Brand:

Rittal VX25 Ri4Power 185 mm Busbar System

Description

A compact busbar system for central power distribution

The Rittal VX25 Ri4Power 185 mm is a busbar and enclosure solution for compact, central power distribution in the VX25 baying enclosure system. Its 185 mm bar centre distance is matched to the VX25 enclosure widths, so the full enclosure width remains usable for equipment. Rittal rates it for rated voltages up to 690 V, rated currents up to 2100 A and short-circuit withstand up to 50 kA.

It is aimed at distribution assemblies where the larger Ri4Power system is not needed. Installation of equipment is stated to comply with IEC 61439 and is documented with a design verification that the Rittal Power Engineering software generates after planning.

Technical specifications

Parameter Specification
Manufacturer / system Rittal / VX25 Ri4Power 185 mm
Rated voltage Up to 690 V
Rated current Up to 2100 A
Short-circuit protection Up to 50 kA; busbar support rated short-time withstand current Icw up to 50 kA
Bar centre distance 185 mm
Contact hazard protection Up to IP 2XB (finger-safe) from the system portfolio
Busbar support For busbar sizes from 40 x 10 to 120 x 10 mm; mounted by system attachment in the VX25 baying enclosure, no drilling
Cover section Integral busbar shielding against accidental arcing; components can be top-mounted
Base tray Rear contact protection; fits VX25 widths from 600 mm to 1200 mm
Component adaptors Two sizes for compact circuit-breakers up to 630 A and 1600 A; clamping or screw attachment
Air circuit-breaker adaptors Listed for breakers up to 630 A and 1600 A
NH slimline switch-disconnectors Fuse sizes 00 to 3, optional electronic fuse monitoring
Connector kits Prepared for ABB, Eaton, Schneider Electric and Siemens breakers; optional current transformer

How the system goes together

Assembly is described in three steps: position the system attachment in the enclosure, secure the busbar assembly, and clip the cover system in place. The busbar contact system is no-drill and lock-home, and air can still circulate between the standardised earthing elements, which Rittal says limits temperature rise and permits higher loads. Cover plate sets are available for each enclosure width, and busbar baying is integrated into the contact protection.

Fuse and switching components

NH slimline switch-disconnectors for sizes 00 to 3 switch with fuses through an integral quick-break contact with double break, so all poles are dead when a fuse is replaced. The lid lock can only be released with a tool and a switch position display is built in. NH slimline fuse-switch disconnectors, also sizes 00 to 3, come as single-pole or 3-pole switchable variants with symmetrical cable outlet at top and bottom, with or without fuse monitoring. Bars are arranged vertically, which reduces mutual heating and removes the need for a separate cable space at the side.

Documents and quotation

The Rittal brochure VX25 Ri4Power 185 mm is available on this page. The wider system with up to 6300 A is on the

Rittal VX25 Ri4Power.

page, and other enclosure products are listed under Automation Accessories. For a quotation send the rated current, short-circuit level, enclosure sizes, breaker makes and ratings, and the number of fuse-switch positions. Final article numbers should be confirmed in the Rittal configurator.

Datasheets & Documents
  • PDF Datasheet Rittal VX25 Ri4Power 185 mm brochure Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Many control panels sit inside a Rittal enclosure or one built to the same pattern. Rittal, founded in 1961 and based in Herborn, Germany, makes enclosures, enclosure climate control and power distribution components. Seven Star LLC, an independent supplier in Muscat, lists Rittal enclosures and cooling units for panel builders and maintenance teams in Oman and the GCC, including the TS 8 system, Blue e+ cooling units and a KEL Ex stainless steel enclosure.

Rittal products listed on our site

The TS 8 is the free-standing, bayable enclosure system found in a very large number of existing panels. Blue e+ wall-mounted cooling units remove heat from closed enclosures. The KEL 9404.600 is a stainless steel Ex enclosure, listed at 380 x 600 x 210 mm, for terminal and junction duties in hazardous areas.

Ordering Rittal enclosures and cooling units: what we need

Rittal parts are ordered by a seven-digit model number such as 9404.600. Send that number, or the width, height and depth, material, protection category and door arrangement. For cooling units add the required cooling output, the rated voltage and the mounting cut-out of the unit being replaced. For Ex enclosures, state the zone and the marking required.

Frequently Asked Questions

What current and voltage does the 185 mm system cover?
Up to 2100 A at up to 690 V, with short-circuit protection up to 50 kA according to the Rittal brochure.
What does 185 mm refer to?
It is the bar centre distance of the busbar system, matched to the VX25 baying enclosure widths.
Which busbar sizes does the support take?
Busbar dimensions from 40 x 10 mm to 120 x 10 mm.
What contact protection is offered?
Contact hazard protection up to IP 2XB (finger-safe), with busbar shielding in the cover section against accidental arcing.
Which fuse sizes can the NH slimline devices take?
The switch-disconnectors and fuse-switch disconnectors are listed for NH fuse sizes 00 to 3.