ABB S201-C50 1P MCB 50 A C Curve, S200
Description
ABB S201-C50 1P miniature circuit breaker, 50 A curve C
The ABB S201-C50 is a single-pole miniature circuit breaker from the System pro M compact S200 range, rated 50 A with a C tripping characteristic. It protects cables and equipment against overload through a delayed thermal release and against short circuit through an electromagnetic release, and it is current limiting. The ABB type code is S201-C50 and the order code is 2CDS251001R0504. It is built for residential, commercial and industrial installations, with a rated short-circuit capacity Icn of 6 kA under IEC/EN 60898-1 and an ultimate breaking capacity Icu of 10 kA under IEC/EN 60947-2.
In use the ABB S201-C50 switches one live conductor of a single-phase circuit, or one phase of a three-phase distribution board. A single-phase 230 V load drawing 50 A corresponds to roughly 11.5 kW at unity power factor; the breaker is sized to the cable first and to the load second.
How to read the S201-C50 type designation
The S200 type code works like a short specification, which makes comparing alternatives quick when a drawing or a bill of quantities lists only the code.
| Code group | Meaning in S201-C50 |
|---|---|
| S201 | S200 family, 1P (single-pole) |
| C | Tripping characteristic C, magnetic release at 5 to 10 times In |
| 50 | Rated current In = 50 A |
The characteristic letter is the most commonly mis-ordered part of the code. Curve B (3 to 5 times In) trips earlier and suits long cable runs, while curve D (10 to 20 times In) tolerates heavier inrush such as transformers. Order S201-C50 only when the cable calculation and the load justify a C curve.
S201-C50 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | ABB / S201-C50 |
| Order code | 2CDS251001R0504 |
| Series | System pro M compact S200 |
| Number of poles | 1P (single-pole) |
| Tripping characteristic | C; magnetic release 5 to 10 times In (250 to 500 A) |
| Rated current In | 50 A |
| Rated frequency | 50 / 60 Hz |
| Rated operational voltage Un (IEC/EN 60898-1) | 1P: 230/400 V AC |
| Rated short-circuit capacity Icn | 6 kA |
| Rated operational voltage Ue (IEC/EN 60947-2) | 230 V AC |
| Rated ultimate short-circuit breaking capacity Icu | 10 kA |
| Rated service short-circuit breaking capacity Ics | 7.5 kA |
| Rated insulation voltage Ui | 440 V AC (phase to phase) |
| Rated impulse withstand voltage Uimp | 4 kV (1.2/50 µs) |
| Reference temperature for tripping characteristic | 55 °C (IEC/EN 60947-2) |
| Standards | IEC/EN 60898-1, IEC/EN 60947-2, UL 1077 |
| UL / CSA rated voltage | 480Y/277 V AC, 60 V DC |
| Terminal cross-section, solid / stranded | up to 35 mm² |
| Terminal cross-section, flexible | up to 25 mm² |
| Tightening torque | 2.8 Nm |
| Busbar cross-section | 10 mm² |
| Pole dimensions (H x D x W) | 88 x 69 x 17.5 mm per pole |
| Width of the 1P | 17.5 mm |
| Mounting | 35 mm DIN rail (EN 60715), any mounting position |
| Weight per piece (catalog) | 0.125 kg |
| Degree of protection | IP20; IP40 in an enclosure with cover |
| Ambient temperature | -25 to +55 °C |
| Storage temperature | -40 to +70 °C |
| Mechanical endurance | 20,000 operations |
| Electrical endurance (AC) | 10,000 operations |
How the S201-C50 protects the circuit
Two mechanisms work together. A bimetal element heats in proportion to the current and bends slowly when the load stays above 50 A, so a modest overload is tolerated for a while and a larger one trips sooner. For a short circuit, an electromagnetic release acts without delay; for this breaker that is a magnetic release that acts at 5 to 10 times In, which for 50 A is 250 to 500 A. Between the two regions the breaker follows the time-current characteristic published for the S200 series.
A red and green contact position indicator on the toggle shows the real contact state, the toggle can be sealed, and the breaker opens quickly enough to limit the energy let through during a fault, which reduces thermal and mechanical stress on cables and busbars.
Choosing curve C for the S201-C50
ABB positions the C characteristic for protection of resistive and inductive loads with low inrush. Typical uses are general lighting, socket outlets, small motors with moderate starting current, heaters, control-panel supplies and most commercial and industrial final circuits.
Curve B (3 to 5 times In) trips earlier and suits long cable runs, while curve D (10 to 20 times In) tolerates heavier inrush such as transformers. The magnetic threshold of this 50 A breaker is 250 to 500 A, so the available short-circuit current at the far end of the cable must exceed the upper figure for the instantaneous trip to be certain. This is the check that decides between curves on long or high-impedance circuits.
Selection and ordering checklist for the S201-C50
- Confirm the pole count: single-pole for one live conductor of a single-phase circuit, or one phase of a three-phase distribution board.
- Confirm the rated current against the cable cross-section and installation method, not only the load.
- Confirm the characteristic letter (C) against the starting or inrush current of the load.
- Check that the prospective short-circuit current at the board does not exceed the 6 kA Icn / 10 kA Icu of this version; the S200 M and S200 P versions cover higher levels.
- Allow 17.5 mm of DIN-rail width and note the -25 to +55 °C ambient range.
- List any auxiliary or signal contacts, shunt trips or motor operators that will be fitted to the S200 range alongside it.
Installation, commissioning and maintenance
The S201-C50 snaps onto a 35 mm DIN rail with a fast clip and can be mounted in any position. The bi-directional cylinder-lift terminals accept conductors up to 35 mm² solid or stranded and 25 mm² flexible, and a busbar slot takes 10 mm² busbar. Tighten the terminal screws to 2.8 Nm with a No. 2 Pozidrive screwdriver and re-check after the first thermal cycle, because loose terminals are a common cause of heating in distribution boards.
After installation, operate the toggle to confirm the position indicator changes between red and green, test downstream circuits before energising, and record the rating in the circuit schedule. In service, a periodic thermal scan of the terminals and a manual operation once a year help to detect deterioration early. If the breaker trips, find and correct the cause before resetting; repeated resets on a fault are a safety risk.
Typical applications in Oman and the GCC
Distribution boards in Oman and the GCC work in high ambient temperatures, dust and, near the coast, humid and salty air. The S200 range is specified for -25 to +55 °C and damp-heat cycling, so the S201-C50 fits final-circuit and sub-distribution duties in commercial buildings, hotels, hospitals, industrial plants, utilities, oil and gas support facilities and water and desalination sites. Single-pole units are common for lighting and socket final circuits and as per-phase protection of small loads.
In hot panels the thermal trip point moves with temperature, and ABB gives a reference temperature for the tripping curve (55 °C for this characteristic). A board that runs well above it may need breakers derated or a larger, better ventilated enclosure. Group several breakers side by side only after checking the derating guidance for the board.
Related S200 breakers and variants
The same rated current and characteristic is available in other pole counts: S202-C50, S203-C50, S204-C50. Within the single-pole family you can step to a neighbouring rating if the cable or load changes, or to another characteristic (B, D, K, Z) for the same current. The S200 M and S200 P versions cover higher fault levels.
| Characteristic | Magnetic trip | Intended duty |
|---|---|---|
| B | 3 to 5 times In | Long cable runs, people and cable protection |
| C | 5 to 10 times In | Resistive and inductive loads, low inrush |
| D | 10 to 20 times In | High inrush, transformers, lamps |
| K | Higher than C, see ABB curves | Motors, transformers, auxiliary circuits |
| Z | 2 to 3 times In | Electronic circuits |
Information to send with an RFQ
To confirm availability and lead time for the S201-C50, send the exact type code, the quantity, the delivery location and the required delivery date. If the breaker is part of a board, add the pole count, rated current, characteristic and any accessories, so one order covers the full set. A photo of the nameplate of an existing breaker helps avoid a mismatch on older installations.
Documents and quotation
The official ABB data sheet for the S 200 series (document 2CDC002157D0202, English) is attached on this page as a PDF and applies to the ABB S201-C50. It covers the full System pro M compact S 200 and S 200 M range: tripping characteristics B, C, D, K and Z, rated currents from 0.5 to 63 A, breaking capacity to IEC/EN 60898-1 and IEC/EN 60947-2, UL 1077 data, terminal capacity, accessories and dimension drawings. Check the rating and the characteristic against your circuit before ordering, then send us the quantity and the delivery location for a quotation.
Quotations are prepared on request, with the technical details above matched to your specification.
Other Models in the Abb S200 Mcb Range
Seven Star LLC supplies models from the Abb S200 Mcb range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
Datasheets & Documents
- Datasheet ABB S 200 / S 200 M Miniature Circuit Breaker Data Sheet (PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Frequently requested ABB models: ABB FENA-21 Two-Port Ethernet Adapter Module, ABB AHM550.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB S201-C50 1P MCB 50 A C Curve, S200
Answers from our engineering team on installation, compatibility and integration.
01What does the S201-C50 code mean?
S201 identifies the S200 family in a single-pole version, C is the C tripping characteristic and 50 is the rated current in amperes. The ABB order code is 2CDS251001R0504.
02How does the S201-C50 trip on a short circuit?
The curve C electromagnetic release acts at 5 to 10 times In, which for 50 A is 250 to 500 A. Below that range the thermal release handles overloads with a time delay.
03What breaking capacity does the S201-C50 have?
The rated short-circuit capacity Icn is 6 kA under IEC/EN 60898-1. Under IEC/EN 60947-2 the ultimate breaking capacity Icu is 10 kA and the service capacity Ics is 7.5 kA.
04How wide is the S201-C50 on the DIN rail?
Each pole is 17.5 mm wide, so the 1P measures 17.5 mm. It mounts on a 35 mm DIN rail with a fast clip and can be installed in any position.
05Which conductors fit the S201-C50 terminals?
The terminals accept up to 35 mm² solid or stranded and 25 mm² flexible conductors, with a recommended tightening torque of 2.8 Nm. A busbar slot takes 10 mm² busbar.