use at 600 V AC) are given separately.

Installing and maintaining the AF09Z-30-01-23

Fixing is on a 35 mm DIN rail or with two M4 screws; contactors can be mounted side by side. Main terminals accept up to 6 mm² and are tightened to 1.5 Nm; coil and auxiliary terminals are tightened to 1.2 Nm. Close any unused terminal screws, since contactors are delivered with the screws open.

Test the control circuit before the first energisation: with the supply off, check that the coil terminals read the expected voltage when the control contact is closed. Measure the voltage at the coil terminals rather than at the transformer, so that cable drop is included. Regular inspection should cover terminal tightness and any signs of overheating on the poles.

Using the AF09Z-30-01-23 in Oman and the GCC

The AF09Z-30-01-23 suits compact motor control centres, packaged skids and PLC-managed panels in oil and gas, water desalination, power generation and facility services. Where control circuits are fed from a UPS or a shared 110 V supply, the low pull-in value can allow more contactors per supply. In hot enclosures, the reduced holding power helps keep internal temperature rise lower.

Choose enclosure ventilation so the contactor stays within its limits: -25 to +60 °C when mounted with an overload relay, and -40 to +70 °C without.

AF09Z-30-01-23 versus the standard AF09-30-01-13

Item AF09Z-30-01-23 AF09-30-01-13
Order code 1SBL136001R2301 1SBL137001R1301
Pull-in (AC) 16 VA 50 VA
Holding (AC) 1.7 VA / 1.5 W 2.2 VA / 2 W
Net weight 0.310 kg 0.270 kg
Coil range 100 to 250 V AC/DC 100 to 250 V AC/DC
Main ratings Same: 9 A AC-3, 4 kW at 400 V Same

RFQ details for the AF09Z-30-01-23

  • Type AF09Z-30-01-23 (1SBL136001R2301) and quantity.
  • Control voltage, AC or DC, and frequency.
  • Motor power and nameplate current.
  • Overload relay, auxiliary block or interlock required.
  • Panel temperature and project standard.

Documents and quotation

A technical datasheet that covers the AF09Z-30-01-23 is attached on this page.

Seven Star LLC supplies ABB low-voltage control gear in Oman and the GCC. Send us the part number AF09Z-30-01-23 and your quantity, and we will confirm availability and a quotation.

Other Models in the Abb Af09 3pole Contactor Range

Seven Star LLC supplies models from the Abb Af09 3pole Contactor range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
ABB AF09-30-01-13 3-Pole Contactor 4 kW, 100-250 V CoilContactors & Overload RelaysView details
ABB AF09Z-30-01-23 Low-Consumption Contactor 4 kW, 100-250 VContactors & Overload RelaysYou are viewing this model
Datasheets & Documents
  • PDF Datasheet ABB AF09Z-30-01-23 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB AF09Z-30-01-23 Low-Consumption Contactor 4 kW,

Answers from our engineering team on installation, compatibility and integration.

01How does the AF09Z-30-01-23 differ from the AF09-30-01-13?
Main-circuit ratings are the same, but the Z coil is a low-consumption design: about 16 VA at pull-in on AC against 50 VA, and about 1.7 VA holding against 2.2 VA. The Z version also weighs 0.310 kg against 0.270 kg.
02Can the AF09Z-30-01-23 coil be supplied with DC?
Yes. The coil is rated 100 to 250 V DC as well as 100 to 250 V at 50/60 Hz, so the same part works on both AC and DC control circuits within that band.
03What is the dip withstand of the AF09Z-30-01-23?
The datasheet gives 22 ms on average at level 0 percent according to IEC 61000-4-11, for Uc from 24 to 250 V at 50/60 Hz and ambient from minus 20 to plus 60 degrees C.
04What motor can the AF09Z-30-01-23 control?
In AC-3 it is rated 9 A at 400 V, which is 4 kW, with 5.5 kW at 500 V and 690 V. The motor nameplate current and start duty should be confirmed before selection.
05Does the AF09Z-30-01-23 need a surge suppressor?
No. ABB states that AF and AF..Z contactors include built-in surge protection, so an extra suppressor across the coil is not needed.