Description
CPCE 22: a hot-gas bypass capacity regulator with an external pilot line
Danfoss 034N0084 is a CPCE 22 hot-gas bypass regulator, a capacity regulator that opens a bypass from the discharge side to the evaporator side when the suction pressure falls below its setting. It has 22 mm (7/8 in) ODF solder connections, a 7/16-20 UNF flare connection for the pilot line and an adjustable range of 0 to 6 bar with a factory setting of 0.4 bar (5.8 psig).
The data show a maximum working pressure of 28 bar (406 psig), a test pressure of 31 bar, a differential pressure of 18 bar and a medium temperature range of -50 to 140 C. The page notes that injection uses the LG liquid-gas mixer. Approvals are C UL US Listed, EAC and UA.
Technical specifications
| Parameter | Specification |
|---|---|
| Danfoss code number | 034N0084 |
| Type | CPCE 22 |
| Approvals as listed | C UL US LISTED; EAC; RoHS; RoHS China; UA |
| Differential pressure | 18 bar |
| Factory setting | 0.4 bar |
| Inlet connection type | Solder, ODF |
| Inlet size | 7/8 in / 22 mm |
| Maximum test pressure | 31 bar |
| Maximum working pressure | 28 bar |
| Medium temperature range | -50 C to 140 C |
| Outlet connection type | Solder, ODF |
| Outlet size | 7/8 in / 22 mm |
| Pilot line conn. size | 7/16 in – 20 UNF |
| Pilot line connection type | Flare |
| Rated cap. conditions | Delta ts=4K; tcond=30 C; tevap=-10 C |
| Rated capacity R404A/R507A | 32 kW |
| Rated capacity R134a | 15.2 kW |
| Rated capacity R22 | 34 kW |
| Rated capacity R407C | 37.1 kW |
| Refrigerants | R1234ze(E); R1270; R134a; R22; R290; R404A; R407A; R407C; R407F; R407H; and others listed in the data sheet |
| Regulation range | 0 bar to 6 bar |
| UL approved refrigerants | R134a; R22; R404A; R407A; R407C; R407F; R407H; R448A; R449A; R449B; and others listed in the data sheet |
| Net weight | 0.85 kg |
| EAN | 5702422020578 |
Capacity regulation with hot gas
When the cooling load falls the compressor may drop its suction pressure and cycle or run into a vacuum. By bypassing hot gas to the low side, the CPCE keeps the suction pressure up and holds the compressor running, avoiding frequent starts. The LG mixer injects liquid into the hot gas so that the bypassed gas arrives as a controlled-temperature mixture.
The capacity at the rating conditions (4 K superheat, 30 C condensing, -10 C evaporating) is 32 kW on R404A/R507A, 15.2 kW on R134a, 34 kW on R22 and 37.1 kW on R407C. Check the data sheet for the capacity curves with the actual conditions before sizing.
Installation and ordering notes
The external pilot line connects the downstream (evaporator side) pressure to the regulator through the flare fitting; fit it with a short line, avoiding traps. Install with the arrow in the flow direction and set the pressure with a gauge. Mind the compressor discharge temperature when large bypass flows are used.
Confirm the refrigerant, the setting range, the connection size and the mixer type before ordering. The same data sheet covers CPCE and LG, and the customer part number 00A426 is shown on the product page.
Related Danfoss products: Danfoss 027H2308 ICSH 25 Dual-Position Servo Valve, 25 mm, Danfoss 027H2081 ICS3 25-10 Pilot-Operated Servo Valve, 25 mm, Danfoss 034L0058 KVL 22 Crankcase Pressure Regulator, 22 mm, Danfoss 034L1075 KVP 22 Evaporator Pressure Regulator, 22 mm and Danfoss 148H3402 ORV 40 Oil Temperature Regulating Valve, 40 mm.
Documents and quotation
For the full drawings, ordering tables and wiring or piping details, open the attached Danfoss Hot gas bypass regulator, CPCE and LG AI557421637476en-000101 (manufacturer, unaltered) (manufacturer PDF, unaltered). More items of this kind are listed under regulators. Seven Star LLC supplies from Muscat as an independent supplier: ask for a quotation on 034N0084.
Datasheets & Documents
- Datasheet Danfoss Hot gas bypass regulator, CPCE and LG AI557421637476en-000101 (manufacturer, unaltered) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.
Danfoss company profile
| Founded | 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966) |
|---|---|
| First product | Thermostatic expansion valve for refrigeration |
| Headquarters | Nordborg, Denmark |
| Ownership | Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family |
| Size | About 42,000 employees (2023) |
| Business segments | Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics) |
| Brands in the group | VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls |
Milestones
- 1932–1933: First expansion valve; the company is founded in Nordborg.
- 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
- 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
- 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
- 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
- 2021: Acquisition of Eaton's hydraulics business.
Choosing Danfoss products
For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.
Where Danfoss products are used
In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.
Danfoss products we list
| Family | Examples |
|---|---|
| Variable speed drives and soft starters | VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter |
| Solenoid valves and coils | EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil |
| Pressure switches and thermostats | KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101 |
| Pressure transmitters | MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2 |
| HVAC and refrigeration valves | AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element |
Ordering Danfoss products: what we need
Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.
Facts checked against Danfoss's company history pages and published company data, October 2026.
Browse Danfoss products by category: AC Drives, Pressure Instrumentation, Control Valves, Solenoid Valve.
Related products
Frequently Asked Questions
A CPCE 22 hot-gas bypass capacity regulator with 22 mm (7/8 in) ODF connections.
It bypasses hot gas to the low-pressure side to hold suction pressure when the load falls.
0 to 6 bar; factory setting 0.4 bar (5.8 psig).
Yes, a 7/16-20 UNF flare connection is provided for the pilot line.
The Danfoss CPCE and LG hot gas bypass regulator data sheet AI557421637476en-000101.