Brand:

ABB ACS580-07-0145A-4 Cabinet Drive 75 kW 145 A

Description

A 75 kW ACS580 on a 400 V supply

ABB lists the ACS580-07-0145A-4 as a ready-built ACS580 drive cabinet on a 400 V network. Frame R6 holds the 145 A, 75 kW power stage. Typical jobs are pumps and fans needing no panel design and retrofit jobs where a finished unit saves site time. Safe Torque Off and the intuitive control panel with its mounting platform are standard in the cabinet.

Technical specifications

Parameter Specification
Type designation ACS580-07-0145A-4
Product family ACS580-07, cabinet-built general purpose drive
Supply voltage 3-phase 380 to 415 V (400 V table)
Nominal rating 75 kW, 145 A
Light-overload rating 138 A = 75 kW
Heavy-duty rating 105 A = 55 kW; 150% for 1 min per 10 min
Maximum output current 178 A
Frame size R6
Cabinet size (H x W x D) 2145 x 430 x 673 mm
Cabinet mass 210 kg
480 V light-overload 124 A, 100 Hp
480 V heavy duty 96 A, 75 Hp
Power loss 1827 W
Input fuses 250 (170M3816D), UL 250 A (DFJ-250)

Ratings and motor matching of the ACS580-07-0145A-4

From the ratings table: nominal 145 A / 75 kW, light overload 138 A / 75 kW, heavy duty 105 A / 55 kW, Imax 178 A. The overload definitions are 110% (light) and 150% (heavy duty) for one minute every ten minutes at 40 degrees C. On a 460 to 480 V network ABB gives 124 A (100 Hp) light-overload and 96 A (75 Hp) heavy duty. Use the light-overload column for pumps and fans and the heavy-duty column for constant-torque loads.

The catalogue names 170M3816D 250 A fuses for IEC and DFJ-250 250 A for UL. Plan for 1827 W of heat in the electrical room; noise is 67 dBA at full fan speed. Cabinet-built drives are offered up to IP54 according to the application notes in the catalogue.

The cabinet for frame R6 is 2145 mm high, 430 mm wide and 673 mm deep and weighs 210 kg. Panel design, fusing and wiring are done by ABB, which shortens engineering time on site.

Ordering code and options

The designation splits into ACS580, 7 (cabinet-built drive), the 145 A size and 4 for 380 to 480 V. Fieldbus and I/O options include +K475 for FENA-21 EtherNet/IP, Modbus TCP and PROFINET IO, +L501 for CMOD-01 external 24 V and relays, +L523 for CMOD-02 with isolated PTC interface. EMC: C2 for wall-mounted drives and cabinets up to frame R9, C3 for modules and the R10 to R11 cabinets. The built-in brake chopper is limited to frame R3, so the cabinet needs an external chopper for braking.

Related ABB products: ABB ACS580-01-145A-4 AC Drive 75 kW 145 A, ABB ACQ580-01-145A-4 Water Drive 75 kW 145 A, ABB ACH580-01-145A-4 HVAC AC Drive 75 kW 145 A, ABB ACS550-01-015A-4 AC Drive 7.5 kW 15.4 A, ABB ACS580-01-018A-4 AC Drive 7.5 kW 17 A and ABB ACS580-01-046A-4 AC Drive 22 kW 45 A.

Documentation and ordering

The ratings, dimensions, fuses and heat loss were read from ABB’s ACS580 catalogue 3AUA0000145061 (revision G, linked) and ABB’s page for the ACS580-07-0145A-4. Seven Star LLC supplies the ACS580-07-0145A-4 on request from Muscat; availability and lead time are stated in the quotation. Please confirm type code, options, motor data and ambient conditions before ordering; the catalogue revision may be newer than the linked one. Send the motor nameplate, supply data, control interface and fieldbus requirement for the ACS580-07-0145A-4 so that the offer lists exactly the plus codes that are needed. Other sizes are listed in AC drives, and the family introduction is on the ABB ACS580 page.

Datasheets & Documents
  • PDF Catalog ABB general purpose drives ACS580 catalog 3AUA0000145061 (Rev G) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

ABB is the Swiss-Swedish engineering group for electrification and automation: low voltage drives, motors, circuit breakers and motor control, process instruments and analysers, control systems and robots. It was formed on 5 January 1988 by the merger of two older companies. ASEA was founded in Västerås, Sweden, in 1883 by Ludvig Fredholm to make electric lighting and generators. BBC Brown Boveri was founded in Baden near Zurich in 1891 by Charles E. L. Brown and Walter Boveri. ABB Ltd is incorporated in Switzerland, headquartered in Zurich and listed on the SIX Swiss Exchange and Nasdaq Stockholm.

ABB company profile

Formed 5 January 1988, by the merger of ASEA (Sweden) and BBC Brown Boveri (Switzerland), each holding 50%
ASEA Founded 1883 in Västerås, Sweden, by Ludvig Fredholm; first products electric lighting and generators
Brown, Boveri & Cie Founded 1891 in Baden, Switzerland, by Charles E. L. Brown and Walter Boveri
Headquarters Zurich, Switzerland; ABB Ltd became the group holding company in 1999
Ownership Public company listed on SIX Swiss Exchange and Nasdaq Stockholm
Brands in the group Baldor (US motors, acquired 2011), B&R (machine automation, acquired 2017), K-TEK level instruments, Endura and Navigator analysers, SACE breakers
Product families Low and medium voltage drives (ACS series), motors, SACE Tmax and Emax breakers, contactors and soft starters, flow, pressure, temperature and level instruments, liquid and gas analysers, Contrac actuators, AC500 PLCs, Ability System 800xA and S800 I/O, protection relays, robots

Milestones

  • 1883: ASEA is founded in Västerås, Sweden.
  • 1891: Brown, Boveri & Cie is founded in Baden, Switzerland.
  • 1987–1988: The merger is announced on 10 August 1987; ABB Asea Brown Boveri starts operating on 5 January 1988.
  • 1999: ABB Ltd, incorporated in Switzerland, becomes the single holding company of the group.
  • 2011 and 2017: Baldor Electric and B&R join ABB.
  • 2020: ABB sells its power grids business to Hitachi, focusing on electrification, motion, process and machine automation.

Choosing an ABB drive

ABB's ACS drive codes are easy to read once you know the pattern. In ACS580-01-046A-4, "ACS580" is the drive family, "01" means a wall-mounted single drive, "046A" is the rated output current (about 46 A) and "-4" means a 380–480 V supply. The family is chosen by application: ACS355 for compact machinery, ACS310 for simple pumps and fans, ACS580 as the general-purpose drive, ACQ580 for water and wastewater with pump functions such as pipe fill and dry-run protection, and ACS880 for heavy industrial duty with direct torque control. Size the drive on the motor's full-load current, not only its kW rating, and allow derating for the high ambient temperatures common in Gulf electrical rooms.

Where ABB products are used

In Oman and the GCC, ABB drives and motors run pumps, fans and compressors in water and wastewater plants, district cooling, oil and gas and industry. ABB flowmeters, level instruments and analysers are used in water utilities, power and desalination plants and refineries, and SACE breakers protect switchboards in buildings and plants.

ABB products we list

Family Examples
AC drives ACS580, ACS580-01-046A-4, ACQ580, ACS355, ACS310, ACS880-01, FEN-31 encoder module
Breakers, motor control and protection SACE Tmax XT, XT3N 250, SACE Emax 2, AF09 contactor, PSR soft starter, REM615 relay
Flow measurement ProcessMaster FEP300, AquaMaster4, CoriolisMaster FCB430, VortexMaster FSV430, SwirlMaster FSS430, OriMaster FPD500
Pressure, temperature and level 266DRH, 267CS multivariable, TTH300, K-TEK AT100, LMT200, MT5000 GWR, KM26 gauge
Analysers Endura AZ20, AK100 hydrogen purity, Navigator AW641 silica, AW402 chlorine, AWT210
Control systems and actuators AC500, AC500-S, S800 AI810, AC 800F SA 811F, Contrac RSD50, Contrac RHD4000

Ordering ABB products: what we need

Send the full type code from the nameplate (for example ACS580-01-046A-4 or 266DSH...) and, for spare parts, the ABB ID number (such as 3BSE008508R1 or 1SBL176001R3010). For drives, add the motor power and current and any option codes (+...). For instruments, send the complete order code, which sets range, materials and approvals. Baldor motors are listed on their own brand page.

Facts checked against ABB company filings and published histories of ASEA and Brown, Boveri & Cie, October 2026.

FAQ

Questions about the ABB ACS580-07-0145A-4 Cabinet Drive 75 kW 145 A

Answers from our engineering team on installation, compatibility and integration.

01What are the duty ratings of the ACS580-07-0145A-4?
ABB lists 145 A nominal (75 kW), 138 A (75 kW) light overload, 105 A (55 kW) heavy duty and 178 A maximum output current.
02What construction is the ACS580-07-0145A-4?
It is the ACS580-07 cabinet-built drive in frame R6, a ready-made cabinet 2145 mm high.
03How much heat does the ACS580-07-0145A-4 produce?
The catalogue gives 1827 W of heat dissipation and 67 dBA of noise.
04Does the ACS580-07-0145A-4 include Safe Torque Off?
Yes. Safe Torque Off (SIL 3) is part of the standard drive according to the ACS580 catalogue.
05Which fieldbus options fit the ACS580-07-0145A-4?
The catalogue lists FDNA-01, FPBA-01, FCAN-01, FSCA-01, FCNA-01, FECA-01, FEPL-02, FENA-11 and FENA-21 adapters; Modbus RTU is built in.