ABB ACS580-04-880A-4 Drive Module 500 kW 880 A
Description
Where the ACS580-04-880A-4 fits
ACS580-04-880A-4 is the open-chassis ACS580-04 module that ABB rates at 500 kW and 400 V. Frame R11 holds the 880 A, 500 kW power stage. Typical jobs are large process fans and main drives built into switchrooms. Safe Torque Off, the intuitive control panel with USB connection and a panel mounting platform are standard on the module.
Technical specifications
| Parameter | Specification |
|---|---|
| Type designation | ACS580-04-880A-4 |
| Product family | ACS580-04, drive module (IP00, for cabinet installation) |
| Supply voltage | 3-phase 380 to 415 V (400 V table) |
| Nominal rating | 500 kW, 880 A |
| Light-overload rating | 865 A = 500 kW |
| Heavy-duty use | 400 kW, 725 A (140% overload) |
| Maximum output current | 1100 A |
| Frame size | R11 |
| IP00 size (H x W x D) | 1662 x 350 x 529 mm |
| Module mass | 200 kg |
| UL rating at 460 to 480 V | 807 A light-overload, 700 Hp |
| UL heavy duty at 480 V | 625 A, 500 Hp |
| Air flow | 1420 m3/h |
| Maximum noise level | 72 dBA |
| Input fuses | See hardware manual 3AXD50000015497 |
| Safety | Safe Torque Off (SIL 3) |
Duty classes, protection and cooling
Two duty classes apply: light overload at 865 A and 500 kW, heavy duty at 725 A and 400 kW. Maximum output current is 1100 A. Overload capability: 110% in light-overload use, 140% in heavy duty, each for 1 minute per 10 minutes at 40 degrees C. On a 460 to 480 V network ABB gives 807 A (700 Hp) light-overload and 625 A (500 Hp) heavy duty. Variable-torque loads such as pumps and fans normally use the light-overload column.
The module dissipates 10500 W (36126 BTU/h) and needs 1420 m3/h of cooling air with a maximum noise level of 72 dBA. Fuse sizes and types for the R10 and R11 modules are given in the ACS580 hardware manual 3AXD50000015497, not in the catalogue, so check them there. Rated at +40 degrees C in an enclosure of IP00 or IP20.
The IP00 chassis measures 1662 x 350 x 529 mm and has a mass of 200 kg. Two construction options exist: +B051 for IP20 shrouds and +H370 for full-size input terminals.
Ordering code and options
Read ACS580-04-880A-4 as series ACS580, construction 4 (drive module), size 880A-4 where the digits are the nominal current, and voltage code 4 for 380 to 480 V. ABB’s option list includes +K462 for FCNA-01 ControlNet, +K469 for FECA-01 EtherCAT, +K475 for FENA-21 EtherNet/IP, Modbus TCP and PROFINET IO. The EMC category C2 is fulfilled by wall-mounted drives and cabinet-built drives up to frame R9; modules and R10 to R11 cabinets meet C3. The brake chopper is not built into the module; external braking equipment is used where needed.
Related ABB products: ABB ACH580-04-585A-4 HVAC Drive Module 315 kW 585 A, ABB ACS580-01-106A-4 AC Drive 55 kW 106 A, ABB ACS580-01-039A-4 AC Drive 18.5 kW 38 A, ABB ACH580-01-088A-4 HVAC AC Drive 45 kW 88 A, ABB ACS580-01-033A-4 AC Drive 15 kW 32 A and ABB ACS580-01-062A-4 AC Drive 30 kW 62 A.
Datasheet and quotation
Values on this page come from ABB’s ACS580 catalogue (3AUA0000145061, revision G) and the ABB product page for the ACS580-04-880A-4; the catalogue is linked here. To request the ACS580-04-880A-4, send Seven Star LLC the motor data and supply details; availability is given in the quotation. Before ordering, check the exact code and options, the motor rating, braking needs and site derating in the ACS580 hardware manuals. For the ACS580-04-880A-4, tell us the application, the cable lengths, the ambient temperature and the installation altitude so derating can be checked before the offer is issued. Other sizes are listed in AC drives, and the family introduction is on the ABB ACS580 page.
Datasheets & Documents
- Catalog ABB general purpose drives ACS580 catalog 3AUA0000145061 (Rev G) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.
ABB company profile
| Formed | 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50% |
|---|---|
| ASEA | Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators |
| Brown, Boveri & Cie | Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri |
| Headquarters | Zurich, Switzerland; ABB Ltd became the group holding company in 1999 |
| Ownership | Public company listed on SIX Swiss Exchange and Nasdaq Stockholm |
| Brands in the group | Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers |
| Product families | Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots |
Milestones
- 1883: ASEA is founded in Västerås, Sweden.
- 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
- 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
- 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
- 2011 and 2017: Baldor Electric and B&R join ABB.
- 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.
Choosing an ABB drive
ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.
Where ABB products are used
In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.
ABB products we list
| Family | Examples |
|---|---|
| AC drives | ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module |
| Breakers, motor control and protection | SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay |
| Flow measurement | ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500 |
| Pressure, temperature and level | 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge |
| Analysers | Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210 |
| Control systems and actuators | AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000 |
Ordering ABB products: what we need
Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.
Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.
FAQ
Questions about the ABB ACS580-04-880A-4 Drive Module 500 kW 880 A
Answers from our engineering team on installation, compatibility and integration.
01What are the duty ratings of the ACS580-04-880A-4?
ABB lists 880 A nominal (500 kW), 865 A (500 kW) light overload, 725 A (400 kW) heavy duty and 1100 A maximum output current.
02What construction is the ACS580-04-880A-4?
It is the ACS580-04 drive module in frame R11, delivered as an IP00 chassis for cabinet installation.
03How much heat does the ACS580-04-880A-4 produce?
The catalogue gives 10500 W of heat dissipation, 1420 m3/h of air flow and 72 dBA of noise.
04Does the ACS580-04-880A-4 include Safe Torque Off?
Yes. Safe Torque Off (SIL 3) is part of the standard drive according to the ACS580 catalogue.
05Which fieldbus options fit the ACS580-04-880A-4?
The catalogue lists FDNA-01, FPBA-01, FCAN-01, FSCA-01, FCNA-01, FECA-01, FEPL-02, FENA-11 and FENA-21 adapters; Modbus RTU is built in.