STT850 SmartLine temperature transmitter with universal input

The Honeywell STT850 is the field-mount, dual-compartment temperature transmitter of the SmartLine range. It accepts RTDs, thermocouples, millivolt and resistance signals on a universal input, converts them to a linearised temperature value and sends the result as 4 to 20 mA with HART, as 4 to 20 mA with Honeywell DE, or as FOUNDATION Fieldbus. A dual-input version adds a second sensor for redundant, differential, averaging or split-range measurement. Seven Star LLC supplies STT850 transmitters in Oman and the GCC as an independent supplier in Muscat.

The STT850 is the higher-performance, housing-mounted sibling of the head-mount STT700 and STT170 transmitters: it adds a digital alarm output option, an advanced graphics display and a 125 ms update time on single-input units.

STT850 technical specifications

Parameter Specification
Manufacturer / part number Honeywell / STT850 SmartLine Temperature Transmitter
Inputs Universal: RTD (2, 3, 4 wire), thermocouple, millivolt and ohm; single or dual input
Digital accuracy Pt100 ±0.10 °C; Pt1000 ±0.10 °C; Ni120 ±0.08 °C; type K ±0.25 °C; type J ±0.25 °C
D/A output accuracy ±0.005 % of span
Stability ±0.01 % of URL per year for ten years
Update time 125 ms single input; 250 ms dual input
Output and protocols 4 to 20 mA with HART 7.9 or Honeywell DE; FOUNDATION Fieldbus (ITK 6.1.2)
Supply voltage at terminals HART 11.8 to 42.4 Vdc; DE 13.8 to 42.4 Vdc; Fieldbus 9 to 32 Vdc (IS versions limited to 30 Vdc)
Isolation 2000 Vdc (1400 Vrms) between inputs and output
Ambient temperature, rated -40 to 85 °C (-40 to 185 °F); storage -55 to 120 °C
Housing and ingress Polyester-coated low-copper aluminium or dual-certified 316/316L stainless steel; Type 4X / IP66 / IP67
Cable entry 1/2 NPT or M20 x 1.5
Net weight Aluminium housing 1.22 kg with display, 1.18 kg without; stainless 2.22 kg with display
Functional safety IEC 61508 SIL 2 non-redundant, SIL 3 redundant

How the STT850 measures and diagnoses

The universal input digitises the sensor signal, applies the sensor linearisation and, for thermocouples, adds cold-junction compensation with a stated ±0.25 °C accuracy. For a calibrated platinum RTD you can enter the four Callendar-Van Dusen coefficients R0, alpha, delta and beta directly (not on DE units), which tightens the loop accuracy to the sensor calibration. Total analog accuracy is the digital accuracy plus the 0.005 % output error; for a Pt100 on a 0 to 200 °C range Honeywell gives 0.11 °C as the worked example.

With two sensors fitted, the transmitter can output the difference, the average, a redundant selection that falls back to the second sensor, or a split range. Sensor burnout is user-selectable upscale or downscale, wire break is indicated on RTD and ohm inputs, and HART and Fieldbus versions support NAMUR NE 107 extended diagnostics. Output failure levels follow either the Honeywell standard (3.8 to 20.8 mA) or NAMUR NE 43 (3.8 to 20.5 mA).

STT850 in the SmartLine system and related parts

The STT850 is tested with Experion PKS and manages through Honeywell Field Device Manager, FDM Express, SCT 3000 for DE units and the Versatilis handheld. The dual-compartment housing keeps wiring in a separate chamber from the electronics, and the temperature board, terminal board with lightning protection, electronics module and display are all field-replaceable (apart from flameproof areas, where the housing must stay closed under the approval).

For head-mounted sensors we also quote the STT700 (DIN Form A) and the STT170 series (DIN Form B head mount). Multivariable flow points use the SMV800, and tank points use the SmartLine GWR and NCR level transmitters.

STT850 selection and ordering checklist

  • Number of inputs: single (S) or dual (T). Dual input is not available for every combination of options.
  • Protocol and output: HART, DE or FOUNDATION Fieldbus. The digital-output alarm option is available on HART units only.
  • Housing and entry: aluminium or dual-certified stainless, with 1/2 NPT or M20 entries.
  • Display and buttons: none, standard LCD, or advanced graphics LCD, with or without external zero, span and configuration buttons, and the language set required.
  • Approvals: FM, CSA, ATEX, IECEx, SAEx, INMETRO, NEPSI, KOSHA, EAC or CCoE codes, and marine or SIL certificate options.
  • Configuration: factory standard or custom (tag, sensor type, range, failsafe, write protect), plus optional calibration report and extended warranty.

Installing and commissioning the STT850

Mount the STT850 on a 2 inch pipe or a wall using the stainless or zinc-plated steel bracket, and keep the conduit entries facing down to shed water. Maximum lead resistance is 50 ohms per leg for thermocouples and RTDs (10 ohms for Pt25). Loop wiring is polarity insensitive, so a reversed pair does no damage. Check the loop load against the supply: for HART the maximum load is 45.6 x (supply voltage – 11.8) ohms, and 250 ohms minimum is needed for handheld communication.

After wiring, set the sensor type, range, damping (HART 0 to 102 s, default 0.5 s) and failsafe direction, then run a loop test and a sensor simulation from the display or the handheld. For replacement units, copy the configuration from the old tag number to avoid range errors.

Typical STT850 applications in Oman and the GCC

The STT850 is used for reactor, furnace and heat-exchanger temperatures in refineries and gas plants, bearing and winding temperatures on rotating machines, and steam and feedwater temperatures in power and desalination units. The -40 to 85 °C ambient rating, IP66/IP67 enclosure and stainless housing option cope with outdoor sun load, dust and salty coastal air. Dual-sensor redundancy is popular where a single sensor failure would otherwise trip a unit.

STT850 input accuracy examples

Input Maximum range Digital accuracy
Pt100 RTD -200 to 850 °C 0.10 °C
Pt500 RTD -200 to 850 °C 0.12 °C
Type K thermocouple -100 to 1370 °C 0.25 °C
Type J thermocouple -200 to 1200 °C 0.25 °C
Type T thermocouple -200 to 400 °C 0.25 °C
Millivolt -20 to 125 mV 0.015 mV

Information to send with an STT850 RFQ

  • Number of inputs, sensor type, wiring and measuring range for each input.
  • Protocol (HART, DE or Fieldbus) and the control system host.
  • Housing material, cable entry, display and button options.
  • Hazardous-area approval, SIL or marine certificate requirement.
  • Tag list, quantity and delivery location.

Documents and quotation

A Honeywell STT850 specification (34-TT-03-14) is attached on this page and lists the approval codes, performance tables and the model selection guide. Send your full STT850 order code or the data above and we will prepare a quotation.

Seven Star LLC is an independent supplier in Muscat; delivery time and availability are confirmed per order.

Other Models in the Honeywell Smartline Stt Range

Seven Star LLC supplies models from the Honeywell Smartline Stt range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Honeywell STT850 SmartLine Temperature TransmitterTemperature InstrumentationYou are viewing this model
Honeywell STT700 SmartLine Temperature TransmitterTemperature InstrumentationView details
Honeywell STT170 Smart Temperature Transmitter (STT 3000)Temperature InstrumentationView details
Datasheets & Documents
  • PDF Datasheet Honeywell STT850 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Honeywell is the American industrial technology group whose products on this site cover gas and flame detection, pressure transmitters, flow measurement, gas metering, fire alarm systems and helicopter rotor balancing equipment. Its roots go back to a thermostat business in Minneapolis in 1885 and to Mark Honeywell's heating company, which merged with it in 1927. Several brands we list have joined Honeywell over the years: Gent fire systems of Leicester (part of Honeywell since 2005), Chadwick-Helmuth (a Honeywell business unit from 2002) and Elster gas metering (acquired around the end of 2015).

Seven Star LLC is an independent supplier in Muscat. We list Honeywell gas detectors and sensors, transmitters, Elster gas meters and flow computers, Gent fire alarm equipment and Chadwick-Helmuth balancers, and supply them and their spares in Oman and the GCC by part number.

Honeywell company profile

Origins 1885, Minneapolis (Butz thermostat business); merged with Mark Honeywell's company in 1927
Brands in our range Honeywell Analytics gas detection, SmartLine transmitters, Elster gas metering, Gent fire detection, Chadwick-Helmuth rotor track and balance
Gent Founded in Leicester, UK, around 1872 by John Thomas Gent; part of Honeywell since 2005
Elster Gas, water and electricity metering; bought by Honeywell from Melrose, deal completed around the end of 2015

Milestones

  • 1885: The Butz thermostat business starts in Minneapolis.
  • 1927: It merges with Mark Honeywell's company.
  • 2005: Gent fire detection (Leicester, UK) becomes part of Honeywell.
  • 2015: Honeywell completes the purchase of Elster from Melrose around the end of the year.

Honeywell products we list

Family Models Typical use
Fixed gas detectors Searchline Excel, Searchline Excel Plus, 02104-N-XSSA, Sensepoint XCD RTD, Sensepoint XCD IR, XCD H2, Sensepoint XCL, Sensepoint XRL, OmniPoint, RAEGuard 2 PID Flammable, toxic and VOC gas detection in process areas
Sensors, flame detection and control SR-W-MP75C LEL sensor, SR-X2V O2 sensor, FS24X Plus flame detector, R4343E flame switch, System 57 card, 5704FS panel Replacement sensors, fire detection and gas detection control panels
Transmitters and flow SmartLine STG700, STG800, STR82D remote seal, VersaFlow Coriolis Process pressure and mass flow measurement
Elster gas metering Q.Sonic plus, TRZ2, Quantometer, RABO, IRM-3 DUO, EK280, EC 350, enCore FC1, enCore ZM1, gas-net F1, gas-net D2, GasLab Q2, USM display Gas meters, volume correction and fiscal flow computing
Gent fire alarm systems Vigilon Plus, Vigilon Compact Plus, Nano, Xenex, S-Quad detector, S-Cubed, ALD302 base, S4-34420 interfaces, loop card, repeat panel, mimic panel, XENS-850 call point, 74430 bell Addressable and conventional fire alarm systems in buildings and plants
Chadwick-Helmuth rotor track and balance 8500C, 8500C Plus, Vibrex 2000, Model 11, photocell system, printer, bracket, protractor Helicopter rotor track and balance and propeller balancing

Gas detection uses two basic approaches. Point detectors such as the Sensepoint XCD measure the gas at one location, with a catalytic or infrared sensor for flammable gas and an electrochemical cell for toxic gas such as H2S. Open path detectors such as the Searchline Excel send an infrared beam across an area up to a few hundred metres long and detect a gas cloud anywhere along it. Infrared sensors cannot be poisoned the way catalytic beads can, which matters on sites with silicones or H2S.

Where Honeywell products are used

In Oman and the GCC, Honeywell gas detectors protect wellheads, gas plants, refineries and tank farms. Elster meters and flow computers measure gas at city gate stations and in industry. Gent systems are installed in commercial buildings, hospitals and hotels, and Chadwick-Helmuth balancers are used by helicopter operators.

Ordering Honeywell products: what we need

Send the part number from the label (for example 02104-N-XSSA or SPXCDASMTXF). For gas detectors, add the gas, range, output and certification. For gas meters, add size (DN), flow range and pressure rating. For Gent equipment, add the panel type and loop protocol.

Facts checked against Honeywell press releases and SEC filings, and published histories of Gent and Chadwick-Helmuth, October 2026.

FAQ

Questions about the Honeywell STT850 SmartLine Temperature Transmitter

Answers from our engineering team on installation, compatibility and integration.

01What sensors can the STT850 connect?
It has a universal input for RTDs (2, 3 or 4 wire), thermocouples, millivolt and ohm signals. A dual-input version accepts two sensors.
02How accurate is the STT850 with a Pt100?
Digital accuracy is ±0.10 °C for a Pt100, plus 0.005 % of span on the analog output. Callendar-Van Dusen coefficients can be entered for calibrated RTDs.
03Which communication options does the STT850 offer?
4 to 20 mA with HART 7.9, 4 to 20 mA with Honeywell DE, or FOUNDATION Fieldbus. The digital alarm output is available on HART units.
04Is the STT850 SIL certified?
The specification states IEC 61508 SIL 2 for non-redundant use and SIL 3 for redundant use, certified by EXIDA and TUV Nord.
05What redundancy functions does the dual-input STT850 provide?
With two sensors it supports redundant, differential, averaging and split-range measurement, and can fall back to the second sensor on a sensor break.