Brand:

Advantech ADAM-4520A-A Robust Isolated RS-232 to RS-422/485 Converter

Description

Overview

The Advantech ADAM-4520A-A is the robust, wide-temperature version of Advantech’s isolated RS-232 to RS-422/485 converter. The manufacturer names it the Robust RS-232 to RS-422/485 Isolated Converter and lists the order code ADAM-4520A-A. It converts the signals of a DB9 female RS-232 port into two-wire RS-485 or four-wire RS-422, extends the data link to as much as 1.2 km, and isolates the two sides with 3,000 VDC. The front label shows a small DIP switch table, SW1, that handles termination, direction control and mode selection without any software.

Seven Star LLC is an independent supplier serving Oman and the GCC. We list the module under the full order suffix so that your purchase order matches the manufacturer documentation exactly.

What you get with the Advantech ADAM-4520A-A

  • Conversion from RS-232 to RS-422 or RS-485 with a maximum data rate of 115.2 kbps.
  • Automatic detection of baud rate and data format, so no baud switch needs to be set.
  • Built-in 120 ohm termination resistors that can be switched in with the DIP switch.
  • DIP switch selection between RS-422 and RS-485, and between automatic and RTS direction control.
  • 3,000 VDC isolation voltage.
  • Unregulated 10 to 48 VDC supply input with reversal protection.
  • Operating and storage temperature of -40 to 85 degrees Celsius.
  • Housing of 102 x 60 x 27 mm with DIN rail mounting adaptor.

Specification summary for Advantech ADAM-4520A-A

Specification ADAM-4520A-A value
Product description Robust RS-232 to RS-422/485 isolated converter
RS-232 connector 1 x DB9 female
RS-422/485 connector 1 x plug-in terminal block, 14 to 22 AWG
Isolation 3,000 VDC
Maximum data rate 115.2 kbps
Distance Up to 1.2 km
Baud rate handling Auto detection of baud rate and data format
Termination 120 ohm, selectable by DIP switch
Power input Unregulated 10 to 48 VDC, reversal protected
Power consumption Typical 0.6 W and maximum 0.8 W at 24 VDC
Operating humidity 5 to 95 percent RH
Operating temperature -40 to 85 degrees Celsius
Storage temperature -40 to 85 degrees Celsius
Dimensions 102 x 60 x 27 mm

Reading the SW1 switch on the Advantech ADAM-4520A-A

The label on the converter carries a four-position switch table. Positions 1 and 2 control the terminal resistor: on gives 120 ohms and off, the default, leaves the line open. Position 3 selects the RS-485 direction control, either RTS or automatic, with automatic as the default. Position 4 selects the mode, RS-422 when on and RS-485 when off, which is the default. Because the factory default is automatic RS-485 without termination, most single-drop tests work immediately. Switch the termination on only at the converter when it sits at one physical end of the bus, and leave it off when the module is a drop in the middle of the trunk, because extra terminating resistors load the line and weaken the signal.

How Advantech ADAM-4520A-A differs from the ADAM-4520-F

Both models convert RS-232 to RS-422/485 with 3,000 VDC isolation, but the specifications diverge. The ADAM-4520-F requires you to set the baud rate with a switch from 1,200 to 115.2 k bps, while the ADAM-4520A-A detects baud rate and data format automatically. The supply window widens from 10 to 30 VDC to 10 to 48 VDC. The temperature range grows from -10 to 70 degrees Celsius to -40 to 85 degrees Celsius, and typical power consumption falls from 0.8 W to 0.6 W. The depth increases from 25 mm to 27 mm. The newer unit also adds built-in selectable 120 ohm termination and a DIN rail adaptor shown in the dimension drawing.

Applications in Oman and the GCC

Because the module covers -40 to 85 degrees Celsius it can be placed in unconditioned shelters, outdoor junction boxes and roadside cabinets where summer temperatures are extreme. Typical jobs include connecting RS-232 chromatograph outputs to a control room, linking weighbridge indicators to a plant network, polling meters from a SCADA master and bridging legacy PLC programming ports. The isolation protects equipment in installations with long cable runs between buildings or between substations and process areas.

Selection and wiring guidance

Pick the Advantech ADAM-4520A-A when ambient conditions are demanding, when the supply could rise toward 48 VDC, or when you do not want to configure baud rates manually. Use twisted pair cable for the differential pair and keep the length within the 1.2 km limit quoted by the manufacturer, reducing the data rate when the cable is long or noisy. Check the terminal markings printed beside the screw block, which show DATA+ and DATA- for RS-485, TX and RX pairs for RS-422, and the supply terminals marked +Vs and GND.

Installation and commissioning

Snap the module on a DIN rail using the adaptor, connect the DB9 cable to the RS-232 device, wire the field cable to the plug-in terminal block, and apply 10 to 48 VDC. Set SW1 for the intended mode, enable the termination only on bus ends, and start communication from the host. The status and com indicators on the front help to confirm that power is present and that data is flowing.

Maintenance

There are no serviceable parts. Inspect terminal tightness, check the supply voltage and verify that the DIP switch settings match your documentation after any maintenance visit. Keep a spare Advantech ADAM-4520A-A so that a failed converter can be swapped without reprogramming, since the module detects the baud rate by itself.

Related items you may also need: Advantech UNO-1372G Atom Quad-Core DIN-Rail Control PC with 3 x GbE and 8 DI/O | Advantech ADAM-6017 8-Channel Analog Input Ethernet I/O Module | Advantech ADAM-6000, ADAM-6200 and ADAM-6300 Ethernet I/O Modules | All Advantech products.

Documents and quotation

The manufacturer datasheet for the ADAM-4520A is attached to this page and includes the features, specifications, dimension drawing and ordering information. To obtain a quotation, send an RFQ stating Advantech ADAM-4520A-A, the quantity, and your delivery destination in Oman or the GCC, together with any DIN rail power supplies you want to include.

Other Models in the Adam 4500 Range

Seven Star LLC supplies models from the Adam 4500 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Advantech ADAM-4520-F Isolated RS-232 to RS-422/485 ConverterAutomation AccessoriesView details
Advantech ADAM-4520A-A Robust Isolated RS-232 to RS-422/485 ConverterAutomation AccessoriesYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Advantech ADAM-4520A-A Robust Isolated RS-232 to RS-422/485 Converter Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Advantech is the Taiwanese maker of industrial computers and IoT hardware: ADAM remote I/O modules, EKI industrial Ethernet switches and serial device servers, industrial PCs, panel PCs and embedded boards. It was founded in Taipei in 1983 by K.C. Liu and partners, and today Advantech Co., Ltd. is headquartered in Taipei and listed on the Taiwan Stock Exchange.

Seven Star LLC supplies Advantech automation products to system integrators and plant teams in Oman, and this page lists items such as an ADAM-6000 Ethernet I/O module, an ADAM-4000 serial converter and an IPC rackmount chassis.

Advantech company profile

Founded 1983, Taipei, Taiwan
Founder K.C. Liu and partners
Headquarters Taipei, Taiwan
Ownership Advantech Co., Ltd., public company listed on the Taiwan Stock Exchange
Product families ADAM-4000 and ADAM-6000 remote I/O, EKI managed and unmanaged switches and serial device servers, industrial PCs and rackmount computers, panel PCs, embedded boards and edge gateways

Advantech ADAM and IPC products listed here

The ADAM-6017 is an 8-channel analog input module from the ADAM-6000 Ethernet I/O family. It brings voltage and current signals onto a network and is read by SCADA or PLC software over Modbus TCP. The ADAM-4520 belongs to the ADAM-4000 serial family and converts RS-232 to isolated RS-422 or RS-485, a common fix for linking a PC or panel to field devices. The IPC-623 is a 4U, 20-slot rackmount chassis that houses a backplane, CPU card and expansion cards for control room computers.

Advantech products we list

Family Examples
Industrial Communications ADAM-4520 Isolated RS-232 to RS-422/485, ADAM-4571 1-Port RS-232/422/485 Serial Device, ECU-1152 Industrial Communication Gateway, EKI-2528 8-Port Unmanaged Industrial Ethernet, EKI-2725 5-Port Gigabit Unmanaged Industrial, EKI-5710E 10-Port Managed Industrial Ethernet, EKI-7710E-2CI 8FE+2G Combo Managed Redundant
Industrial Computers ARK-3534B LGA1700 Expansion Fanless Box PC, IPC-610-L 4U 15-Slot Rackmount Industrial, IPC-623 Industrial 4U Rackmount Chassis, TPC-1051WP-E3AE Panel PC, TPC-1551WP-E3AE Panel PC, UNO-1372G Atom Quad-Core DIN-Rail Control PC, UNO-2484G V2 Modular Fanless Box PC with 4 x
PLC & I/O Cards ADAM-4017+ 8-Channel Analog Input Module, ADAM-6017 8-Channel Analog Input Ethernet I/O, ADAM-6050 12DI/6DO Ethernet Digital I/O Module
Controllers & Data Acquisition ADAM-4055 16-Channel Isolated Digital I/O, ADAM-4150 Robust 15-Channel Digital I/O

Ordering Advantech hardware: what we need

Send the full part number with its suffix. Advantech adds letters after the model, as in ADAM-6017-D, to mark the hardware revision, and existing configurations sometimes depend on it. For an IPC chassis, state the backplane, power supply and drive bay arrangement, since these are ordered as specific versions. We supply across the GCC and check part numbers against Advantech documentation.

Facts checked against Advantech's published corporate profile, October 2026.

FAQ

Questions about the Advantech ADAM-4520A-A Robust Isolated RS-232 to

Answers from our engineering team on installation, compatibility and integration.

01What temperature range does the Advantech ADAM-4520A-A support?
The datasheet lists -40 to 85 degrees Celsius for both operating and storage, with operating humidity of 5 to 95 percent RH.
02Does the ADAM-4520A-A need a baud rate switch setting?
No, it detects the baud rate and data format automatically, with a maximum data rate of 115.2 kbps.
03What supply does the ADAM-4520A-A accept?
It accepts an unregulated 10 to 48 VDC supply with reversal protection and consumes typically 0.6 W and at most 0.8 W at 24 VDC.
04Does the ADAM-4520A-A include termination resistors?
Yes, it has built-in 120 ohm termination resistors that are selected with the SW1 DIP switch, and the default position leaves them open.
05How far can the ADAM-4520A-A extend an RS-232 link?
The manufacturer states that it can extend RS-232 data signals up to 1.2 km using the RS-422 or RS-485 side, at up to 115.2 kbps.