Brand:

Danfoss 003N3100 WVFX 20 Pressure-Operated Water Valve, G 3/4

Description

WVFX 20: a condenser water valve controlled by refrigerant pressure

Danfoss 003N3100 is a WVFX 20 pressure-operated water valve with G 3/4 internal threads, a brass body and a Kv value of 3.4 m3/h. A control line from the condenser (1/4 in, 6 mm SAE flare) acts on a bellows, and the valve opens on rising condensing pressure. The adjustable control range is 3.5 to 16 bar.

The maximum working pressure on the water side is 16 bar (232 psig), the maximum differential 10 bar, the medium temperature range -25 to 130 C and the orifice 20 mm. The refrigerant side is rated for 26.4 bar (MWP) with a test pressure of 29 bar. Approvals are C UL US Listed, EAC, PED and UA.

Technical specifications

Parameter Specification
Danfoss code number 003N3100
Type WVFX 20
Approvals as listed C UL US LISTED; EAC; PED; RoHS; RoHS China; UA
Body material Brass
Connection Internal/External Internal
Connection size (refrigerant) 1/4 in – 6 mm
Connection size 3/4
Connection standard ISO 228-1
Connection type G
Connection type (refrigerant) SAE flare
Control pressure range 3.5 bar to 16 bar
Differential pressure 10 bar
Kv value 3.4 m3/h
Max. test pressure Pe 24 bar
Maximum working pressure 16 bar
Max.test press.(refrig.) 29 bar
Media Fresh water; Neutral brine
Medium temperature range -25 C to 130 C
MWP (refrigerant) 26.4 bar
Oil free refrigerants R513A
Opening configuration Opens on rising cond. pressure
Orifice size 20 mm
Refrigerants R1234yf; R134a; R22; R404A; R407A; R407C; R407F; R407H; R422B; R422D; and others listed in the data sheet
UL approved refrigerants R134a; R22; R404A; R407A; R407C; R407F; R407H; R422B; R422D; R448A; and others listed in the data sheet
Net weight 1.166 kg
EAN 5702422042488

Condenser water regulation

A water-cooled condenser needs just enough water to hold the condensing pressure; too much wastes water, too little raises the head pressure and the power consumption. The WVFX senses the pressure in the condenser, and the water flow follows the load automatically without electricity. It works on fresh water and neutral brine.

For R513A the page lists oil-free compatibility. The valve is a member of the WVFX / WVS data sheet group, which also covers sizes 10, 15, 25, 32 and 40.

Setting and ordering notes

Set the valve with a pressure gauge on the condenser: turn the spindle to the desired condensing pressure. Install the valve on the water outlet side of the condenser, with the arrow in flow direction, and connect the control line to the condenser or the liquid line near it without liquid traps.

Confirm the refrigerant, the pressure range (3.5 to 16 bar here), the thread type (G rather than NPT) and the water quality. WVO versions with NPT threads have different codes, so confirm the thread before ordering.

Other types and sizes from the same Danfoss family that appear in the Danfoss store listing include WVFX 32 (003F1232), WVFX 40 (003F1240), WVFX 10 (003N1100), WVFX 15 (003N2100), WVFX 25 (003N2117). These are listed for orientation only; each has its own datasheet values, so check size, connection and version before ordering.

Related Danfoss products: Danfoss 027H2081 ICS3 25-10 Pilot-Operated Servo Valve, 25 mm, Danfoss 027H2308 ICSH 25 Dual-Position Servo Valve, 25 mm, Danfoss 003N8062 WVO 15 Pressure-Operated Water Valve, 1/2 NPT, Danfoss 027H7122 ICS 100 Pilot-Operated Servo Valve, 100 mm, Danfoss 034L0058 KVL 22 Crankcase Pressure Regulator, 22 mm and Danfoss 034L1075 KVP 22 Evaporator Pressure Regulator, 22 mm.

Documents and quotation

For the full drawings, ordering tables and wiring or piping details, open the attached Danfoss Pressure operated water valve, WVFX / WVS AI555732126235en-000101 (manufacturer, unaltered) (manufacturer PDF, unaltered). More items of this kind are listed under regulators. Seven Star LLC supplies from Muscat as an independent supplier: ask for a quotation on 003N3100.

Datasheets & Documents
  • PDF Datasheet Danfoss Pressure operated water valve, WVFX / WVS AI555732126235en-000101 (manufacturer, unaltered) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.

Danfoss company profile

Founded 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966)
First product Thermostatic expansion valve for refrigeration
Headquarters Nordborg, Denmark
Ownership Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family
Size About 42,000 employees (2023)
Business segments Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics)
Brands in the group VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls

Milestones

  • 1932–1933: First expansion valve; the company is founded in Nordborg.
  • 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
  • 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
  • 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
  • 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
  • 2021: Acquisition of Eaton's hydraulics business.

Choosing Danfoss products

For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.

Where Danfoss products are used

In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.

Danfoss products we list

Family Examples
Variable speed drives and soft starters VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter
Solenoid valves and coils EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil
Pressure switches and thermostats KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101
Pressure transmitters MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2
HVAC and refrigeration valves AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element

Ordering Danfoss products: what we need

Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.

Facts checked against Danfoss's company history pages and published company data, October 2026.

FAQ

Questions about the Danfoss 003N3100 WVFX 20 Pressure-Operated Water

Answers from our engineering team on installation, compatibility and integration.

01What is Danfoss 003N3100?
A WVFX 20 pressure-operated water valve with G 3/4 threads for condenser water regulation.
02What is its control range?
3.5 to 16 bar on the refrigerant control side.
03Which media can it regulate?
Fresh water and neutral brine.
04What is the Kv value?
3.4 m3/h.
05Which document is attached?
The Danfoss WVFX / WVS data sheet AI555732126235en-000101.