- Automation & ControlView all 1,922 products
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- HMI Displays
- Industrial Computers
- Motor Soft Starters
- Servo Drives
- Pneumatic Cylinders
- Machine Vision
- Automation Software
- Robotics
Brand: Lovato Electric
Lovato DMG210 DIN-Rail LCD Multimeter
Description
Reading volts, amps, power and energy on one screen
The DMG210 is a modular LCD multimeter, non-expandable from the Lovato Electric DMG range for three-phase + neutral systems. It measures with true RMS inputs, connects to current transformers with 1 A or 5 A secondaries, and shows readings on a backlit LCD.
The auxiliary supply covers 100-240 VAC and 110-250 VDC. Voltage inputs are rated 690 VAC line-to-line and 400 VAC line-to-neutral. Active energy accuracy is Class 1 (IEC/EN 62053-21).
Technical specifications
| Parameter | Specification |
|---|---|
| Order code | DMG210 |
| Product designation | Modular LCD multimeters. non expandable |
| Product type designation | DMG210 |
| Type | Three-phase + neutral |
| DIN rail module number | 4 |
| Auxiliary rated supply voltage AC | 100-240 VAC |
| Auxiliary rated supply voltage DC | 110-250 VDC |
| AC (min) | 85 VAC |
| AC (max) | 264 VAC |
| DC (min) | 93.5 VDC |
| DC (max) | 300 VDC |
| Operational frequency (min) | 45 Hz |
| Operational frequency (max) | 66 Hz |
| Power consumption (max) | 4.5 VA |
| Power dissipation Max | 1.7 W |
| phase-phase | 690 VAC |
| phase-neutral | 400 VAC |
| phase-phase (Operating voltage range) | 20-830 VAC |
| phase-neutral (Operating voltage range) | 10-480 VAC |
| Voltage inputs operational frequency (min) | 45 Hz |
| Voltage inputs operational frequency (max) | 66 Hz |
| Voltage inputs measurement method | True RMS |
| Connection method | Single. two. three-phase with or without neutral. balanced three-phase systems |
| Rated current (Ie) | 5 A |
| Measurement range | 0.01-6 |
| Overload capacity | +20% Ie through external CT with 5A secondary |
| Overload peak | 50A for 1s |
| VLN voltage | ±0.5% |
| VLL voltage | ±0.5% |
| Current | ±0.5% |
| Frequency | ±0.05% |
| Active power | ±1% |
| Active energy | Class 1 (IEC/EN 62053-21) |
| Reactive energy | Class 2 (IEC/EN 62053-23) |
| Baud rate | Programmable 1200-38400 bps |
| Rated insulation voltage Ui IEC/EN | 690 V |
| Rated impulse withstand voltage Uimp | 9.5 kV |
| Operating frequency withstand voltage | 5.2 kV |
| Harmonic analysis | THD only |
| Type of communication port | RS485 |
| Housing type | Polyamide |
| Operating temperature (min) | -20 °C |
| Operating temperature (max) | +60 °C |
| Storage temperature (min) | -30 °C |
| Storage temperature (max) | +80 °C |
| Maximum Pollution degree | 2 |
| Protection degree | IP30 |
Selecting the meter
The DMG range offers several display and expansion combinations; the DMG210 is one of them, so check the product designation and the communication port against the panel requirements.
Check the current transformer ratio and set it in the meter during commissioning.
Applications and installation
Plant engineers use them on main distribution boards and feeder panels to log load profiles and check power quality, with RS485 output to a SCADA or building management system.
Housing: Polyamide.
For panel design and commissioning, the practical figures to keep at hand are: rated current (Ie) 5 A; measurement range 0.01-6; overload capacity +20% Ie through external CT with 5A secondary; overload peak 50A for 1s; VLN voltage ±0.5%; VLL voltage ±0.5%; current ±0.5%; frequency ±0.05%; active power ±1%; reactive energy Class 2 (IEC/EN 62053-23); baud rate Programmable 1200-38400 bps; housing type Polyamide; protection degree IP30; operating temperature (min) -20 °C. These come straight from the datasheet and are repeated here so that the key installation limits are visible without opening the PDF.
Documents and quotation
Attached is the English datasheet that Lovato Electric’s online catalogue generates for DMG210; the specification table above reproduces its values. Check the system voltage, the current transformer ratio and the communication interface you need against your own drawings first; the manufacturer may update datasheet figures without notice. Browse automation accessories for alternatives. To order DMG210, submit the quotation form with your quantity and site; Seven Star LLC, an independent supplier in Muscat, handles the reply. The datasheet adds the accuracy classes, input ranges and terminal data needed to commission the instrument correctly.
Datasheets & Documents
- Datasheet Lovato Electric DMG210 datasheet (EN, catalogue export) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.
Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.
Lovato Electric at a glance
| Established | 1922, Bergamo, Italy |
|---|---|
| Headquarters | Gorle (Bergamo), Italy |
| Ownership | Private, family-run for four generations |
| Product families | Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs |
Lovato products we list
| Family | Models | Typical use |
|---|---|---|
| Contactors | BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing | Switching motors, heaters, lighting and capacitor banks |
| Motor protection and starters | SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay | Short-circuit and overload protection and direct starting of motors |
| Soft starters | ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 | Reducing starting current and mechanical shock on pumps, fans and compressors |
| Variable speed drives | VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 | Speed control of pumps, fans and conveyors to save energy |
| Power management and control | DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC | Power factor correction, mains/generator changeover and energy monitoring |
Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.
Where Lovato products are used
In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.
Ordering Lovato products: what we need
Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.
Facts checked against Lovato Electric company profile brochures, October 2026.
Browse Lovato Electric products by category: Motor Soft Starters, Automation Accessories, Controllers & Data Acquisition, PLC & I/O Cards, Circuit Breakers, Diesel Generator Spare Parts.
FAQ
Questions about the Lovato DMG210 DIN-Rail LCD Multimeter
Answers from our engineering team on installation, compatibility and integration.
01What does the DMG210 measure?
Three-phase voltages, currents, power, energy and related values, as listed in the datasheet.
02What supply does it need?
100-240 VAC or 110-250 VDC.
03What is its energy accuracy?
Active energy Class 1 (IEC/EN 62053-21).
04Which communication port?
RS485.
05Is it expandable?
Modular LCD multimeters. non expandable.


















Reviews