Samson 3768 Inductive Limit Switch
Description
Samson 3768 is an inductive limit switch for pneumatic control valves. Two built-in inductive proximity switches report when valve travel passes above or below limits you set, and an optional 3/2-way solenoid valve in the same housing adds a binary on/off pneumatic control. It does not position the valve; it tells the control system where the valve is, and it can force the actuator to a fail-safe position. Everything below is based on the manufacturer’s data sheet T 8356, edition January 2025.
How the Samson 3768 detects position
Valve travel is passed by a coupling pin to a lever, which turns a shaft. Two adjustable metal tags on the shaft interact with two SJ2-SN proximity switches. When a tag sits in the inductive field the switch presents a high resistance, and when it leaves the field the resistance falls. A switching amplifier built to EN 60947-5-6 must be connected in the output circuit. Each contact can be overridden and configured as normally closed or normally open.
Technical data for 3768
| Rated travel, direct on Type 3277 | 7.5 to 30 mm |
|---|---|
| Rated travel, NAMUR IEC 60534 | 7.5 to 120 mm |
| Rotary actuators | VDI/VDE 3845 attachment |
| Proximity switches | 2 x SJ2-SN |
| Hysteresis at rated travel | up to 1 percent |
| Ambient temperature, plastic gland | -20 to +80 C |
| Ambient temperature, metal gland | -45 to +80 C |
| Solenoid supply air | 1.4 to 6 bar (20 to 90 psi) |
| Solenoid coil voltages | 6, 12 or 24 V DC |
| Signal 0 / signal 1 at 24 V | up to 4.7 V / at least 18.0 V |
| Coil resistance at 20 C | 2909 ohm (6 V), 5832 ohm (12 V), 11714 ohm (24 V) |
| Solenoid KV coefficient | 0.14 m3/h |
| Air consumption | OFF up to 60 normal litres per hour; ON up to 10 |
| Protection | IP65 (also NEMA 4X with filter check valve accessory) |
Order code of 3768 explained
The article code for Type 3768 encodes explosion protection, solenoid voltage, pneumatic connections, electrical connection and housing. The explosion-protection digit is 0 for none, 1 for II 2G Ex ia IIC T6 under ATEX, 3 for CSA and FM intrinsically safe or non-incendive, and 8 for II 3G Ex nA II T6. The solenoid digit is 0 for none, 2 for 6 V DC, 3 for 12 V DC and 4 for 24 V DC. Pneumatic ports are 1/4-18 NPT (digit 1) or ISO G 1/4 (digit 2). The cable gland digit selects blue plastic, black plastic or nickel-plated brass. Housings are aluminium; the CrNiMo steel housing is noted as not available since April 2020.
Approvals listed for 3768
- 3768-1: PTB 02 ATEX 2077, II 2G Ex ia IIC T6
- 3768-3: CSA certificate 1607265 for Ex ia IIC T6, Class I Zone 0, and Divisions 1 and 2; FM certificate FM24US0232 for intrinsically safe and non-incendive use, Type 4X
- 3768-8: PTB 03 ATEX 2182 X, II 3G Ex nA II T6
How 3768 differs from other Samson limit switches
The Type 4740 and 4746 are electric or pneumatic switches with different internals, and the Type 4744 is a limit switch designed for hazardous areas. The 3768 is inductive, and it is the one that can optionally include a solenoid valve for binary actuation. It also works with the Type 3277 actuator directly. It does not provide a continuous position signal, which positioners with transmitter options can do, so it suits open/closed confirmation and alarm limits.
Where limit switches with a solenoid are used
Emergency shutdown valves, on/off process valves and fire water isolation valves often need two confirmations and a safe de-energised state. With 3768 the solenoid vents the actuator when de-energised, so the valve moves to its fail-safe position; the speed of air supply can be adjusted with a restriction. In refineries, tank farms and utilities across Oman and the GCC, this combination replaces separate boxes and short pipework with one compact unit.
Installation and adjustment
Mount directly to a Type 3277 actuator or fit the kit for NAMUR or rotary actuators. Attach the lever so that the pin follows the stem, set both metal tags to the required switching points and connect the proximity switches to approved switching amplifiers. For intrinsically safe versions, check the entity parameters of the amplifier against the certificate. Supply air to the optional solenoid should be clean and within 1.4 to 6 bar.
Maintenance
Record the switching positions after commissioning so a later check can detect tag slippage quickly. There are no contacts to wear, so maintenance means checking tag fixing, lever linkage, cable gland sealing and the condition of the filter check valve accessory. When replacing a unit, copy the full article code of the original, because a different explosion protection digit changes the certificate.
Spare planning deserves a note about the temperature window: the plastic cable gland versions are rated down to minus 20 C, while the nickel-plated brass gland version is rated to minus 45 C, so cold sites or exposed pipe racks should use the metal gland. The 24 V coil has a resistance of 11714 ohm at 20 C, which is a high-impedance, low-power load. Please always verify the thresholds of the control system output against the signal 0 and signal 1 voltages in the table above, since a voltage that sits between them leaves the solenoid in an undefined state.
Documents and quotation
The data sheet T 8356 for Samson 3768 is attached. For an RFQ, give the complete article code beginning with 3768, quantity, solenoid voltage, pneumatic thread and hazardous-area requirement. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Installation and Commissioning Planning
Planning ahead shortens downtime when a Samson 3768 goes into service. Confirm the available mounting space, cable entry or process connection, and the tools and spare seals needed on the day. Keep the existing configuration or calibration data so the new unit can be set up to match, and check that loop drawings and the asset register are updated after the swap. If the installation has to fit a short shutdown window, tell us the date when you request a quotation so that delivery of the Samson equipment can be planned around it.
Datasheets & Documents
- Datasheet Samson 3768 Inductive Limit Switch Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
SAMSON is a German manufacturer of control valves, actuators, positioners and self-operated regulators. Hermann Sandvoss founded the company in Düsseldorf on 1 April 1907, and its first important product was a thermostatic valve that controlled temperature without external power. After moves to Mannheim, SAMSON settled in Frankfurt am Main in 1916, where SAMSON AG is still headquartered.
Seven Star LLC supplies Samson control valves, pneumatic actuators and positioners to process plants in Oman, including the types listed on this page and their replacement units.
Samson company profile
| Founded | 1 April 1907, Düsseldorf, by Hermann Sandvoss, as VULCAN Technische Apparate Baugesellschaft; products sold under the SAMSON name |
|---|---|
| Headquarters | Frankfurt am Main, Germany, since 1916 |
| Legal form | SAMSON AG |
| First product | A self-operated thermostatic valve |
| Group brands | SAMSON together with PFEIFFER, LEUSCH, VETEC and AIR TORQUE |
| Product families | Globe valves such as Type 3241, rotary and butterfly valves, 3271 and 3277 pneumatic actuators, 3730 and 3731 positioners, self-operated pressure and temperature regulators |
Milestones
- 1907: Hermann Sandvoss founds the company in Düsseldorf.
- 1909: It is re-established as SAMSON Apparatebau GmbH.
- 1916: After a period in Mannheim, the company moves to Frankfurt am Main.
- 1975: The name becomes SAMSON Mess- und Regeltechnik.
Samson valve, actuator and positioner types
Samson builds a control valve from modules. The Type 3241 globe valve is the general-service body of Series 240, and the Type 3251 is the Series 250 body for higher pressure ratings. Either one is combined with a Type 3271 pneumatic diaphragm actuator or a Type 3277, whose yoke allows the positioner to be attached directly with a concealed travel linkage.
Among the positioners listed are the Type 3725 and the Type 3730 family: the 3730-1 as the basic electropneumatic version, sold in its current generation as TROVIS 3730-1, and the 3730-3 with HART communication and valve diagnostics. Samson also makes PROFIBUS PA and FOUNDATION fieldbus variants in the same family, plus self-operated pressure and temperature regulators.
Where Samson valves are used
Samson control valves throttle steam, gas and liquids in chemical and petrochemical units, refineries, gas processing, power stations, water and desalination plants, and food production. Many reach site as part of a skid or package, so the plant instrument team often meets them first when a positioner or actuator needs replacing. We supply these items to end users and contractors throughout the GCC.
Samson products we list
Ordering Samson parts: what we need
Every Samson device has a nameplate with the type, a configuration ID (Var-ID) and a serial number. A photo of that plate is the surest route to an exact match. Without it, please send:
- Valve: type, DN or NPS, pressure rating, body and trim material, Kvs or Cv, plug and seat style, packing and bonnet type
- Actuator: type, effective area in cm², bench range, fail action and travel
- Positioner: full type code including Ex protection, communication and options such as limit switches or position transmitter
We check the code against Samson documentation and provide the manufacturer's data sheet on request.
Facts checked against SAMSON's corporate chronicle and press material, October 2026.
Browse Samson products by category: Control Valves, Valve Positioner, Valve Actuator.
FAQ
Questions about the Samson 3768 Inductive Limit Switch
Answers from our engineering team on installation, compatibility and integration.
01What does Samson 3768 do?
It contains two inductive proximity switches that signal travel limits and can include a 3/2-way solenoid valve for binary control of the actuator.
02What travel range does 3768 cover?
Direct on a Type 3277 actuator it covers 7.5 to 30 mm, and with NAMUR attachment it covers 7.5 to 120 mm.
03What solenoid voltages are available for 3768?
6 V DC, 12 V DC or 24 V DC, with coil resistances of 2909, 5832 and 11714 ohm at 20 C.
04Is 3768 available for hazardous areas?
Yes: 3768-1 is ATEX II 2G Ex ia IIC T6, 3768-3 has CSA and FM intrinsically safe listings, and 3768-8 is II 3G Ex nA II T6.
05Does 3768 need a switching amplifier?
Yes, the two SJ2-SN switches must be connected to switching amplifiers according to EN 60947-5-6 in the output circuit.