The Kidde KC2-OSH-CD is a conventional, low-profile, self-diagnostic, two-wire photoelectric smoke detector combined with a rate-of-rise and fixed-temperature heat sensor in one head. Multi-criteria optical sensing and an alarm verification feature are meant to tell smoke from a fire from nuisance smoke from non-fire sources. The datasheet lists it for commercial and industrial environments as well as life safety protection, and as compatible with the Kidde AEGIS-PHX, AEGIS 2.0 and AEGIS-XLT conventional control units.

Technical specifications

Parameter Specification
Model KC2-OSH-CD detector head only, datasheet K-70-370 Rev AC (August 2026)
Operating voltage 6.5 to 33 VDC
Standby current 88 microamps at 18 VDC; 145 microamps at 33 VDC
Alarm current Up to 60 mA max. if not limited by the control unit
Photoelectric sensitivity 0.5 to 4.36 percent per ft obscuration (1.63 to 13.62 percent per m)
Heat sensing Rate-of-rise 15 degrees F/min (8 degrees C/min); fixed temperature 135 degrees F (57.2 degrees C), actual alarm point 129 to 141 degrees F
Response time index Quick (evaluated by FM Approvals)
LED indicator Normal: green every 30 s; trouble: green every 5 s; alarm: steady red; remote LED output 0.225 mA average
Reset 2.5 V maximum, 1 second minimum
Dimensions Head 4.375 in. D x 2.25 in. H (11.10 x 5.70 cm); base 4.4 in. D x 0.75 in. H; total 2.625 in. (6.67 cm); white
Operating / storage temperature 32 to 100 degrees F (0 to 38 degrees C); storage -4 to 140 degrees F; 0 to 93 percent RH non-condensing
Air velocity 0 to 4,000 ft/min (0 to 20.32 m/s)
Compatibility identifier UL two-wire detector identifier S10AR2; bases KC2-SB, KC2-SB4, KC2-RB, KC2-RB4
Listings as printed FM Approved; cULus Listed; California State Fire Marshal
Ordering KC2-OSH-CD head; KC2-SB and KC2-SB4 standard bases; KC2-RB and KC2-RB4 relay bases; GSA-TS trim skirt; GSA-LED remote LED; SIGA-RTA removal tool; SM200-12PKG test smoke

Bases and installation

The head attaches to either a KC2-SB standard base or a KC2-RB relay base, and the head alone is not a complete detector point, so a base must be ordered with it. The relay base changes contact state when the detector alarms. The -4 variants suit 4 in. square boxes and include a trim skirt. Bases mount to a North American single-gang box, 3-1/2 or 4 in. octagon boxes, a European 75 mm single-gang box, or a BESA box with 60.3 mm fixing centers. Terminals are accessible from the room side. Class A and Class B wiring diagrams show a 5.1 k, 0.5 W end-of-line resistor, P/N 06-220184-001. The maximum wall mounting distance from the ceiling is 12 in. (305 mm).

What to confirm before ordering

Check that the panel’s two-wire detector compatibility list includes the KC2 series, since the datasheet points to separate compatibility documents (K-70-300 and K-84-901). State the quantity of heads, the base type, and whether remote LEDs or relay functions are needed. Mounting height, spacing and environment follow the applicable fire alarm code and the designer’s layout.

Documents and quotation

The manufacturer’s datasheet K-70-370 (2 pages) is attached to this page as a download. Seven Star LLC is an independent supplier in Muscat. Price, delivery time and availability are quoted once we have the article number and number of units. More detection items are listed in Fire & Gas Detectors.

Datasheets & Documents
  • PDF Datasheet Kidde KC2-OSH-CD datasheet K-70-370 Rev AC (August 2026) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Kidde is a fire protection brand founded in 1917 in New Jersey by engineer Walter Kidde. After buying the rights to a steam-based shipboard fire system, Kidde replaced the steam with carbon dioxide, and the company went on to build the first portable CO2 extinguisher and the first built-in industrial CO2 system in the mid-1920s. Since December 2024 the Kidde brand has belonged to Kidde Global Solutions.

Seven Star LLC lists Kidde clean agent cylinders, control heads and pilot cylinders, and supplies Kidde fire systems parts to operators and fire contractors in Oman as an independent supplier. Household smoke alarms and aircraft systems sold under the same name are outside our scope.

Kidde company profile

Founded 1917, New Jersey, USA, by Walter Kidde
Founder Walter Kidde, a construction engineer born in Hoboken in 1877
Key technology Carbon dioxide fire suppression for ships, industry and portable extinguishers
Ownership United Technologies 2005–2020, Carrier 2020–2024, Kidde Global Solutions since December 2024
Product families Portable fire extinguishers, CO2 and clean-agent (FM-200, Novec 1230) suppression systems, smoke, heat and carbon monoxide alarms, detection and control panels

Milestones

  • 1917: Walter Kidde founds the company.
  • 1918: Kidde acquires the rights to the 'Rich' shipboard system and adapts it to carbon dioxide.
  • 1924: The first portable carbon dioxide fire extinguisher.
  • 1925: The first built-in industrial carbon dioxide system.
  • 1966: Kidde acquires Fenwal.
  • 2024: Kidde becomes part of Kidde Global Solutions.

Kidde fire suppression parts listed here

The listed items are release-train components: the WK-890181-000 electric control head, a 24 V DC unit used on Kidde FM-200 systems, an FM-200 (HFC-227ea) clean agent cylinder in the 200 lb size, and the K62462 pilot gas cylinder. Kidde also builds high-pressure CO2 systems with their own control heads and nitrogen pilot cylinders. Typical sites in the GCC are turbine enclosures, switchgear and control rooms, data halls and marine machinery spaces.

Kidde products we list

Family Examples
Fire Fighting ADS HFC-227ea Engineered Clean Agent Sup…, CARDOX Low-Pressure CO2 Fire Suppression…, FM-200 200 Lb Clean Agent Fire Suppressi…, HPCO2 High Pressure CO2 Fire Suppression…, NATURA Inert Gas Fire Suppression System, NATURA-Micro LHS Cabinet Fire Suppressio…, WK-890181-000 Electric Control Head, P/N K62462 | Kidde
Logic Controllers AEGIS-PHX Conventional Fire Alarm Suppre…, ARIES-MLX Multi-Loop Addressable Suppres…, ARIES-SLX Single-Loop Addressable Suppre…
Fire & Gas Detectors LHS Linear Heat Detection Sensor Cable, ModuLaser Modular Aspirating Smoke Detec…

Ordering Kidde parts: what we need

Kidde components are ordered by part number, so send it exactly as printed on the label or in the system drawings. For an agent cylinder we also need the fill weight, valve type and the transport documents required. Send the nameplate photo and the system design reference whenever possible.

Facts checked against Kidde's own history pages (kidde.com) and published company histories, October 2026.

FAQ

Questions about the Kidde KC2-OSH-CD Two-Wire Smoke and Heat Detector

Answers from our engineering team on installation, compatibility and integration.

01What does the KC2-OSH-CD detect?
Smoke through a photoelectric chamber with multi-criteria sensing, and heat through a rate-of-rise sensor at 15 degrees F per minute plus a fixed 135 degrees F sensor.
02Does the head include a base?
No. The part number is the detector head only. It attaches to a KC2-SB or KC2-RB base, ordered separately.
03Which control units are named as compatible?
The datasheet lists the Kidde AEGIS-PHX, AEGIS 2.0 and AEGIS-XLT conventional control units.
04What is the operating voltage range?
6.5 to 33 VDC, with a standby current of 88 microamps at 18 VDC.
05What does the LED show?
A green flash every 30 seconds is normal, every 5 seconds is trouble, and a steady red LED is alarm.